Plan Review Details - Permit 08020502
Plan Review Stops For Permit 08020502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By shill Date 2008-03-24 Time 09:26 Rev Time 0.00
Received By shill Date 2008-03-24 Time 09:26 Sent To  
Notes
2008-03-24 09:36:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE SITE PLAN SHOWS THIS AS TWO LOTS, OUR RECORDS
 SHOW ONE LOT.SEE ZONING COMMENTS REGARDING THE NEW
 PLAT.
  
 2.SEVERAL PLANS WERE SUBMITTED FOR THIS ADDRESS, AND
 THERE WERE SOME REFERENCES TO BRADLEY PLACE AND
 SEMINOLE.PLEASE VERIFY ALL EASEMENT AND ADDRESS
 REFERENCES AND REVISE AS NECESSARY.
  
 3.SEPARATE PERMITS REQUIRED (INFORMATIONAL ONLY).
  
 4.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 20:19 Sent To  
Notes
2008-03-08 20:22:46** DENIED **
  
 ** 400 S. AUSTRALIAN AVE.
 PERMIT# 08020502
  
 ** SEE NOTES UNDER ALL OTHER SUBMITTED PERMIT #'S.
  
 PLEASE SEE THAT THIS SCOPE OF WORK IS FOR SITE
 UTILITIES YET THERE AE ELECTRICLA PLANS AND OTHER ITEMS
 SUBMITTED NOT RELEVANT FOR THIS SCOPE.
 PLEASE ONLY SUBMIT PLANS FOR APPLIED SCOPE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By rchokshi Date 2008-03-18 Time 11:33 Rev Time 0.00
Received By rchokshi Date 2008-03-18 Time 11:27 Sent To  
Notes
2008-03-18 11:33:49FAILED FOR FOLLOWING REASONS:
  
  
 1. WATER /SEWER PLANS MUST BE APPROVED FROM 1000 45TH
 STREET ENGINEERING BEFORE WE APPROVE.
  
 2. IFYOU ARE DIGGING CITY'S PROPERTY OR RIGHT OF WAY
 ORPUTTING AN APPROACH, DRIVEWAY, SIDEWALK & CUTTING A
 CURB IN CITY'S RIGHT OF WAY,YOU NEED CITY'S RIGHT OF
 WAY APPROVAL FROM WINDEL PALMER 494-1040, 1000 45TH
 STREET, ENG DEPT.ONCE WE HAVE AN APPROVAL FROM
 WINDEL PALMER, WE WILL REVIEW YOUR DRAWINGS.
  
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 16:23 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 16:16 Sent To  
Notes
2008-03-25 16:22:27*****DENIED*****
  
  
 1.THE ADDRESS SHOWN ON THE TITLE SHEET (C-1) OF 300
 SEMINOLE AVENUE REFERS TO WHAT/WHERE?
  
 2.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.ON SHEET C-2 & C-3, THE VERBAGE OF "450 S
 AUSTRALIAN AV" IS SHOWN IN THE MIDDLE OF THE PARKING
 LOT.WHAT IS ITS PURPOSE FOR BEING THERE?
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 16:16 Rev Time 0.00
Received By mawillia Date 2008-02-22 Time 10:43 Sent To  
Notes
2008-02-22 10:43:39TO "COMM" BD#26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-21 Cont ID  
Sent By tgordon Date 2008-03-21 Time 08:59 Rev Time 0.20
Received By tgordon Date 2008-03-21 Time 08:59 Sent To  
Notes
2008-03-21 09:01:24*** NOTICE ***
 1) A BUILDING PERMIT WILL BE REQUIRED FOR THE FIRE PUMP
 SHED.
  
 2) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS WILL BE NEEDED FOR THE VENTILATION FAN.
  
 3) MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS WILL BE NEEDED FOR THE ALUMINUM INTAKE
 LOUVER AND PERHAPS A PRODUCT APPROVAL OR N.O.A.
  
 ** DIESEL GENERATOR UNDER PERMIT #08020683.
  
 NO MECHANICAL WORK TO BE DONE AT THIS TIME. NO
 MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT
 NUMBER APPLIED FOR AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By kstevens Date 2008-03-26 Time 11:55 Rev Time 0.00
Received By kstevens Date 2008-03-26 Time 11:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By eschneid Date 2008-02-29 Time 17:07 Rev Time 0.00
Received By eschneid Date 2008-02-29 Time 17:07 Sent To  
Notes
2008-02-29 17:10:29FAILED
  
 RESPOND TO COMMENTS IN WRITING.
  
 1) A MINOR PLANNED DEVELOPMENT AMENDMENT TO THE
 REFLECTIONS DPD TO APPROVE THE MODIFICATIONS, INCLUDING
 THE ADDITION OF THE PUMP HOUSE AND GENERATOR, IS
 REQUIRED PRIOR TO THE ISSUANCE OF BUILDING PERMITS.
 APPLICATION IS AVAILABLE FROM ERIC SCHNEIDER, PRINCIPAL
 PLANNER.
  
 2)THE ADDRESS OF THE SITE IS 400 SOUTH AUSTRALIAN
 AVENUE.THE PLANS STATE THE ADDRESS AS 300 SEMINOLE
 AVE. ON SHEET C-1.
  
 3) A SURVEY, LESS THAN A YEAR OLD, SHOWING ALL EXISTING
 CONDITIONS AND EASEMENTS IS REQUIRED.
  
 4) HAS THE PLAT THAT SUBDIVIDES THIS PROPERTY FROM 450
 SOUTH AUSTRALIAN AVENUE BEEN RECORDED?IF SO, PLEASE
 PROVIDE THE OR BOOK AND PAGE.
  
 5) IT APPEARS THAT THE LOCATION OF THE PUMP HOUSE AND
 GENERATOR ARE LOCATED ON PARKING SPACES.REQUIRED
 PARKING MAY NOT BE REMOVED.PROVIDE A TABLE WHICH
 LISTS THE PARKING COUNT FOR THE ENTIRE SITE AND THE NEW
 400 SOUTH AUSTRALIAN AVE. PARCEL.THE TABLE SHALL
 INCLUDE THE SQUARE FOOTAGE OF EACH BUILDING.
  
 6) THE GENERATOR SHALL BE SCREENED BY A WALL AND A
 HEDGE.
  
 7) THE FIRE PUMP HOUSE AND THE DOMESTIC WATER STRUCTURE
 REQUIRE FOUNDATION PLANTING ON THE SIDES THAT DO NOT
 HAVE A DOOR.
  
 8) THERE SHALL BE NO REDUCTION IN THE AMOUNT OF
 LANDSCAPE AS PART OF THIS PERMIT.IF LANDSCAPE IS TO
 BE REMOVED WITHIN THE AREA OF WORK, AN EQUAL AMOUNT
 SHALL BE REPLACED IN ANOTHER AREA.
  
 9) A FENCE PERMIT IS REQUIRED FOR THE NEW FENCE AND
 GATE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.