| Plan Review Stops For Permit 08020617 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-08-11 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-08-11 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2008-08-11 13:48:28 | RESTAMP OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-07-17 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-07-17 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2008-07-17 09:25:57 | ****CORRECTIONS**** | | | ****RESTAMP**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.PLEASE PROVIDE EITHER A LETTER OR REVISE SHEET T1 | | | TO SHOW COMPLIANCE WITH THE REQUIREMENT OF 1.15 | | | IMPORTANCE FACTOR, FBC1603.1.4.ALSO DECLARE EXPOSURE | | | CLASSIFICATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-21 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-21 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-04-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-01 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-01 |
Time |
10:19 |
Sent To |
PC |
|
| Notes |
| 2008-04-01 10:19:44 | PLANS PROCESSED, ELECTRICAL PERMIT STILL REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
20:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-04 |
Time |
20:28 |
Sent To |
|
|
| Notes |
| 2008-03-04 20:32:58 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE THERE ARE TWO ACTIVE PERMIT | | | APPLICATIONS FOR THE SAME SCOPE. | | | PLEASE CLEAR UP WHICH ONE IS GOING TO BE USED TO APPLY | | | FOR PERMIT. | | | | | | 2) NOTE: SEE ZONING COMMENTS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-31 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2008-03-31 10:42:25 | *****PROVISO***** | | | | | | 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE | | | REQUIRED EXIT STAIRTOWERS.PLEASE PROVIDE A NOTE ON | | | THE PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY | | | EXIT STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY. | | | | | | 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT | | | INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR | | | DEVICES. | | | | | | 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT | | | INTERFERE ANY STANDPIPE ROOF MANIFOLDS. | | | | | | 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK | | | TO COMPLY WITH NFPA 241. | | | | | | | | | (PLAN SHEET C4.1 STAMPED, INITIALED, AND DATED) | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-30 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-30 |
Time |
08:39 |
Sent To |
B |
|
| Notes |
| 2008-07-30 08:39:58 | TO "SHILL" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-09 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-09 |
Time |
14:44 |
Sent To |
B |
|
| Notes |
| 2008-07-09 14:45:01 | TO "SHILL" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-27 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2008-02-27 10:43:50 | TO "COMM" BD#49 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-02-27 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-02-27 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2008-02-27 13:23:19 | ***APPROVED - PER ISPR CASE NO. 08-02*** |
|
|