Plan Review Details - Permit 08020633
Plan Review Stops For Permit 08020633
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-21 Cont ID  
Sent By btrobaug Date 2008-04-15 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2008-03-21 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-12 Cont ID  
Sent By rmcdouga Date 2008-03-12 Time 12:15 Rev Time 0.00
Received By rmcdouga Date 2008-03-12 Time 11:18 Sent To  
Notes
2008-03-12 12:14:562004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO (2) COPIES OF OF PRODUCT APPROVALS FOR
 STORM PANELS FOR THE NEW NON-IMPACT WINDOW. SPECIFY
 CONNECTION TYPE, FASTENER TYPE AND SPACING, EDGE
 DISTANCE, ETC. CIRCLE THE APPROPRIATE ITEMS ON THE
 PRODUCT APPROVAL. FBC R301.2.1.2
  
 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-02-29 Time 13:56 Rev Time 0.00
Received By rmcdouga Date 2008-03-06 Time 14:18 Sent To  
Notes
2008-03-06 15:47:482004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1)SHOW THAT THE NEW BEDROOM COMPLIES WITH R310.1
 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 BASEMENTS WITH HABITABLE SPACE AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM, BUT SHALL NOT
 BE REQUIRED IN ADJOINING AREAS OF THE BASEMENT. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING
 A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES
 AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS
 PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD
 ENCLOSURE SHALL COMPLY WITH SECTION 310.3 . THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY
 ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT
 BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED
 WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2 .
 THE EMERGENCY ESCAPE AND RESCUE OPENING SHALL BE
 PERMITTED TO OPEN INTO A SCREEN ENCLOSURE, OPEN TO THE
 ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING
 AWAY FROM THE RESIDENCE.
  
 2) IF A NEW EXTERIOR WINDOW OR DOOR IS INSTALLED TO
 COMPLY WITH COMMENT #1, SUBMIT TWO COPIES OF PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THE ITEM AND FOR
 STORM PANELS IF REQUIRED. FAC RULE 9B-72, FBC 106.3.3*
 CITY AMENDMENTS AND FBC R301.2.1.2
  
 3) SPECIFY THE WOOD CONNECTORS THAT WILL BE USED TO
 ATTACH THE NEW STUDS TO THE EXISTING WOOD BEAM AT THE
 TOP OF THE NEW WOOD BEARING WALL TO COMPLETE THE
 CONTINUOUS LOAD PATH REQUIRED BY R301.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-05-02 Cont ID  
Sent By btrobaug Date 2008-05-02 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-05-02 Time 10:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-04-15 Cont ID  
Sent By btrobaug Date 2008-04-15 Time 14:28 Rev Time 0.00
Received By btrobaug Date 2008-04-15 Time 14:28 Sent To PC
Notes
2008-04-15 14:56:49 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE REVISION SUBMITTED FOR ELECTRICAL REVIEW HAS A
 RELOCATED WALL, DOOR (EGRESS), SINK, WATER HEATER,
 RANGE, REFRIGERATOR, WASHER, DRYER AND ELECTRICAL PANEL
 ALL NOTED AS EXISTING, BUT NOT THE SAME AS THE
 "EXISTING" CONDITIONS ON THE PERMIT SET.REVISE SHEET
 A-1 TO INDICATE FIELD CONDITIONS FOR ALL TRADES
 IMPACTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-21 Cont ID  
Sent By btrobaug Date 2008-03-21 Time 11:20 Rev Time 0.00
Received By btrobaug Date 2008-03-21 Time 10:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-18 Cont ID  
Sent By btrobaug Date 2008-03-18 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2008-03-18 Time 14:02 Sent To P
Notes
2008-03-18 14:14:46 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT WAS FROM THE PREVIOUS TWO REVIEWS, AND NOT
 ADDRESSED:
  
 2/29/08 REVIEW: 1} THE RISER DIAGRAM ON SHEET A-2
 INDICATES "EXISTING", BUT NOTES PERTAINING TO THE RISER
 INDICATE LOCATION OF THE METER TO BE UNKNOWN. CLARIFY
 TO INDICATE IF EXISTING OR TO BE INSTALLED, ALSO LOCATE
 THE SERVICE EQUIPMENT ON THE PLAN. 3/11/08 REVIEW: *
 THIS COMMENT WAS OVERLOOKED. PLEASE LOCATE ALL SERVICE
 EQUIPMENT IN THE FLOOR PLAN, A-1..** 3/18/08 REVIEW-
 THE METER AND DISCONNECT SHOWN ON THE RISER STILL HAVE
 NOT BEEN LOCATED ON THE PLAN. NOW ON THIS PLAN THE THE
 PANEL IS SHOWN AS "EXISTING", THE WALL IT'S SHOWN IN IS
 A NEW WALL, OBVIOUSLY THE PANEL CANNOT BE IN THAT
 LOCATION. THE PERSON TAKING RESPONSIBILITY FOR THIS
 PLAN SHOULD VISIT THE SITE TO DETERMINE THESE
 LOCATIONS.
  
 NEW COMMENT :
  
 2} THE LOCATION SHOWN FOR THE PANEL IS IN VIOLATION OF
 THE CLEARANCE REQUIREMENTS OF 110.26, 2005 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-11 Cont ID  
Sent By btrobaug Date 2008-03-11 Time 16:03 Rev Time 0.00
Received By btrobaug Date 2008-03-11 Time 15:23 Sent To P
Notes
2008-03-11 15:56:58 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT WAS FROM THE PREVIOUS REVIEW, AND NOT
 ADDRESSED:
  
 1} THE RISER DIAGRAM ON SHEET A-2 INDICATES "EXISTING",
 BUT NOTES PERTAINING TO THE RISER INDICATE LOCATION OF
 THE METER TO BE UNKNOWN. CLARIFY TO INDICATE IF
 EXISTING OR TO BE INSTALLED, ALSO LOCATE THE SERVICE
 EQUIPMENT ON THE PLAN* THIS COMMENT WAS OVERLOOKED.
 PLEASE LOCATE ALL SERVICE EQUIPMENT IN THE FLOOR PLAN,
 A-1..
  
 2} THE RESUBMITTAL NOW INDICATES A 150 AMP RATED PANEL
 WITH A 200 AMP MAIN BREAKER. THE RISER. SEE 408.36
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By btrobaug Date 2008-02-29 Time 13:54 Rev Time 0.00
Received By btrobaug Date 2008-02-29 Time 13:13 Sent To M
Notes
2008-02-29 13:53:23 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} THE RISER DIAGRAM ON SHEET A-2 INDICATES "EXISTING",
 BUT NOTES PERTAINING TO THE RISER INDICATE LOCATION OF
 THE METER TO BE UNKNOWN. CLARIFY TO INDICATE IF
 EXISTING OR TO BE INSTALLED, ALSO LOCATE THE SERVICE
 EQUIPMENT ON THE PLAN.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. IF IT IS
 DETERMINED TO BE AN EXISTING SERVICE THIS ISSUE MUST BE
 CORRECTED AS IT IS A LIFE SAFETY ISSUE.
  
 3}RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1)
 AND 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN THE NEW BEDROOM AND KITCHEN.
  
 4} A RECEPTACLE IS REQUIRED IN THE HALL/ENTRY PER
 210.52(H).
  
 5}210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 09:47 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 09:47 Sent To E
Notes
2008-05-02 09:48:29TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 08:47 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 08:47 Sent To  
Notes
2008-03-14 08:51:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 16:30 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 16:30 Sent To Z
Notes
2008-03-07 16:30:33TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-06 Cont ID  
Sent By rmcdouga Date 2008-03-06 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2008-02-26 Time 16:37 Sent To  
Notes
2008-02-26 16:38:13TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 11:55 Rev Time 0.20
Received By tgordon Date 2008-03-03 Time 11:55 Sent To P
Notes
2008-03-03 11:55:48NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-20 Cont ID  
Sent By jleech Date 2008-03-20 Time 08:32 Rev Time 0.00
Received By jleech Date 2008-03-20 Time 08:12 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-12 Cont ID  
Sent By jleech Date 2008-03-12 Time 09:28 Rev Time 0.00
Received By jleech Date 2008-03-12 Time 09:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By jleech Date 2008-03-04 Time 08:34 Rev Time 0.00
Received By jleech Date 2008-03-04 Time 08:19 Sent To B
Notes
2008-03-04 08:43:01DENIED;
 AUTOMATIC CLOTHES WASHER CANNOT BE DELETED. SEE FBC
 PLUMBING TABLE 403.1(R3) MINIMUM PLUMBING FIXTURES
 REQUIRES A WASHING MACHINE HOOK UP. ALSO SEE SECTION
 406.3 THE BRANCH DRAIN SHALL BE 3".
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-18 Cont ID  
Sent By choops Date 2008-03-18 Time 10:31 Rev Time 0.00
Received By choops Date 2008-03-18 Time 10:31 Sent To E
Notes
2008-03-18 10:32:17***APPROVED - RESUB #2 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-10 Cont ID  
Sent By choops Date 2008-03-10 Time 15:50 Rev Time 0.00
Received By choops Date 2008-03-10 Time 15:50 Sent To E
Notes
2008-03-10 15:50:57***APPROVED - RESUB #1 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status P Date 2008-02-27 Cont ID  
Sent By choops Date 2008-02-27 Time 14:31 Rev Time 0.00
Received By choops Date 2008-02-27 Time 14:31 Sent To E
Notes
2008-02-27 14:34:11***APPROVED***