Plan Review Details - Permit 08020500
Plan Review Stops For Permit 08020500
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-11 Cont ID  
Sent By mjacobs Date 2008-04-11 Time 18:59 Rev Time 0.00
Received By mjacobs Date 2008-04-11 Time 18:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-22 Cont ID  
Sent By mjacobs Date 2008-03-22 Time 11:09 Rev Time 0.00
Received By mjacobs Date 2008-03-22 Time 09:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By mjacobs Date 2008-02-27 Time 14:14 Rev Time 0.00
Received By   Date 2008-02-28 Time 09:17 Sent To  
Notes
2008-02-27 14:14:45 
 BUILDING PLAN REVIEW
 PERMIT: 08020500
 ADD: 1920 WEKIVA WAY SUITE 301
 CONT: PHOENIX REALTY HOMES INC.
 TEL: (561)799-5900
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-27-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)THE BUILDING CONSTRUCTION TYPE FOR THE BASE
 BUILDING IS TYPE V-B; HOWEVER, THE PLANS FOR THE
 INTERIOR BUILD-OUT INDICATE THE BUILDING AS TYPE IIB ON
 SHEET T.1. NOTE: PER FBC 602.2 ANY WOOD USED IN TYPE
 IIB BUILDINGS SHALL BE FIRE-RETARDANT-TREATED WOOD.
  
 5)SHEET A.3 DETAIL #6 THE SLAB INFILL SHALL HAVE
 STEEL REINFORCEMENT EMBEDDED INTO THE EXISTING FLOOR TO
 PREVENT THE INFILL CONCRETE FROM FALL OUT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-11 Cont ID  
Sent By btrobaug Date 2008-04-11 Time 12:47 Rev Time 0.00
Received By btrobaug Date 2008-04-11 Time 12:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-18 Cont ID  
Sent By btrobaug Date 2008-03-18 Time 16:04 Rev Time 0.00
Received By btrobaug Date 2008-03-18 Time 16:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By btrobaug Date 2008-02-26 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2008-02-26 Time 07:48 Sent To  
Notes
2008-02-26 08:07:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PLANS DO NOT SHOW COMPLIANCE WITH NFPA-75 OR
 NFPA-70 ARTICLE 645, FOR ROOM 111WHICH HOUSES THE I.T
 EQUIPMENT.
  
 2}METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR
 THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE
 BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY
 DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED.
 SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL
 REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. SEE
 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-11 Cont ID  
Sent By mawillia Date 2008-04-11 Time 16:43 Rev Time 0.00
Received By mawillia Date 2008-04-11 Time 16:26 Sent To  
Notes
2008-04-11 16:43:50*****REVISION DATED 4/3/08, APPROVED*****
  
 REVISED PLAN SHEETS A.1, A.2, AND E.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 15:44 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 09:48 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 09:48 Sent To  
Notes
2008-04-10 09:50:46TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 15:39 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 15:39 Sent To  
Notes
2008-03-14 15:42:06TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-28 Cont ID  
Sent By jleech Date 2008-02-28 Time 10:18 Rev Time 0.00
Received By jleech Date 2008-02-21 Time 16:54 Sent To  
Notes
2008-02-21 16:57:21TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 11:29 Rev Time 0.30
Received By tgordon Date 2008-02-25 Time 11:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-18 Cont ID  
Sent By jleech Date 2008-03-18 Time 08:31 Rev Time 0.00
Received By jleech Date 2008-03-18 Time 07:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-28 Cont ID  
Sent By jleech Date 2008-02-28 Time 09:49 Rev Time 0.00
Received By jleech Date 2008-02-28 Time 09:18 Sent To  
Notes
2008-02-28 10:18:00DENIED;
 1. BREAK SINK; IF DOORS ARE INSTALLED UNDER SINK THE
 DOORS MUST ROLE INTO CABINET SO THEY WILL NOT BE A
 TRIPPING PROBLEM OR INTERFER WITH APPROACH.
 2. PAGE P-1 WATER RISER DIAGRAM; WATER HAMMER ARRESTOR
 REQUIRED FOR ICE LINE,SPECOUT TYPE AND SIZE ON PLAN AND
 SHOW ON DIAGRAM. SEE FBCPLUMBING SECTION 604.9.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 08:58 Rev Time 0.00
Received By choops Date 2008-02-25 Time 08:58 Sent To  
Notes
2008-02-25 08:58:25*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.