| Plan Review Stops For Permit 08020549 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-03-10 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-03-10 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-05-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-23 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-23 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-22 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-22 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2008-04-23 12:11:24 | BUILDING PLAN REVIEW #2 | | | PERMIT: 08020549 | | | ADD: 5760 CORPORATE WAY #2-3-4 | | | CONT: O?CONNOR & TAYLOR INC. | | | TEL: (561)282-7492 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST 4-22-08 | | | ACTION: DENIED | | | | | | 1)OK | | | | | | 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) OK | | | 4)OK | | | | | | ** NEW** THE INPUT DATA REPORT FOR THE ENERGY | | | CALCULATIONS DO NOT MATCH THE PLANS. THE WALL SECTION | | | CONTAINS REFERENCES TO METAL ROOFING, THE DOORS WHICH | | | ARE SHOWN AS GLASS DOORS ON THE PLANS, ARE REFERENCE AS | | | INSULATED ALUMINIUM DOORS; THE INSULATION ON THE | | | DRAWINGS IS DIFFERENT TO WHAT IS STATED ON THE | | | CALCULATION SHEETS. THERE ARE OTHER ISSUES, SO PLEASE | | | MAKE THE CORRECTIONS ACCORDINGLY TO MATCH WHAT IS SHOWN | | | ON THE PLANS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX 561) 805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-10 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-08 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2008-03-10 07:58:47 | BUILDING PLAN REVIEW | | | PERMIT: 08020549 | | | ADD: 5760 CORPORATE WAY #2-3-4. | | | CONT: O?CONNOR TAYLOR | | | TEL: (561)863-7349 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 4)1210.2 WALLS. | | | WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL | | | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF | | | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. | | | NOTE:PAINT ON DRYWALL IS NOT CONSIDERED A HARD | | | SURFACE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX 561) 805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-03 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-03 |
Time |
07:21 |
Sent To |
PC |
|
| Notes |
| 2008-06-03 07:23:18 | REDLINED PLANS AS THE EXTERIOR FIXTURES WHICH ARE NOT | | | SHOWN AS EXISTING WERE NOT IN IDR OF CALCULATIONS. | | | SPOKE TO CONTRACTOR, THESE ARE EXISTING AND THERFORE | | | ARE NOT BEING ADDED INTO THE IDR AT THIS TIME. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-22 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-22 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2008-04-22 14:23:30 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME OF THE EXACT NOTES FROM PREVIOUS | | | REVIEW ARE STILL IN NEED OF ADDRESSING. | | | PLEASE ALSO SEE NEW NOTES WITH RESPECT TO RE-SUB. SOME | | | DOCUMENTS/INFORMATION WAS NOT SUBMITTED ON PREVIOUS | | | REVIEW. | | | | | | 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS REQUIRED | | | UNDER 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 IS NOT CODE | | | COMPLIANT ON PLANS. | | | THERE IS NOT ENOUGH INFORMATION FOR THE PROPOSED OVER | | | RIDE MOTION SENSOR DEVICES. | | | FOR EXAMPLE: | | | PLEASE SEE LS 101 7.8.1.2.2 AND FBC 1016.1 AS THE | | | DEVICE USED FOR NORMAL EGRESS LIGHTING SHALL BE FAIL | | | SAFE ON AND MUST ALSO BE DUAL TECHNOLOGY. MAY NOT ONLY | | | BE MOTION AS STATED ON PLANS. MUST ALSO STATE * FAIL | | | SAFE ON* | | | FOR EXAMPLE: | | | PLEASE SEE THE PLANS INDICATE WHAT APPEAR TO BE | | | STANDARD SWITCHES IN OTHER AREAS. THE SYMBOL LEGEND | | | DOES NOT PROVIDE THE REQUIRED DEVICES. | | | | | | 2) NOTE: PLEASE SEE THE FOLLOWING COMMENTS ARE BASED ON | | | THE ENERGY CALCULATIONS NOW SUBMITTED AS METHOD *B*. | | | THE INPUT DATA REPORT WILL BE NOTED AS IDR. | | | PLEASE SEE NOTES FROM PREVIOUS REVIEW AS IT STATES THE | | | INFORMATION ON THE IDR MUST COMPLY WITH THE MINIMUM IN | | | THE FBC AND ALL INFORMATION ON PLANS IS REQUIRED TO | | | COORDINATE WITH THE ENERGY CALCULATIONS AND THE | | | INFORMATION PLACED IN THE IDR. PLEASE SEE SOME ITEMS | | | NOTED BELOW ARE EXAMPLES OF SPECIFIC ITEMS WHICH DO NOT | | | CORRELATE. THIS IS IN NO WAY AN EXHAUSTED LIST OF ALL | | | POSSIBLE ITEMS. | | | FOR EXAMPLE: | | | PLEASE SEE THE ELECTRICAL WATER HEATERS ON PLANS ARE | | | NOT ON THE IDR. HOW IS IT POSSIBLE THAT THE IDR IS | | | BLANK FOR WATER HEATERS? | | | FOR EXAMPLE: | | | PLEASE SEE THE LIGHTING ON THE WAREHOUSE PLANS STILL | | | SHOWS THE FIXTURES AS *J*, AND THE IDR SHOWS FIXTURES | | | AS ONE 514WATT FIXTURE. HOW IS THIS POSSIBLE? PLEASE | | | SEE THE PRINT OUT FROM MANUFACTURE FOR THIS SAME | | | FIXTURE AS LISTED ON THE FIXTURE LEGEND AS THIS FIXTURE | | | BEING AN 8FT FIXTURE CONTAINS 4-32W BULBS. PLEASE SEE | | | THE SPECS WHICH INDICATE 60W INPUT FOR EACH 4FT | | | SECTION. BASED ON THE FIXTURES ON PLANS EVEN IF ALL | | | FIXTURES IN WAREHOUSE WERE DONE AS ONE FIXTURE (WHICH | | | IS NOT PERMITTED) THE TOTAL WATTAGE IS NOT ACCURATE | | | WITH PLANS AND DOES NOT COORDINATE. | | | FOR EXAMPLE: | | | PLEASE SEE THE JURISDICTION IS LISTED AS PALM BEACH | | | COUNTY WHEN THE SCOPE OF WORK IS LISTED IN CITY OF WEST | | | PALM BEACH. | | | FOR EXAMPLE: | | | PLEASE SEE ITEMS FOR BUILDING WHICH WILL BE NOTED UNDER | | | BUILDING REVIEW. DOORS SHOWN AS INSULATED ALUMINUM | | | DOORS WHEN DOORS ARE GLASS. PLEASE SEE WALL SECTIONS OF | | | THE IDR WHICH LISTS * METAL ROOF AND R-19 FOR A WALL. | | | HOW IS THIS POSSIBLE?ITEMS LIKE THESE WILL BE PART OF | | | MECH/ BLDG REVIEW AND ARE NOTED FOR INFORMATION. | | | | | | ** AS NOTED ABOVE THIS IS NOT AN EXHAUSTED LIST AND | | | ITEMS ARE GIVEN AS A BENEFIT FOR INFORMATION TO GIVE | | | EXAMPLES. | | | 13-415.2, 13-400.3.B, 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | | | | 3) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH | | | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING | | | GIVEN AT THIS TIME. THIS IS ONLY A NOTICE. | | | PLEASE KNOW SOME ELECTRICAL PLANS ALONG WITH ENERGY | | | CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH WERE AT | | | THE END OF THE REVIEW WHICH WERE LABELED AS | | | *IMPORTANT*. THIS PREVIOUS NOTE REQUESTED THE | | | OLD/VOIDED SHEETS TO BE RETURNED SEPARATE FOR | | | REVIEW/COMPARISON OF CHANGES. THESE WERE NOT LOCATED IN | | | SETS OF RESUBMITTED PLANS. | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-08 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-08 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2008-03-10 08:03:22 | ** DENIED REVIEW ** | | | | | | PERMIT # 08020549 | | | | | | 1) NOTE: PLEASE SEE THE CODES LISTED ON COVER SHEET | | | STATES 2001 FBC? | | | PLEASE BE SURE THE ARCHITECTURAL SHEETS AND ELECTRICAL | | | SHEETS. | | | 2004 FBC W/ 2007 REVISIONS. | | | | | | 2) NOTE: PLEASE SEE PLANS WHICH STATES * NEW BUILDING* | | | YET BASED ON PLANS AND PERMIT APPLICATION THIS SEEMS TO | | | BE FOR TENANT BLD OUTS. | | | PLEASE KNOW ADDRESSING WILL BE NEEDED FOR SUITE/UNIT | | | NUMBERS TO BE ASSIGNED. THIS WILL BE SENT TO ADDRESSING | | | REVIEWER. | | | | | | 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS | | | IN NEED. | | | A) PLEASE SEE13-400.3.A, HOW CAN METHOD *A* AS | | | SUBMITTED BE USED WHEN THIS IS NOT FOR WHOLE BUILDING? | | | PLEASE SEE 13-415.2. | | | PLEASE SEE FIXTURE LEGEND ON PLANS IS NOT COMPLETE WITH | | | THE NEW FIXTURES AND CAN NOT VERIFY ANY | | | CALCULATIONS.(MISSING FIXTURE *J* ALL TOGETHER. PLEASE | | | SEE THE NUMBER OF FIXTURES AND WATTAGES DO NOT | | | CORRELATE. | | | PLEASE SEE 13-415.2.ABC .1, .1.1, .1.2 AND .1.3. | | | | | | B) PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 AS | | | NO LIGHTING CONTROL SYSTEMS WERE SUBMITTED. | | | PLEASE SUBMIT COMPLETE DETAILS. | | | PLEASE SEE SECTION ABOVE FOR SEPARATE SPACES AS PLANS | | | SHOW NO DEVICES FOR COMPLIANCE. | | | PLEASE SUBMIT MAXIMUM TIMES ON DEVICES. | | | PLEASE SUBMIT TIME SCHEDULING ETC. | | | THERE ARE MANY ITEMS MISSING AT THIS TIME WHICH CAN NOT | | | BE REVIEWED. | | | | | | C) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 FOR REQUIRED | | | NOTES TO BE ON PLANS. | | | | | | 4) NOTE: PLEASE SEE 600.5 AS THE MIN VA FOR SIGN | | | CIRCUIT IS REQUIRED AT 1200VA. | | | | | | 5) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW | | | RECEPTACLE. PLEASE SEE 220.42 FOR LOADS. | | | | | | 6) NOTE: PLEASE SEE MISSING CONTROLS AND CIRCUITING FOR | | | EXTERIOR LIGHTS. ARE THESE ALL EXISTING AND FROM HOUSE | | | PANEL? IF NOT PLEASE SEE 13-415.1.ABC.1.4 AS NOTED | | | ABOVE. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-02 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-02 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2008-06-02 14:43:18 | *****APPROVED***** | | | | | | PLAN SHEET SHEET E-1 STAMPED, INIALED, AND DATED; | | | SHEET TI-1 PREVIOUSLY FIRE-STAMPED ON 5/06/2008. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-06 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-06 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2008-05-06 11:29:07 | *****PROVISO***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED.PLAN SHEET TI-1 STAMPED, INITIALED, | | | AND DATED;SHEET E-1 TO BE FIRE-STAMPED WHEN THE | | | ELECTRICAL REVIEWER HAS BEEN SATISFIED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-31 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2008-03-31 16:01:41 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | | PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS, | | | FIRE LANES) | | | | | | 3.IN ADDITION TO THE ADDRESS NUMBERS ON THE EXTERIOR | | | ELEVATION WHICH FRONTS CORPORATE WAY, THE TENANT SPACE | | | NUMBERS SHALL BE SHOWN.AS PER WEST PALM BEACH CODE, | | | THE UNIT NUMBERS (NOT TO BE INSTALLED ON THE FRONT | | | DOORS) SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS | | | THAN 1" IN WIDTH. UNIT NUMBERS SHALL ALSO BE REQUIRED | | | THE ON/AT THE REAR DOORS.FOR ADDRESSING MATTERS, | | | CONTACT LILI URSU AT 561-822-1239 | | | | | | 4.CLASSIFY THE CONTENTS OF THE OCCUPANCY IN TERMS OF | | | LOW HAZARD, ORDINARY HAZARD, OR HIGH HAZARD DEPENDING | | | ON THE CHARACTER OF MATERIALS STORED, THEIR PACKAGING, | | | AND OTHER FACTORS. | | | | | | 5.THE DOOR IN THE 1-HOUR RATED PARTITION BETWEEN THE | | | BUSINESS AREA (OFFICE) AND THE STORAGE AREA (WAREHOUSE) | | | SHALL BE A MINIMUM 20 MINUTE FIRE-RATING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-13 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-13 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2008-05-13 08:50:24 | TO "COMM" BD#14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-15 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-15 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2008-04-15 15:27:47 | TO "COMM" BD#47 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-25 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2008-02-25 10:47:40 | TO "COMM" BD#55 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-27 |
Time |
14:25 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-05-27 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-04-23 |
Time |
09:03 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-04-23 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2008-04-23 09:17:38 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 2) SEE ENERGY CALCULATIONS PAGE 7, OTHER REQUIRED | | | COMPLIANCE (CHECK LIST), PLEASE COMPLETE, PER 2004 FBC | | | 13-103.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-06 |
Time |
09:31 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-03-06 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2008-03-06 09:49:08 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SEE PLAN PAGE TI-1 SHELL BUILDING DATA SHOWS FBC | | | 2001, THE FBC BEING USED AT THIS TIME IS THE 2004. | | | PLEASE CORRECT. | | | | | | 2) SEE PLAN PAGE MP-1 FRESH AIR CALCULATIONS SHOWS | | | ASHRAE 62-1989, THE ASHRAE BEING USED AT THIS TIME IS | | | THE 62-2004. PLEASE CORRECT. | | | | | | 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR | | | PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND | | | FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). | | | | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND | | | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. | | | AMEND. 106.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-04-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-21 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-21 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2008-04-21 15:43:37 | PASSED/PROVISO--TANKLESS WATER HEATER SHALL BE | | | LISTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-26 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-26 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2008-03-26 18:12:54 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT TI-1 BLDG DATA: BUILD-OUT SHALL BE DESIGNED TO | | | FBC- 2004 W/2007 AMENDMENTS. PLEASE INDICATE ON PLANS. | | | | | | 2. SHT TI-1 INDICATES BOTH STORAGE OCCUPANCY, (13,392 | | | SF), AND BUSINESS, (3,329 SF) TYPICAL SPACE. (SEE | | | TYPICAL SPACE LIFE SAFETY TABULATIONS). PLEASE CLARIFY. | | | IF THE SPACES ARE MIXED OCCUPANCY, INDICATE THE SQUARE | | | FOOTAGE OF EACH OCCUPANCY IN EACH TYPICAL SPACE. | | | | | | 3. ALL MP & E SHEETS. THE ADDRESS IN THE TITLE BLOCK | | | DOES NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA | | | STATE DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCKS OR | | | THE DBPR WEBSITE SO THE ADDRESS REFLECTS. FAC | | | 61G15-23.002(2) & FS 471.025. | | | | | | 4. SHT MP--2 HOT WATER IS REQUIRE TO THE JANITOR SINKS | | | PER SECTION 607.1. PLEASE SHOW COMPLIANCE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|