Plan Review Details - Permit 08020538
Plan Review Stops For Permit 08020538
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By mjacobs Date 2008-03-18 Time 09:38 Rev Time 0.00
Received By mjacobs Date 2008-03-17 Time 13:29 Sent To  
Notes
2008-03-18 09:37:58BUILDING PLAN REVIEW
 PERMIT: 08020538
 ADD: 5301 S. DIXIE HWY
 CONT: PLAN REVIEW ONLY.
 TEL: (561)585-1701
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-18-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 3) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4) FL S S 713.13. NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 5) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 6)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS FOR THE
 EXTERIOR HOLLOW METAL DOOR AND THE STOREFRONT DOOR NEED
 SHALL BE APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PLEASE HI-LIGHT OR CIRCLE THE DOOR WHICH WILL BE
 INSTALLED AT THE PROJECT FROM THE PRODUCT APPROVAL.
  
 7) FBC 106.3.5 INDICATE ON THE DRAWINGS THE FOLLOWING
 INFORMATION.
 A)THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 B) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 C) THE OCCUPANT LOAD, SEE 1004.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 E) PROVIDE THE SCHEMATIC FOR THE FIRE SPRINKLER ON A
 CEILING PLAN IN RELATION WITH THE NEW WALLS.
  
 8)ADDITIONAL INFORMATION IS REQUIRED FOR ALL NEW
 WALLS. ARE THE WALLS CONNECTED TO THE STRUCTURE ABOVE
 OF THE CEILING?SUBMIT A FRAMING DETAIL DRAWING FOR
 THE NEW EXTERIOR WALL SHOWING THE HEADER AND FLOOR
 ATTACHMENT WITH A UL# AND THE FIRE RATING OF THE WALL.
  
 9)THERE IS NO BATHROOM OR DRINKING FOUNTAIN FACILITY
 SHOWN ON THE DRAWINGS, INDICATE THESE SYSTEMS ON THE
 DRAWINGS. THE DRINKING FOUNTAIN SHALL MEET THE
 REQUIREMENTS OF SECTION 11-4.15. FBC 11-4.17.2 WATER
 CLOSETS IN ACCESSIBLE STALLS SHALL COMPLY WITH SECTION
 11-4.116.
  
 10)TABLE 803.5 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 11)SUBMIT A LIFE SAFETY PLAN SHOWING THE MEANS OF
 EGRESS, EXIT ACCESS, EXIT, TRAVEL DISTANCE ETC.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By dpalmer Date 2008-03-06 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 21:03 Sent To  
Notes
2008-03-06 11:01:36** DENIEDREVIEW **
  
 1) NOTE: THE PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW ONCE SUBMITTING FOR PERMIT FOR CONSTRUCTION THIS
 MUST BE DONE BY A LICENSED CONTRACTOR. MAY NOT APPLY
 FOR PERMIT UNDER AN OWNER/BUILDER FOR PROPERTY AS
 LISTED.
 PLEASE SEE FS 489 PART 1.
 THE OWNER/BUILDER DISCLOSURE STATEMENT SUBMITTED HAS
 BEEN VOIDED
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS.
 FBC 2004 W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE)
  
 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY NOTE THAT
 FBC CHAPTER 13 DOES NOT APPLY BECAUSE OF THE SIZE OF
 THE SPACE AND THE BUILDING.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE WHEN FBC CHAPTER 13
 DOES APPLY TO ANY SIZE BUILDING, LIGHTING CONTROLS IN
 BUILDINGS IS ONLY ONE PART TO FBC AND CHAPTER 13.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1.1, .1.2, ETC (PLEASE BE SURE
 TO SEE MECHANICAL REVIEW COMMENTS)
 PLEASE SUBMIT AND SHOW LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4 (BUILDING IS
 SHOWN OVER 5K SQ FT BASED ON AERIALS AND RECORDS.
  
 4) NOTE; PLEASE SEE PLANS CALL FOR EMERGENCY AND EXIT
 LIGHTS TO BE CIRCUITED TO LOCAL CIRCUITS HOWEVER BASED
 ON CIRCUITING AS SHOWN THIS IS NOT DONE.
 700.12F
 ** PANEL SCHEDULE EVEN INDICATES A DEDICATE CIRCUIT??
  
 5) NOTE: PLEASE CLARIFY RISER AS PANEL *A* IS SHOWN AS
 EXISTING YET RISER APPEARS TO BE SHOWN AS PROPOSED
 NEW?
 PLEASE SEE 230.2, 230.70, 230.71, 230.72 AS ONLY ONE
 SERVICE IS PERMITTED FOR THE BUILDING AND ALL MAINS ARE
 REQUIRED TO BE GROUPED.
 AS THE REMAINDER OF THE SERVICE FOR BUILDING ETC DOES
 NOT SHOW ANY OTHER ELECTRICAL THIS NEW SERVICE AS SHOWN
 IS NOT PERMITTED.
  
 6) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS.
 THIS WILL ALSO DEPEND ON SERVICE NOTE ABOVE.
 IN EITHER CASE LOAD CALCULATIONS AS STATED IN THE NEC
 220 NEEDS TO BE SHOWN.
 PLEASE SHOW TRACK LIGHTING LOADS AND HOW THEY WERE
 DETERMINED.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. RECEPTACLE
 LOADS, LIGHTING LOADS ETC.
 220.12, 220.14, 220.42, 220.44, 220.43, 215.3, 230.42
 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR MINIMUM AND ADDITIONAL
 INFORMATION.
  
 7) NOTE: PLEASE SEE 210.62 FOR ANY WINDOW AREAS WHICH
 WILL REQUIRE SHOW WINDOW RECEPTACLE(S). INCLUDE IN
 CALCULATIONS.
 *WINDOW ABOVE DOOR?*
  
 8) NOTE: PLEASE INCLUDE SUITE/UNIT # ON PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-05 21:03:482008-03-05 21:03:48
  
 IN ELEC FOR REVIEW. NOTES WILL FOLLOW ONCE REVIEW IS
 COMPLETED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-03-22 Time 22:17 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 21:37 Sent To  
Notes
2008-03-22 22:17:30*****DENIED*****
  
 1.PLEASE INDICATE IF THE BUILDING HOUSES A SINGLE OR
 MULTIPLE TENANTS.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.INDICATE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THIS
 STRUCTURE.
  
 6.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY.AS PER WEST PALM BEACH CODE, NUMBERS SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 7.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 8.SHOW THE LOCATION OF THE 2A:10 BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2008-02-22 Time 16:33 Sent To  
Notes
2008-02-22 16:38:31TO "COMM" BD#44

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 14:21 Rev Time 0.40
Received By tgordon Date 2008-03-21 Time 14:21 Sent To  
Notes
2008-03-21 14:32:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** FOR PLAN REVIEW ONLY NOT FOR PERMIT.
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR 12"X12"
 RUSKIN LOUVERS, PER FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 15:37 Rev Time 0.00
Received By kstevens Date 2008-03-26 Time 15:37 Sent To  
Notes
2008-03-26 15:38:24NO PLUMBING WORK SHOWN OR INDICATED ON PLANS.--BLDG
 PLAN REVIEW COMMENT REQUESTS LOCATION OF TOILET ROOM &
 DRINKING FOUNTAIN.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By adavila Date 2008-02-27 Time 09:00 Rev Time 0.00
Received By adavila Date 2008-02-26 Time 16:51 Sent To  
Notes
2008-02-27 09:01:05PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY.
  
 2. PROVIDE SETBACK DIMENSIONS TO THE MECHANICAL (COND.)
 UNITS.PLEASE NOTE THAT PER SECTION 94-305(B)(4),
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 3. ALL MECHANICAL EQUIPMENTS SHALL BE SCREENED PER
 SECTION 94-444.
  
 4. THERE IS A DISCREPANCY BETWEEN THE PLANS.SOME
 PLANS ONLY SHOW 1 MECHANICAL (COND.) UNIT, WHILE OTHER
 PLANS SHOW 2 MECHANICAL (COND.) UNITS.PLEASE
 ADDRESS.
  
 5. PROVIDE THE HEIGHT OF THE PARAPET AND THE OVERALL
 BUILDING HEIGHT.
  
 6. PLEASE NOTE THAT IF THE BUILDING IS DEFINED AS A
 NONCONFORMING USE PER ARTICLE XVI OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, THAN ALL REPAIRS AND
 ALTERATIONS SHALL BE SUBJECT TO THE REGULATIONS FOR
 NONCONFORMING USES.
 A. PLEASE PROVIDE THE VALUE OF THE BUILDING/STRUCTURE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.