| 2008-02-27 10:02:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET SP-1 HAS A TITLE BLOCK FROM POPPER & |
| | ASSOCIATES CA# 2950, WITH FRED J. POPPER ARCHITECT OF |
| | RECORD, FLORIDA REGISTRATION AR8988. SHEET SP-1 IS |
| | SIGNED, SEALED, DATED AND PART OF THE PERMITTED SET OF |
| | PLANS FOR THE MASTER PERMIT NUMBER (07080049) INDICATED |
| | ON THE IRRIGATION PERMIT APPLICATION. PER CHAPTER 481 |
| | FLORIDA STATUTES, PART 1, ANY REVISIONS TO SAID SHEET |
| | (ADDITION OF THE IRRIGATION SYSTEM) MUST BE BY THE |
| | ORIGINAL DESIGN PROFESSIONAL OF RECORD, AND BE SIGNED, |
| | SEALED, DATED AND REVISION NUMBER INDICATED BY SAID |
| | DESIGN PROFESSIONAL. |
| | |
| | NOTE: THE IRRIGATION CONTRACTOR CAN SUBMIT IRRIGATION |
| | PLANS OF THEIR OWN DESIGN AS LONG AS ALL PLANS, |
| | SPECIFICATIONS, AND ACCOMPANYING DATA BEING FILED FOR |
| | PUBLIC RECORD SHALL CONTAIN THE PRINTED NAME OF THE |
| | RESPONSIBLE PERSON WITH THE ORIGINAL SIGNATURE AND DATE |
| | ON SUCH INFORMATION. PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER 1, SECTION *106.3.4.3. |
| | |
| | END OF COMMENTS: |
| | |