Plan Review Details - Permit 08020549
Plan Review Stops For Permit 08020549
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-03-10 Cont ID  
Sent By lursu Date 2008-03-10 Time 12:05 Rev Time 0.00
Received By lursu Date 2008-03-10 Time 12:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-23 Cont ID  
Sent By mjacobs Date 2008-05-23 Time 13:49 Rev Time 0.00
Received By mjacobs Date 2008-05-23 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By mjacobs Date 2008-04-22 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2008-04-22 Time 07:32 Sent To  
Notes
2008-04-23 12:11:24BUILDING PLAN REVIEW #2
 PERMIT: 08020549
 ADD: 5760 CORPORATE WAY #2-3-4
 CONT: O?CONNOR & TAYLOR INC.
 TEL: (561)282-7492
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 4-22-08
 ACTION: DENIED
  
 1)OK
  
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
 4)OK
  
 ** NEW** THE INPUT DATA REPORT FOR THE ENERGY
 CALCULATIONS DO NOT MATCH THE PLANS. THE WALL SECTION
 CONTAINS REFERENCES TO METAL ROOFING, THE DOORS WHICH
 ARE SHOWN AS GLASS DOORS ON THE PLANS, ARE REFERENCE AS
 INSULATED ALUMINIUM DOORS; THE INSULATION ON THE
 DRAWINGS IS DIFFERENT TO WHAT IS STATED ON THE
 CALCULATION SHEETS. THERE ARE OTHER ISSUES, SO PLEASE
 MAKE THE CORRECTIONS ACCORDINGLY TO MATCH WHAT IS SHOWN
 ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX 561) 805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By mjacobs Date 2008-03-10 Time 07:58 Rev Time 0.00
Received By mjacobs Date 2008-03-08 Time 14:11 Sent To  
Notes
2008-03-10 07:58:47BUILDING PLAN REVIEW
 PERMIT: 08020549
 ADD: 5760 CORPORATE WAY #2-3-4.
 CONT: O?CONNOR TAYLOR
 TEL: (561)863-7349
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)1210.2 WALLS.
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 NOTE:PAINT ON DRYWALL IS NOT CONSIDERED A HARD
 SURFACE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX 561) 805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 07:21 Sent To PC
Notes
2008-06-03 07:23:18REDLINED PLANS AS THE EXTERIOR FIXTURES WHICH ARE NOT
 SHOWN AS EXISTING WERE NOT IN IDR OF CALCULATIONS.
 SPOKE TO CONTRACTOR, THESE ARE EXISTING AND THERFORE
 ARE NOT BEING ADDED INTO THE IDR AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-22 Cont ID  
Sent By dpalmer Date 2008-04-22 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2008-04-22 Time 14:23 Sent To  
Notes
2008-04-22 14:23:30** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE EXACT NOTES FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW NOTES WITH RESPECT TO RE-SUB. SOME
 DOCUMENTS/INFORMATION WAS NOT SUBMITTED ON PREVIOUS
 REVIEW.
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS REQUIRED
 UNDER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 IS NOT CODE
 COMPLIANT ON PLANS.
 THERE IS NOT ENOUGH INFORMATION FOR THE PROPOSED OVER
 RIDE MOTION SENSOR DEVICES.
 FOR EXAMPLE:
 PLEASE SEE LS 101 7.8.1.2.2 AND FBC 1016.1 AS THE
 DEVICE USED FOR NORMAL EGRESS LIGHTING SHALL BE FAIL
 SAFE ON AND MUST ALSO BE DUAL TECHNOLOGY. MAY NOT ONLY
 BE MOTION AS STATED ON PLANS. MUST ALSO STATE * FAIL
 SAFE ON*
 FOR EXAMPLE:
 PLEASE SEE THE PLANS INDICATE WHAT APPEAR TO BE
 STANDARD SWITCHES IN OTHER AREAS. THE SYMBOL LEGEND
 DOES NOT PROVIDE THE REQUIRED DEVICES.
  
 2) NOTE: PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON
 THE ENERGY CALCULATIONS NOW SUBMITTED AS METHOD *B*.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR.
 PLEASE SEE NOTES FROM PREVIOUS REVIEW AS IT STATES THE
 INFORMATION ON THE IDR MUST COMPLY WITH THE MINIMUM IN
 THE FBC AND ALL INFORMATION ON PLANS IS REQUIRED TO
 COORDINATE WITH THE ENERGY CALCULATIONS AND THE
 INFORMATION PLACED IN THE IDR. PLEASE SEE SOME ITEMS
 NOTED BELOW ARE EXAMPLES OF SPECIFIC ITEMS WHICH DO NOT
 CORRELATE. THIS IS IN NO WAY AN EXHAUSTED LIST OF ALL
 POSSIBLE ITEMS.
 FOR EXAMPLE:
 PLEASE SEE THE ELECTRICAL WATER HEATERS ON PLANS ARE
 NOT ON THE IDR. HOW IS IT POSSIBLE THAT THE IDR IS
 BLANK FOR WATER HEATERS?
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING ON THE WAREHOUSE PLANS STILL
 SHOWS THE FIXTURES AS *J*, AND THE IDR SHOWS FIXTURES
 AS ONE 514WATT FIXTURE. HOW IS THIS POSSIBLE? PLEASE
 SEE THE PRINT OUT FROM MANUFACTURE FOR THIS SAME
 FIXTURE AS LISTED ON THE FIXTURE LEGEND AS THIS FIXTURE
 BEING AN 8FT FIXTURE CONTAINS 4-32W BULBS. PLEASE SEE
 THE SPECS WHICH INDICATE 60W INPUT FOR EACH 4FT
 SECTION. BASED ON THE FIXTURES ON PLANS EVEN IF ALL
 FIXTURES IN WAREHOUSE WERE DONE AS ONE FIXTURE (WHICH
 IS NOT PERMITTED) THE TOTAL WATTAGE IS NOT ACCURATE
 WITH PLANS AND DOES NOT COORDINATE.
 FOR EXAMPLE:
 PLEASE SEE THE JURISDICTION IS LISTED AS PALM BEACH
 COUNTY WHEN THE SCOPE OF WORK IS LISTED IN CITY OF WEST
 PALM BEACH.
 FOR EXAMPLE:
 PLEASE SEE ITEMS FOR BUILDING WHICH WILL BE NOTED UNDER
 BUILDING REVIEW. DOORS SHOWN AS INSULATED ALUMINUM
 DOORS WHEN DOORS ARE GLASS. PLEASE SEE WALL SECTIONS OF
 THE IDR WHICH LISTS * METAL ROOF AND R-19 FOR A WALL.
 HOW IS THIS POSSIBLE?ITEMS LIKE THESE WILL BE PART OF
 MECH/ BLDG REVIEW AND ARE NOTED FOR INFORMATION.
  
 ** AS NOTED ABOVE THIS IS NOT AN EXHAUSTED LIST AND
 ITEMS ARE GIVEN AS A BENEFIT FOR INFORMATION TO GIVE
 EXAMPLES.
 13-415.2, 13-400.3.B, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING
 GIVEN AT THIS TIME. THIS IS ONLY A NOTICE.
 PLEASE KNOW SOME ELECTRICAL PLANS ALONG WITH ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH WERE AT
 THE END OF THE REVIEW WHICH WERE LABELED AS
 *IMPORTANT*. THIS PREVIOUS NOTE REQUESTED THE
 OLD/VOIDED SHEETS TO BE RETURNED SEPARATE FOR
 REVIEW/COMPARISON OF CHANGES. THESE WERE NOT LOCATED IN
 SETS OF RESUBMITTED PLANS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 08:03 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 08:02 Sent To  
Notes
2008-03-10 08:03:22** DENIED REVIEW **
  
 PERMIT # 08020549
  
 1) NOTE: PLEASE SEE THE CODES LISTED ON COVER SHEET
 STATES 2001 FBC?
 PLEASE BE SURE THE ARCHITECTURAL SHEETS AND ELECTRICAL
 SHEETS.
 2004 FBC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE PLANS WHICH STATES * NEW BUILDING*
 YET BASED ON PLANS AND PERMIT APPLICATION THIS SEEMS TO
 BE FOR TENANT BLD OUTS.
 PLEASE KNOW ADDRESSING WILL BE NEEDED FOR SUITE/UNIT
 NUMBERS TO BE ASSIGNED. THIS WILL BE SENT TO ADDRESSING
 REVIEWER.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS
 IN NEED.
 A) PLEASE SEE13-400.3.A, HOW CAN METHOD *A* AS
 SUBMITTED BE USED WHEN THIS IS NOT FOR WHOLE BUILDING?
 PLEASE SEE 13-415.2.
 PLEASE SEE FIXTURE LEGEND ON PLANS IS NOT COMPLETE WITH
 THE NEW FIXTURES AND CAN NOT VERIFY ANY
 CALCULATIONS.(MISSING FIXTURE *J* ALL TOGETHER. PLEASE
 SEE THE NUMBER OF FIXTURES AND WATTAGES DO NOT
 CORRELATE.
 PLEASE SEE 13-415.2.ABC .1, .1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 AS
 NO LIGHTING CONTROL SYSTEMS WERE SUBMITTED.
 PLEASE SUBMIT COMPLETE DETAILS.
 PLEASE SEE SECTION ABOVE FOR SEPARATE SPACES AS PLANS
 SHOW NO DEVICES FOR COMPLIANCE.
 PLEASE SUBMIT MAXIMUM TIMES ON DEVICES.
 PLEASE SUBMIT TIME SCHEDULING ETC.
 THERE ARE MANY ITEMS MISSING AT THIS TIME WHICH CAN NOT
 BE REVIEWED.
  
 C) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 FOR REQUIRED
 NOTES TO BE ON PLANS.
  
 4) NOTE: PLEASE SEE 600.5 AS THE MIN VA FOR SIGN
 CIRCUIT IS REQUIRED AT 1200VA.
  
 5) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW
 RECEPTACLE. PLEASE SEE 220.42 FOR LOADS.
  
 6) NOTE: PLEASE SEE MISSING CONTROLS AND CIRCUITING FOR
 EXTERIOR LIGHTS. ARE THESE ALL EXISTING AND FROM HOUSE
 PANEL? IF NOT PLEASE SEE 13-415.1.ABC.1.4 AS NOTED
 ABOVE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-02 Cont ID  
Sent By mawillia Date 2008-06-02 Time 14:56 Rev Time 0.00
Received By mawillia Date 2008-06-02 Time 14:38 Sent To  
Notes
2008-06-02 14:43:18*****APPROVED*****
  
 PLAN SHEET SHEET E-1 STAMPED, INIALED, AND DATED;
 SHEET TI-1 PREVIOUSLY FIRE-STAMPED ON 5/06/2008.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 11:32 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 11:10 Sent To  
Notes
2008-05-06 11:29:07*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED.PLAN SHEET TI-1 STAMPED, INITIALED,
 AND DATED;SHEET E-1 TO BE FIRE-STAMPED WHEN THE
 ELECTRICAL REVIEWER HAS BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 16:33 Rev Time 0.00
Received By mawillia Date 2008-03-31 Time 15:28 Sent To  
Notes
2008-03-31 16:01:41*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS,
 FIRE LANES)
  
 3.IN ADDITION TO THE ADDRESS NUMBERS ON THE EXTERIOR
 ELEVATION WHICH FRONTS CORPORATE WAY, THE TENANT SPACE
 NUMBERS SHALL BE SHOWN.AS PER WEST PALM BEACH CODE,
 THE UNIT NUMBERS (NOT TO BE INSTALLED ON THE FRONT
 DOORS) SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH. UNIT NUMBERS SHALL ALSO BE REQUIRED
 THE ON/AT THE REAR DOORS.FOR ADDRESSING MATTERS,
 CONTACT LILI URSU AT 561-822-1239
  
 4.CLASSIFY THE CONTENTS OF THE OCCUPANCY IN TERMS OF
 LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD DEPENDING
 ON THE CHARACTER OF MATERIALS STORED, THEIR PACKAGING,
 AND OTHER FACTORS.
  
 5.THE DOOR IN THE 1-HOUR RATED PARTITION BETWEEN THE
 BUSINESS AREA (OFFICE) AND THE STORAGE AREA (WAREHOUSE)
 SHALL BE A MINIMUM 20 MINUTE FIRE-RATING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 08:46 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 08:45 Sent To  
Notes
2008-05-13 08:50:24TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-15 Cont ID  
Sent By adarroug Date 2008-04-15 Time 15:25 Rev Time 0.00
Received By adarroug Date 2008-04-15 Time 15:25 Sent To  
Notes
2008-04-15 15:27:47TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 15:29 Rev Time 0.00
Received By mawillia Date 2008-02-25 Time 10:47 Sent To  
Notes
2008-02-25 10:47:40TO "COMM" BD#55

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 14:25 Rev Time 0.30
Received By tgordon Date 2008-05-27 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By tgordon Date 2008-04-23 Time 09:03 Rev Time 0.25
Received By tgordon Date 2008-04-23 Time 09:03 Sent To  
Notes
2008-04-23 09:17:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) SEE ENERGY CALCULATIONS PAGE 7, OTHER REQUIRED
 COMPLIANCE (CHECK LIST), PLEASE COMPLETE, PER 2004 FBC
 13-103.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By tgordon Date 2008-03-06 Time 09:31 Rev Time 0.45
Received By tgordon Date 2008-03-06 Time 09:31 Sent To  
Notes
2008-03-06 09:49:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE PLAN PAGE TI-1 SHELL BUILDING DATA SHOWS FBC
 2001, THE FBC BEING USED AT THIS TIME IS THE 2004.
 PLEASE CORRECT.
  
 2) SEE PLAN PAGE MP-1 FRESH AIR CALCULATIONS SHOWS
 ASHRAE 62-1989, THE ASHRAE BEING USED AT THIS TIME IS
 THE 62-2004. PLEASE CORRECT.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-21 Cont ID  
Sent By kstevens Date 2008-04-21 Time 15:43 Rev Time 0.00
Received By kstevens Date 2008-04-21 Time 15:43 Sent To  
Notes
2008-04-21 15:43:37PASSED/PROVISO--TANKLESS WATER HEATER SHALL BE
 LISTED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 18:03 Rev Time 0.00
Received By kstevens Date 2008-03-26 Time 18:03 Sent To  
Notes
2008-03-26 18:12:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT TI-1 BLDG DATA: BUILD-OUT SHALL BE DESIGNED TO
 FBC- 2004 W/2007 AMENDMENTS. PLEASE INDICATE ON PLANS.
  
 2. SHT TI-1 INDICATES BOTH STORAGE OCCUPANCY, (13,392
 SF), AND BUSINESS, (3,329 SF) TYPICAL SPACE. (SEE
 TYPICAL SPACE LIFE SAFETY TABULATIONS). PLEASE CLARIFY.
 IF THE SPACES ARE MIXED OCCUPANCY, INDICATE THE SQUARE
 FOOTAGE OF EACH OCCUPANCY IN EACH TYPICAL SPACE.
  
 3. ALL MP & E SHEETS. THE ADDRESS IN THE TITLE BLOCK
 DOES NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA
 STATE DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCKS OR
 THE DBPR WEBSITE SO THE ADDRESS REFLECTS. FAC
 61G15-23.002(2) & FS 471.025.
  
 4. SHT MP--2 HOT WATER IS REQUIRE TO THE JANITOR SINKS
 PER SECTION 607.1. PLEASE SHOW COMPLIANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]