Plan Review Details - Permit 08020653
Plan Review Stops For Permit 08020653
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-08-07 Cont ID  
Sent By shill Date 2008-08-07 Time 11:39 Rev Time 0.00
Received By shill Date 2008-08-07 Time 11:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-07-21 Cont ID  
Sent By shill Date 2008-07-21 Time 14:57 Rev Time 0.00
Received By shill Date 2008-07-21 Time 14:57 Sent To  
Notes
2008-07-21 14:58:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LISTS:
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 2ND REVIEW - PRODUCT APPROVALS WERE NOT SUBMITTED. THIS
 IS REQUIRED FOR ALL COMPONENTS AND CLADDING, WHICH
 WOULD INCLUDE WALL PANELS, ROOF COMPONENTS & CLADDING
 (ROOF COVER, NOT DECK UNLESS THE DECK IS ALSO ACTING AS
 ROOF COVER), LOUVERS IF NEW LOUVERS ARE INSTALLED.
  
 3RD REVIEW - SOMEONE WROTE "TOWN & COUNTY 5 RIB ROOF
 PANELS SEE ATTTACHED PROD APPROVAL" ON A PHOTOCOPY OF A
 PORTION OF THE ROOF PLAN.NO PRODUCT APPROVALS WERE
 SUBMITTED.PLEASE PRINT THE PRODUCT APPROVAL ALONG
 WITH ALL ASSOCIATED DOCUMENTS (EVALUATION REPORT,
 INSTALLATION INSTRUCTIONS) FROM THE WEBSITE
 WWW.FLORIDABUILDING.ORG.THE ENGINEER IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3 (SHOP DRAWING REVIEW
 STAMP OR LETTER OR INCORPORATE REFERENCE INTO SIGNED
 AND SEALED PLAN).
  
 4TH REVIEW - PLEASE PROVIDE PRODUCT APPROVALS AS
 REQUIRED.WWW.FLORIDABUILDING.ORG OR
 WWW.BUILDINGCODEONLINE.COM
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 08:52 Rev Time  
Received By shill Date 2008-06-30 Time 16:30 Sent To  
Notes
2008-07-01 08:52:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2ND REVIEW - SHEET S3, SHOWING LOCATION OF
 IMPROVEMENTS, IS PREPARED BY AN ENGINEER BUT NOT
 SIGNED, SEALED, AND DATED.THE PERMIT IS TO CLEARLY
 SHOW SCOPE OF WORK; THEREFORE A LOCATION PLAN IS
 REQUIRED.THIS SHOULD BE DONE BY THE DESIGNER OF
 RECORD OR DELEGATED ENGINEER.IF DONE BY A DELEGATED
 ENGINEER, IT SHOULD BE REVIEWED BY ENGINEER OF RECORD.
  
 IT IS NOT CLEAR WHICH OF THE MECHANICAL ROOMS ARE TO BE
 INCLUDED IN THIS PERMIT.S3 IS A ROOF FRAMING PLAN
 SHOWING THE FRAMING FOR THE ENTIRE ROOF.PLEASE
 CLARIFY SCOPE OF WORK ON THE PLAN.
  
 3RD REVIEW - SAME ROOF PLAN SUBMITTED.PROVIDE AN
 OVERALL ROOF PLAN WHICH CLEARLY SHOWS LOCATION OF
 PROPOSED REPAIRS.DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS FS471, FS481.
  
 2.ADDRESSED.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 2ND REVIEW - PRODUCT APPROVALS WERE NOT SUBMITTED.
 THIS IS REQUIRED FOR ALL COMPONENTS AND CLADDING, WHICH
 WOULD INCLUDE WALL PANELS, ROOF COMPONENTS & CLADDING
 (ROOF COVER, NOT DECK UNLESS THE DECK IS ALSO ACTING AS
 ROOF COVER), LOUVERS IF NEW LOUVERS ARE INSTALLED.
  
 3RD REVIEW - SOMEONE WROTE "TOWN & COUNTY 5 RIB ROOF
 PANELS SEE ATTTACHED PROD APPROVAL" ON A PHOTOCOPY OF A
 PORTION OF THE ROOF PLAN.NO PRODUCT APPROVALS WERE
 SUBMITTED.PLEASE PRINT THE PRODUCT APPROVAL ALONG
 WITH ALL ASSOCIATED DOCUMENTS (EVALUATION REPORT,
 INSTALLATION INSTRUCTIONS) FROM THE WEBSITE
 WWW.FLORIDABUILDING.ORG.THE ENGINEER IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3 (SHOP DRAWING REVIEW
 STAMP OR LETTER OR INCORPORATE REFERENCE INTO SIGNED
 AND SEALED PLAN).
  
 4-6. ADDRESSED.
  
 7. THE ORIGINAL PERMIT PACKAGE WAS NOT SUBMITTED.OLD
 SHEETS ARE TO BE SUBMITTED FOR REFERENCE, AND THE
 PERMIT APPLICATION IS REQUIRED FOR PERMIT ISSUANCE.
  
 3RD REVIEW, THE ORIGINAL PERMIT PACKAGE WAS NOT
 SUBMITTED.WHEN RESUBMITTING, PICK UP THE ORIGINAL
 PERMIT PACKAGE FROM THE FRONT DESK.PROVIDE TWO
 IDENTICAL, COLLATED SETS OF PERMIT DOCUMENTS.OLD
 SHEETS ARE TO BE MARKED "VOID" AND SUBMITTED FOR
 REFERENCE.THIS WAS DONE FOR THIS REVIEW AS A
 COURTESY, BUT DUE TO WORK LOAD WE ARE UNABLE TO DO THIS
 FOR EVERY PERMIT.
  
 8.ADDRESSED.
  
 9.EXISTING CONDITIONS NOT CLEAR.SEE ENGINEERING
 CALCS SHEET 3 AND ROOF FRAMING PLAN SHEET S3 (PREPARED
 BY DE BRITT & ASSOCIATES ENGINEERS).IT APPEARS THAT
 ADDITIONAL FRAMING MEMBERS WERE ADDED GRAPHICALLY.THE
 ALTERED PLAN SHOWS ROOF BEAMS WHICH ARE CONSISTENT WITH
 SHEET 3 OF CALCS.SHEET 3 STATES THAT 9.75' SPAN DOES
 NOT WORK FOR COMPONENT & CLADDING WIND PRESSURES, AND
 NEW DECK SPAN IS 4.8'.THE EXISTING PLAN APPEARS TO
 SHOW ONE ROOF FRAMING MEMBER IN THE CENTER, WHICH DOES
 NOT APPEAR ON THE NEW PLAN.DOES THIS GET REMOVED? SEE
 SHEET S1 PREPARED BY PBSJ, WHICH STATES "3ALL STEEL
 BEAMS ARE EXISTING".IT IS NOT CLEAR WHY S1 SHOWS THE
 ROOF FRAMING AS EXISTING AND NO CHANGES TO BE DONE, BUT
 THE CALCS SHEET 03 SHOW THAT A TOTAL OF 8 ROOF JOISTS
 ARE TO BE INSTALLED (EXISTING FRAMING HAS ONLY 3).IT
 IS NOT CLEAR WHY THE CALCS WOULD INDICATE THAT
 ADDITIONAL REINFORCEMENT IS NEEDED, BUT THE PLAN (WHICH
 IS WHAT THE CONTRACTOR AND INSPECTOR WILL USE TO DO THE
 WORK) DO NOT SHOW THIS REINFORCEMENT.
  
 3RD REVIEW, NOT ADDRESSED.PLANS SHOW ROOF PANELS OVER
 EXISTING, BUT CALCS STATE THAT EXISTING SPAN DOES NOT
 WORK.PLEASE SEE CALCULATIONS.SEE ALSO FBC EB
 407.1.2, FBC EB 507.2.IT IS NOT CLEAR IF DESIGNER HAS
 DETERMINED THIS TO BE A REPAIR OR LEVEL 1 ALTERATION,
 BUT BASED ON CALCULATIONS PROVIDED IT APPEARS THAT
 ADDITIONAL STRUCTURAL WORK MUST BE DONE.PLEASE
 CLARIFY.
  
 10-11. ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-18 Cont ID  
Sent By shill Date 2008-04-18 Time 07:53 Rev Time 0.00
Received By shill Date 2008-04-18 Time 07:53 Sent To  
Notes
2008-04-18 09:09:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 SHEET S3, SHOWING LOCATION OF IMPROVEMENTS, IS PREPARED
 BY AN ENGINEER BUT NOT SIGNED, SEALED, AND DATED.THE
 PERMIT IS TO CLEARLY SHOW SCOPE OF WORK; THEREFORE A
 LOCATION PLAN IS REQUIRED.THIS SHOULD BE DONE BY THE
 DESIGNER OF RECORD OR DELEGATED ENGINEER.IF DONE BY A
 DELEGATED ENGINEER, IT SHOULD BE REVIEWED BY ENGINEER
 OF RECORD.
  
 IT IS NOT CLEAR WHICH OF THE MECHANICAL ROOMS ARE TO BE
 INCLUDED IN THIS PERMIT.S3 IS A ROOF FRAMING PLAN
 SHOWING THE FRAMING FOR THE ENTIRE ROOF.PLEASE
 CLARIFY SCOPE OF WORK ON THE PLAN.
  
 2.ADDRESSED.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 PRODUCT APPROVALS WERE NOT SUBMITTED.THIS IS REQUIRED
 FOR ALL COMPONENTS AND CLADDING, WHICH WOULD INCLUDE
 WALL PANELS, ROOF COMPONENTS & CLADDING (ROOF COVER,
 NOT DECK UNLESS THE DECK IS ALSO ACTING AS ROOF COVER),
 LOUVERS IF NEW LOUVERS ARE INSTALLED.
  
 4-6. ADDRESSED.
  
 NEW COMMENTS:
  
 7. THE ORIGINAL PERMIT PACKAGE WAS NOT SUBMITTED.OLD
 SHEETS ARE TO BE SUBMITTED FOR REFERENCE, AND THE
 PERMIT APPLICATION IS REQUIRED FOR PERMIT ISSUANCE.
  
 8.THE SCOPE OF WORK HAS CHANGED FROM ORIGINAL
 APPLICATION.THE WORK AS SHOWN IS NOT WITHIN THE SCOPE
 OF A SHEET METAL CONTRACTOR LICENSE, LIGHT GAGE METAL
 ONLY, FS489.A ROOF PERMIT AND A STRUCTURAL PERMIT
 WILL BE REQUIRED.
  
 9.EXISTING CONDITIONS NOT CLEAR.SEE ENGINEERING
 CALCS SHEET 3 AND ROOF FRAMING PLAN SHEET S3 (PREPARED
 BY DE BRITT & ASSOCIATES ENGINEERS).IT APPEARS THAT
 ADDITIONAL FRAMING MEMBERS WERE ADDED GRAPHICALLY.THE
 ALTERED PLAN SHOWS ROOF BEAMS WHICH ARE CONSISTENT WITH
 SHEET 3 OF CALCS.SHEET 3 STATES THAT 9.75' SPAN DOES
 NOT WORK FOR COMPONENT & CLADDING WIND PRESSURES, AND
 NEW DECK SPAN IS 4.8'.THE EXISTING PLAN APPEARS TO
 SHOW ONE ROOF FRAMING MEMBER IN THE CENTER, WHICH DOES
 NOT APPEAR ON THE NEW PLAN.DOES THIS GET REMOVED? SEE
 SHEET S1 PREPARED BY PBSJ, WHICH STATES "3ALL STEEL
 BEAMS ARE EXISTING".IT IS NOT CLEAR WHY S1 SHOWS THE
 ROOF FRAMING AS EXISTING AND NO CHANGES TO BE DONE, BUT
 THE CALCS SHEET 03 SHOW THAT A TOTAL OF 8 ROOF JOISTS
 ARE TO BE INSTALLED (EXISTING FRAMING HAS ONLY 3).IT
 IS NOT CLEAR WHY THE CALCS WOULD INDICATE THAT
 ADDITIONAL REINFORCEMENT IS NEEDED, BUT THE PLAN (WHICH
 IS WHAT THE CONTRACTOR AND INSPECTOR WILL USE TO DO THE
 WORK) DO NOT SHOW THIS REINFORCEMENT.
  
 10.PLEASE REMOVE HVHZ FROM DESIGN CRITERIA.IN THE
 PAST THERE HAVE BEEN SOME SIGNIFICANT DESIGN
 DIFFERENCES IN HVHZ, AND SOME HAVE NOT BEEN MORE
 STRINGENT (FOR INSTANCE, A STRESS INCREASE FOR STEEL
 WHICH WAS NEVER PERMITTED IN FBC2001 OR 2004).
 THEREFORE, DESIGN IS TO BE DONE TO FBC2004 MINIMUM.
  
 11.PT WOOD NAILERS ARE SHOWN.PROVIDE ENOUGH
 INFORMATION ABOUT THIS BUILDING TO SHOW THAT
 COMBUSTIBLES ARE PERMITTED.IF THIS IS A TYPE I OR II
 BUILDING, THIS DOES NOT APPEAR TO BE PERMITTED IN
 FBC603.1.IF THIS IS NOT A TYPE I OR II BUILDING,
 PROVIDE A CODE SUMMARY (BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY) TO SHOW
 THAT COMBUSTIBLES CAN BE USED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By shill Date 2008-02-27 Time 11:36 Rev Time 0.00
Received By shill Date 2008-02-27 Time 11:36 Sent To  
Notes
2008-02-27 12:17:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2.PLEASE SUBMIT PLANS WHICH DO NOT USE HIGHLIGHTER.
 WHEN SCANNED, THIS DOES NOT APPEAR.PLEASE USE INK FOR
 ALL ITEMS WHICH ARE REQUIRED TO SHOW CODE COMPLIANCE.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.THE PRODUCT APPROVAL PROVIDED IS EXPIRED,
 FBC2001 RATHER THAN FBC2004.
  
 4.THE PRODUCT APPROVAL IS DIFFICULT TO READ.THERE
 ARE WIND LOAD CHARTS BUT NO DESIGN PRESSURE
 INFORMATION.DESIGN PRESSURES ARE DETERMINED BY A
 NUMBER OF FACTORS, OF WHICH WIND SPEED IS ONE.THE
 PAPERWORK APPEARS INCOMPLETE.WHEN RESBUMITTING,
 PLEASE SUBMIT TWO COMPLETE LEGIBLE SETS INCLUDING ALL
 INFORMATION REQUIRED TO SHOW CODE COMPLIANCE.FBC*106.
  
  
 5.A WALL SECTION WAS PROVIDED (BUT SEE ITEM 1 ABOVE),
 NO ROOF PITCH STATED.FOR ALL REROOF PERMITS, ROOF
 PITCH AND MEAN ROOF HEIGHT IS REQUIRED ON THE
 APPLICATION OR IN THE PLAN.PLEASE PROVIDE THIS
 INFORMATION.FBC*106.
  
 6.PROVIDE ROOF FRAMING SPAN INFORMATION, FBC16,
 FBC*106.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 16:00 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 16:00 Sent To B
Notes
2008-06-30 16:01:14TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 16:17 Sent To B
Notes
2008-06-16 16:17:45TO "SHILL' DESK/RESUB