| Plan Review Stops For Permit 08020502 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-24 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-24 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2008-03-24 09:36:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.THE SITE PLAN SHOWS THIS AS TWO LOTS, OUR RECORDS | | | SHOW ONE LOT.SEE ZONING COMMENTS REGARDING THE NEW | | | PLAT. | | | | | | 2.SEVERAL PLANS WERE SUBMITTED FOR THIS ADDRESS, AND | | | THERE WERE SOME REFERENCES TO BRADLEY PLACE AND | | | SEMINOLE.PLEASE VERIFY ALL EASEMENT AND ADDRESS | | | REFERENCES AND REVISE AS NECESSARY. | | | | | | 3.SEPARATE PERMITS REQUIRED (INFORMATIONAL ONLY). | | | | | | 4.DECLARE GOVERNING CODE, INCLUDING 2007 | | | REVISIONS/SUPPLEMENTS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-08 |
Time |
20:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-08 |
Time |
20:19 |
Sent To |
|
|
| Notes |
| 2008-03-08 20:22:46 | ** DENIED ** | | | | | | ** 400 S. AUSTRALIAN AVE. | | | PERMIT# 08020502 | | | | | | ** SEE NOTES UNDER ALL OTHER SUBMITTED PERMIT #'S. | | | | | | PLEASE SEE THAT THIS SCOPE OF WORK IS FOR SITE | | | UTILITIES YET THERE AE ELECTRICLA PLANS AND OTHER ITEMS | | | SUBMITTED NOT RELEVANT FOR THIS SCOPE. | | | PLEASE ONLY SUBMIT PLANS FOR APPLIED SCOPE. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-03-18 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-03-18 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2008-03-18 11:33:49 | FAILED FOR FOLLOWING REASONS: | | | | | | | | | 1. WATER /SEWER PLANS MUST BE APPROVED FROM 1000 45TH | | | STREET ENGINEERING BEFORE WE APPROVE. | | | | | | 2. IFYOU ARE DIGGING CITY'S PROPERTY OR RIGHT OF WAY | | | ORPUTTING AN APPROACH, DRIVEWAY, SIDEWALK & CUTTING A | | | CURB IN CITY'S RIGHT OF WAY,YOU NEED CITY'S RIGHT OF | | | WAY APPROVAL FROM WINDEL PALMER 494-1040, 1000 45TH | | | STREET, ENG DEPT.ONCE WE HAVE AN APPROVAL FROM | | | WINDEL PALMER, WE WILL REVIEW YOUR DRAWINGS. | | | | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-25 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-25 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2008-03-25 16:22:27 | *****DENIED***** | | | | | | | | | 1.THE ADDRESS SHOWN ON THE TITLE SHEET (C-1) OF 300 | | | SEMINOLE AVENUE REFERS TO WHAT/WHERE? | | | | | | 2.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN | | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 3.ON SHEET C-2 & C-3, THE VERBAGE OF "450 S | | | AUSTRALIAN AV" IS SHOWN IN THE MIDDLE OF THE PARKING | | | LOT.WHAT IS ITS PURPOSE FOR BEING THERE? | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-25 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-22 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2008-02-22 10:43:39 | TO "COMM" BD#26 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-21 |
Time |
08:59 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-03-21 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2008-03-21 09:01:24 | *** NOTICE *** | | | 1) A BUILDING PERMIT WILL BE REQUIRED FOR THE FIRE PUMP | | | SHED. | | | | | | 2) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS WILL BE NEEDED FOR THE VENTILATION FAN. | | | | | | 3) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS WILL BE NEEDED FOR THE ALUMINUM INTAKE | | | LOUVER AND PERHAPS A PRODUCT APPROVAL OR N.O.A. | | | | | | ** DIESEL GENERATOR UNDER PERMIT #08020683. | | | | | | NO MECHANICAL WORK TO BE DONE AT THIS TIME. NO | | | MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT | | | NUMBER APPLIED FOR AT THIS TIME. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-26 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-26 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-02-29 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-02-29 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2008-02-29 17:10:29 | FAILED | | | | | | RESPOND TO COMMENTS IN WRITING. | | | | | | 1) A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE | | | REFLECTIONS DPD TO APPROVE THE MODIFICATIONS, INCLUDING | | | THE ADDITION OF THE PUMP HOUSE AND GENERATOR, IS | | | REQUIRED PRIOR TO THE ISSUANCE OF BUILDING PERMITS. | | | APPLICATION IS AVAILABLE FROM ERIC SCHNEIDER, PRINCIPAL | | | PLANNER. | | | | | | 2)THE ADDRESS OF THE SITE IS 400 SOUTH AUSTRALIAN | | | AVENUE.THE PLANS STATE THE ADDRESS AS 300 SEMINOLE | | | AVE. ON SHEET C-1. | | | | | | 3) A SURVEY, LESS THAN A YEAR OLD, SHOWING ALL EXISTING | | | CONDITIONS AND EASEMENTS IS REQUIRED. | | | | | | 4) HAS THE PLAT THAT SUBDIVIDES THIS PROPERTY FROM 450 | | | SOUTH AUSTRALIAN AVENUE BEEN RECORDED?IF SO, PLEASE | | | PROVIDE THE OR BOOK AND PAGE. | | | | | | 5) IT APPEARS THAT THE LOCATION OF THE PUMP HOUSE AND | | | GENERATOR ARE LOCATED ON PARKING SPACES.REQUIRED | | | PARKING MAY NOT BE REMOVED.PROVIDE A TABLE WHICH | | | LISTS THE PARKING COUNT FOR THE ENTIRE SITE AND THE NEW | | | 400 SOUTH AUSTRALIAN AVE. PARCEL.THE TABLE SHALL | | | INCLUDE THE SQUARE FOOTAGE OF EACH BUILDING. | | | | | | 6) THE GENERATOR SHALL BE SCREENED BY A WALL AND A | | | HEDGE. | | | | | | 7) THE FIRE PUMP HOUSE AND THE DOMESTIC WATER STRUCTURE | | | REQUIRE FOUNDATION PLANTING ON THE SIDES THAT DO NOT | | | HAVE A DOOR. | | | | | | 8) THERE SHALL BE NO REDUCTION IN THE AMOUNT OF | | | LANDSCAPE AS PART OF THIS PERMIT.IF LANDSCAPE IS TO | | | BE REMOVED WITHIN THE AREA OF WORK, AN EQUAL AMOUNT | | | SHALL BE REPLACED IN ANOTHER AREA. | | | | | | 9) A FENCE PERMIT IS REQUIRED FOR THE NEW FENCE AND | | | GATE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|