| 2008-03-05 20:22:08 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS/DETAILS FOR REQUIRED |
| | GROUNDING ELECTRODE SYSTEM FOR FOOTINGS PER 250.50 |
| | PLEASE INCLUDE ON SHEETS CONTAINING TITLE BLOCKS, |
| | SIGNED, DATED AND SEALED BY THE ELECTRICAL DESIGNER OF |
| | RECORD FOR BASE BUILDING. |
| | |
| | 2) NOTE: PLEASE SUBMIT DETAILS FOR ANY SLAB, UNDER |
| | GROUND CONDUITS, OR DUCT BANKS WHICH MAY BE GETTING |
| | INSTALLED IN FOOTINGS, SLAB ETC. |
| | FBC106.3.5.1.2, 106.1.2 |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |