Plan Review Details - Permit 08020505
Plan Review Stops For Permit 08020505
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 20:12 Sent To  
Notes
2008-03-08 20:12:49** DENIED **
  
 ** 400 S. AUSTRALIAN AVE.
 PERMIT #08020505
  
 ** A PRELIMINARY REVIEW WAS DONE AND PROVIDED TO THE
 ENGINEER SEVERAL MONTHS AGO HOWEVER MOST OF THE SAME
 ITEMS GIVEN ON THAT REVIEW ARE STILL THE SAME ON
 PLANS.
  
 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW
 ELECTRICAL HOWEVER THIS SCOPE OF WORK SHOULD HAVE BEEN
 INCLUDED WITH OTHER SCOPE OF WORK AS APPLIED UNDER
 OTHER PERMIT NUMBERS.
 AS SUBMITTED, EACH SET OF PLANS SUBMITTED UNDER EACH
 PERMIT WILL BE REQUIRED TO CONTAIN ALL OTHER
 INFORMATION FROM OTHER PERMITS. AS EACH IS A SEPARATE
 RECORD AND EACH HAS A DIRECT AFFECT ON THE OTHER
 COMPLETE SETS WILL BE REQUIRED FOR ALL PERMITS. PLEASE
 KNOW AS OF THIS REVIEW A NOTICE HAS BEEN SENT TO
 BUILDING OFFICIAL ON HOW THE PERMITS WERE APPLIED.
 PLEASE SEE REVIEWS UNDER OTHER APPLIED PERMITS. THESE
 MAY ALL BE COMING IN UNDER CONSOLIDATE PERMIT(S) BEFORE
 ALL REVIEWS ARE COMPLETED AND WITH RELEVANT SUB PERMITS
 NEEDED.
 PLANS AND ALL PERMIT APPLICATIONS AND DOCUMENTS AS
 SUBMITTED ARE VERY CONFUSING AS APPLIED EVEN THOUGH
 THIS REVIEWER UNDERSTANDS THE INTENT OF THE PROPOSED
 TOTAL SCOPE OF WORK.
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS UNDER DESIGNS
 FOR:
 NFPA-70 2005
 NFPA-20 2003
 NFPA-110 2002
 NFPA-101 2003
  
 ** THERE ARE TOO MANY ITEMS TO LIST ALL CODE VIOLATIONS
 ON THIS LIST. THE FOLLOWING ARE SOME ITEMS.
  
 3) NOTE: PLEASE SEE NFPA-20, THE FIRE PUMP DISCONNECT
 AND SERVICE EQUIPMENT SHALL NOT BE LOCATED IN THE MAIN
 ELECTRICAL ROOMS.
 PLEASE ALSO SUBMIT COMPLETE INFORMATION FOR FPC, FP,
 FOR LOCKED ROTOR OVER CURRENT PROTECTION ETC. PLEASE
 SEE NEC 695.3, 695.4 AND NFPA-20 CHAPTERS 9 AND 10.
 ETC
 THERE ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR
 CODE COMPLIANCE.
  
 4) NOTE: PLEASE SEE 230.71, 230.70 AS NO MORE THAN 8FT
 OF UNPROTECTED CONDUCTORS SHALL BE PERMITTED INSIDE THE
 BUILDING.
  
 5) NOTE: PLANS SHOWS THE REMOVAL OF THE UN-PERMITTED
 GENERATOR FOR CELL SITE HOWEVER PLANS DO NOT PROVIDE
 ENOUGH INFORMATION ON THIS UNIT. WILL THIS BE REMOVED
 AND RE-INSTALLED UNDER SEPARATE PERMIT, PLANS ETC?
  
 6) NOTE: PLEASE KNOW AS THE SEPARATE PERMIT WAS SUBMIT
 FOR GENERATOR NOT ENOUGH INFORMATION FOR NEW LOADS ON
 PROPOSED
 ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER
 PERMIT APPLICATIONS FOR THIS SAME LOCATION, PLEASE SEE
 ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER
 REVIEWS.
 700, 701, 702
  
 7) NOTE: PLEASE SEE NO RUN TIMES FOR ON-SITE FUEL WAS
 SUBMITTED. PLEASE SEE NFPA-20 9.6.2.2
  
 8) NOTE: PLEASE SEE NFPA-110 ALL, AS THE GENERATOR DOES
 FEED LIFE SAFETY AND LEGALLY REQUIRED LOADS.PLEASE
 SEE 7 FOR LOCATIONS, ELEVATIONS, ETC
  
 9) NOTE: PLEASE SEE PERMIT # 08020653 AS THE GENERATOR
 APPLIED WAS FOR A JOHN DEERE GENERATOR AND THESE PLANS
 SUBMITTED UNDER 08020505 ARE FOR A CATERPILLAR. THE
 SIZE IS NOT THE SAME, ONE IS 150KW AND THE OTHER
 160KW.
  
 10) NOTE: PLEASE SEE MUCH OF THE SERVICE EQUIPMENT AS
 SHOWN DOES NOT CONTAIN ANY VOLTAGES.
 NEC ALL, NFPA AS NOTED.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE NFPA-110 AS THE LIFE SAFETY
 SERVICE EQUIPMENT IS NOT PERMITTED INSIDE ELECTRICAL
 ROOM AS SHOWN.7.1.3, 7.2.2, 7.2.2.1
  
 12) NOTE: PLEASE SEE NO LOAD INFORMATION AND ACTUAL TAP
 LOCATIONS FOR NEW DP WAS LOCATED ON PLANS.
 THE LOAD SUMMARY FOR ( MAIN #1, HOUSE AMPACITY ) DOES
 NOT PROVIDE ENOUGH INFORMATION.
 NEC 220.87 ETC
  
 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO PROPOSED SHED.
  
 14) NOTE:PLEASE KNOW THEVALUE SHALL INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THIS INCLUDES THE
 GENERATOR, ATS ETC.
  
  
 ** THERE ARE MANY ITEMS WHICH ARE NEEDED AND MAY VERY
 WELL BE COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 17:00 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 16:42 Sent To  
Notes
2008-03-25 16:59:09*****DENIED*****
  
  
 1.THE ADDRESS SHOWN ON THE TITLE SHEET (C-1) OF 300
 SEMINOLE AVENUE REFERS TO WHAT/WHERE?
  
 2.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.ON SHEET C-2 & C-3, THE VERBAGE OF "450 S
 AUSTRALIAN AV" IS SHOWN IN THE MIDDLE OF THE PARKING
 LOT.WHAT IS ITS PURPOSE FOR BEING THERE?
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO/EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES, ETC.) .
  
 6.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 7.PROVIDE THE OCCUPANCY TYPE AND OCCUPANT LOAD.
  
 8.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 9.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER IN THE NEW STRUCTURE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 17:02 Rev Time 0.00
Received By mawillia Date 2008-02-22 Time 11:07 Sent To  
Notes
2008-02-22 11:07:17TO "COMM" BD#26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 10:32 Rev Time 0.30
Received By tgordon Date 2008-03-21 Time 10:32 Sent To  
Notes
2008-03-21 10:34:00*** NOTICE ***
 1) A BUILDING PERMIT WILL BE REQUIRED FOR THE FIRE PUMP
 SHED.
  
 2) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS WILL BE NEEDED FOR THE VENTILATION FAN.
  
 3) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS WILL BE NEEDED FOR THE ALUMINUM INTAKE
 LOUVER AND PERHAPS A PRODUCT APPROVAL OR N.O.A.
  
 ** DIESEL GENERATOR UNDER PERMIT #08020683.
  
 NO MECHANICAL WORK TO BE DONE AT THIS TIME. NO
 MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT
 NUMBER APPLIED FOR AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By eschneid Date 2008-02-29 Time 17:12 Rev Time 0.00
Received By eschneid Date 2008-02-29 Time 17:12 Sent To  
Notes
2008-02-29 17:15:11FAILED
  
 RESPOND TO COMMENTS IN WRITING.
  
 1) A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 REFLECTIONS DPD TO APPROVE THE MODIFICATIONS, INCLUDING
 THE ADDITION OF THE PUMP HOUSE AND GENERATOR, IS
 REQUIRED PRIOR TO THE ISSUANCE OF BUILDING PERMITS.
 APPLICATION IS AVAILABLE FROM ERIC SCHNEIDER, PRINCIPAL
 PLANNER.
  
 2)THE ADDRESS OF THE SITE IS 400 SOUTH AUSTRALIAN
 AVENUE.THE PLANS STATE THE ADDRESS AS 300 SEMINOLE
 AVE. ON SHEET C-1.
  
 3) A SURVEY, LESS THAN A YEAR OLD, SHOWING ALL EXISTING
 CONDITIONS AND EASEMENTS IS REQUIRED.
  
 4) HAS THE PLAT THAT SUBDIVIDES THIS PROPERTY FROM 450
 SOUTH AUSTRALIAN AVENUE BEEN RECORDED?IF SO, PLEASE
 PROVIDE THE OR BOOK AND PAGE.
  
 5) IT APPEARS THAT THE LOCATION OF THE PUMP HOUSE AND
 GENERATOR ARE LOCATED ON PARKING SPACES.REQUIRED
 PARKING MAY NOT BE REMOVED.PROVIDE A TABLE WHICH
 LISTS THE PARKING COUNT FOR THE ENTIRE SITE AND THE NEW
 400 SOUTH AUSTRALIAN AVE. PARCEL.THE TABLE SHALL
 INCLUDE THE SQUARE FOOTAGE OF EACH BUILDING.
  
 6) THE GENERATOR SHALL BE SCREENED BY A WALL AND A
 HEDGE.
  
 7) THE FIRE PUMP HOUSE AND THE DOMESTIC WATER STRUCTURE
 REQUIRE FOUNDATION PLANTING ON THE SIDES THAT DO NOT
 HAVE A DOOR.
  
 8) THERE SHALL BE NO REDUCTION IN THE AMOUNT OF
 LANDSCAPE AS PART OF THIS PERMIT.IF LANDSCAPE IS TO
 BE REMOVED WITHIN THE AREA OF WORK, AN EQUAL AMOUNT
 SHALL BE REPLACED IN ANOTHER AREA.
  
 9) A FENCE PERMIT IS REQUIRED FOR THE NEW FENCE AND
 GATE.
  
 10) THE PERMIT SCOPE OF WORK SHEET INCLUDES REFERENCE
 TO AN ELECTRICAL BUILDING WHICH IS NOT SHOWN ON THE
 PLANS.PLEASE CLARIFY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435