Plan Review Details - Permit 08020593
Plan Review Stops For Permit 08020593
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-03 Cont ID  
Sent By mjacobs Date 2008-05-03 Time 13:02 Rev Time 0.00
Received By mjacobs Date 2008-05-03 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-09 Cont ID  
Sent By mjacobs Date 2008-04-09 Time 08:56 Rev Time 0.00
Received By mjacobs Date 2008-04-09 Time 07:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By mjacobs Date 2008-03-05 Time 17:41 Rev Time 0.00
Received By mjacobs Date 2008-03-05 Time 13:58 Sent To  
Notes
2008-03-05 17:41:37BUILDING PLAN REVIEW
 PERMIT: 08020593
 ADD: 580 VILLAGE BLVD. #304
 CONT: BIEBER CONST.
 TEL: (561)276-9966
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-5-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)F.S 481.221 ALL FINAL CONSTRUCTION DOCUMENTS AND
 INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS, PLANS,
 SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE
 REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC RECORD
 SHALL BEAR THE SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE DOCUMENT AND THE
 DATE ON WHICH THEY WERE SEALED. THE SIGNATURE, DATE,
 AND SEAL SHALL BE EVIDENCE OF THE AUTHENTICITY OF THAT
 TO WHICH THEY ARE AFFIXED. THE DATE IS MISSING ON THE
 SEAL. THE CERTIFICATE OF AUTHORIZATION FOR THE
 DIFFERENT ENGINEERING AND ARCHITECTURAL FIRMS INDICATED
 ON THE PLANS IS REQUIRED TO BE SHOWN ON THE PLANS.
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)WHAT IS THE OCCUPANT LOAD OF THE SPACE? INDICATE
 THE SQUARE FOOTAGE OF THE NEW SPACE AND GIVE THE
 OCCUPANT LOAD USING TABLE 1004.1.2.
  
 5)FBC 11-7.2(2) (I) A PORTION OF THE RECEPTIONIST
 WINDOW SHALL BE A MINIMUM LENGTH OF 36 INCHES AND A
 MAXIMUM HEIGHT OF 36 INCHES. DETAILS #2 AND #4 ON SHEET
 A7.0 SHOW A HEIGHT OF 3'6" AT THE RECEPTIONIST WINDOW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 09:36 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 09:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 13:00 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 06:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By btrobaug Date 2008-02-29 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2008-02-28 Time 07:53 Sent To  
Notes
2008-02-29 15:52:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE WHAT THE PRIMARY OCP IS FOR TRANSFORMER
 "TLM". IF THE 60 AMP RATED DISCONNECT HAS IN FACT A 60
 AMP OCP INSTALLED, IT WOULD NOT COMPLY WITH 450.3(B).
 125% OF A 30000 WATT TRANSFORMER WOULD ALLOW A 50 AMP
 OCP MAXIMUM.
  
 2} THERE IS NO SECONDARY OCP FOR "TLM" AS PANEL "LM" IS
 LISTED AS MAIN LUG ONLY. SEE 408.36 AND 450.3(B).
  
 3} THE LIGHTING CIRCUITS ARE NOT ON THE PANEL SCHEDULE
 AND DO NOT APPEAR TO BE CALCULATED AT 125% (CONTINUOUS
 LOAD) PER 215.2.
  
 4} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. THE DATE IS MISSING.
  
 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER PER
 61G15-23.002FLORIDA ADMINISTRATIVE CODE..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 11:56 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 11:39 Sent To B1
Notes
2008-05-06 11:55:59*****APPROVED*****
  
 PLAN SHEETS AN-3, A1.0, A5.0, AND E2 WERE PREVIOUSLY
 FIRE-STAMPED ON 4/08/2008;NEW SHEET A1.0 WAS STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 16:09 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 15:30 Sent To B1
Notes
2008-04-08 16:09:32*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS AN-3, A1.0, A5.0, AND E2
 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 16:10 Rev Time 0.00
Received By mawillia Date 2008-03-10 Time 15:16 Sent To  
Notes
2008-03-10 16:10:44*****DENIED*****
  
 1.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO AND/OR EGRESS FROM OTHER TENANT SPACES ON THE
 FLOOR OR THE BUILDING.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED
 DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND
 AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 4.PLEASE LIST THE OCCUPANT LOAD FOR THIS NEW TENANT
 SPACE.
  
 5.SHOW THE LOCATION OF THE 2A10:BC FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 6.SHOW A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THIS
 SCOPE OF WORK.IF THE ALTERATION HAS CAUSE FOR THE
 SPRINKLER SYSTEM BE REMODELED, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED ONCE THE MASTER PERMIT HAS BEEN
 ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE (ON THE PLAN) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 15:36 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 15:36 Sent To  
Notes
2008-05-16 15:38:53TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 10:28 Sent To  
Notes
2008-04-22 10:37:46TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 09:12 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 09:10 Sent To  
Notes
2008-03-31 09:15:08TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 15:16 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 08:40 Rev Time 0.30
Received By tgordon Date 2008-05-21 Time 08:40 Sent To  
Notes
2008-05-21 08:44:54*** PROVISO ***
 1) HAVE PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED
 CONDENSER STANDS ON JOB SITE FOR CITY INSPECTOR, PER FS
 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND FAC
 9B-72.010(31)(G).
  
 ** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 14:24 Rev Time 0.30
Received By tgordon Date 2008-04-03 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-28 Cont ID  
Sent By tgordon Date 2008-02-28 Time 15:15 Rev Time 1.00
Received By tgordon Date 2008-02-28 Time 15:15 Sent To  
Notes
2008-02-28 15:40:36PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ARCHITECTURAL FIRM LICENSE NUMBER MUST APPEAR IN
 THE TITLE BLOCK OF EACH ARCHITECTURAL PLAN, SEE FAC
 61G1-16.004.
  
 2) THE ARCHITECT (ANGELO LUIS LEBRON) MUST HAVE HIS
 PRINTED NAME IN THE TITLE BLOCK, SEE SAME.
  
 3) THE ARCHITECT MUST ALSO PUT THE DATE WHEN SIGNING
 AND SEALING PLANS, SEE FAC 61G1-16.003.
  
 4) THE ENGINEER MUST ALSO PUT THE DATE WHEN SIGNING AND
 SEALING PLANS, SEE FAC 61G15-23.002.
  
 5) THE ENGINEERING FIRM (MAY-BLANKENBEKER, INC.) MUST
 HAVE THEIR CERTIFICATE OF AUTHORIZATION NUMBER IN THE
 TITLE BLOCK OF EACH ENGINEERING PLAN, SEE FAC
 61G-23.002.
  
 6) SEE PLAN M-2 TELECOM ROOM CRAC-1 UNIT HAS A NOTE #3
 NEXT TO IT. DO YOU WANT TO REMOVE DUCK AND CAP? PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-28 Cont ID  
Sent By jleech Date 2008-04-28 Time 10:48 Rev Time 0.00
Received By jleech Date 2008-04-28 Time 10:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-04 Cont ID  
Sent By jleech Date 2008-04-04 Time 07:53 Rev Time 0.00
Received By jleech Date 2008-04-04 Time 07:31 Sent To  
Notes
2008-04-04 08:36:32DENIED;
 1. PAGE P1, DWV RISER; NO DEAD ENDS PERMITED IN THE
 SANITARY DRAINAGE SYSTEM LONGER THAN 2'. FBC-PLUMBING
 SECTION 704.5.
 2. PAGE A1.0 CLEAR FLOOR UNDER BREAK SINK TO COMPLY
 WITH FBC-BUILDING SECTION 11-4.24.5 THE CLEAR FLOOR
 SPACE SHALL EXTEND 19" UNDER THE SINK.
 3. PAGE A7.0 DETAIL 3; NO DOORS OR BASE PERMITED IN
 FRONT OF BREAK ROOM SINK. SEE SECTION 11-4.24.3 KNEE
 CLEARANCE 19"DEEP SHALL BE PROVIDED UNDERNEATH THE
 SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By jleech Date 2008-02-29 Time 09:49 Rev Time 0.00
Received By jleech Date 2008-02-29 Time 09:37 Sent To  
Notes
2008-02-29 10:04:40DENIED;
 1. WATER RISER DIAGRAM; WATER HAMMER ARRESTOR IS
 REQUIRED AT BREAKICE BOX SEE FBC PLUMBING SECTION
 604.9. SPEC OUT SIZE AND MANUFACTURE ON PLANS.
 2. CONDENSATE FROM COMPUTER A/C TO DISCHARGE TO THE
 OUTSIDE, STORM DRAINS OR TO CONDENSATE DRAINS. NOT
 PERMITED TO GO TO SANITARY. WEST PALM BEACH UTILITY
 ORD.
 3. BREAK SINK TO MEET ACCESSIBILITY CODE CHAPTER 11 OF
 THE FBC BUILDING CODE. SEE SECTIONS 11-4.24.1 THRU
 11-4.24.7. SHOW THE FRONTAL CLEAR FLOOR SPACE ON FLOOR
 PLANS .
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-27 Cont ID  
Sent By choops Date 2008-02-27 Time 13:26 Rev Time 0.00
Received By choops Date 2008-02-27 Time 13:26 Sent To  
Notes
2008-02-27 13:26:59*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.