| Plan Review Stops For Permit 08020534 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-09 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-09 |
Time |
10:59 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-14 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-14 |
Time |
09:26 |
Sent To |
FIRE |
|
| Notes |
| 2008-04-14 09:41:51 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | | FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-26 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-26 |
Time |
15:01 |
Sent To |
FIRE |
|
| Notes |
| 2008-02-26 16:38:41 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | EQUIPMENT TO BE INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-07-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-07-15 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-07-15 |
Time |
11:31 |
Sent To |
E |
|
| Notes |
| 2008-07-15 11:57:48 | *****APPROVED***** | | | | | | PLAN SHEETS SEC-1, SEC-3 THRU SEC-10 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-04-14 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-14 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2008-04-14 12:41:38 | *****UNSAT***** | | | THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEEDS TO BE ADDRESSED: | | | | | | 1.PLEASE INDICATE EXIT DOORS ON PLAN SHEETS TO | | | DETERMINE IF THE ARRANGEMENT IS ALLOWABLE AS PER NFPA | | | 101, LIFE SAFETY CODE, 2003 EDITION.EXIT DOORS HAVE | | | BEEN MARKED ON PLANS, HOWEVERHAND DRAWN MARKINGS ARE | | | NOT ACCEPTED | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW, PLEASE SHOW ON THE PLAN | | | THAT THE ABOVE ITEMS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-06 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-06 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2008-03-06 14:54:24 | *****DENIED***** | | | | | | 1.PLEASE INDICATE EXIT DOORS ON PLAN SHEETS TO | | | DETERMINE IF THE ARRANGEMENT IS ALLOWABLE AS PER NFPA | | | 101, LIFE SAFETY CODE, 2003 EDITION. | | | | | | 2.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | | CONTOL SYSTEM PROVIDED THE CRITERIA OF 7.2.1.6.2 OF | | | NFPA 101 ARE FOLLOWED. | | | | | | TO EXPEDITE THE PLAN REVIEW, PLEASE SHOW ON THE PLAN | | | THAT THE ABOVE ITEMS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-09 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-09 |
Time |
09:18 |
Sent To |
E |
|
| Notes |
| 2008-07-09 09:18:41 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-04-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-11 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-11 |
Time |
08:49 |
Sent To |
FIRE |
|
| Notes |
| 2008-04-11 08:49:28 | TO "F" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-06 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-22 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2008-02-22 14:59:25 | TO "E" BOX |
|
|