Plan Review Details - Permit 08020473
Plan Review Stops For Permit 08020473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By mjacobs Date 2008-03-08 Time 13:50 Rev Time 0.00
Received By mjacobs Date 2008-03-08 Time 11:05 Sent To  
Notes
2008-03-08 13:50:38BUILDING PLAN REVIEW
 PERMIT: 08020473
 ADD: 1801 PBL BLVD #300
 CONT: CONSTRUCTION CENTRAL CONS CORP
 TEL: (407)498-0644
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST.
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)NUDELL ARCHITECTS NEEDS TO INDICATE THE CERTIFICATE
 OF AUTHORIZATION IN THE TITLE BLOCK. 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 5)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVAL
 FOR THE NEW LOUVER WINDOW
  
 6)THE PLANS NEED TO CLEARLY SHOW THE LOCATION OF THE
 GENERATOR IN REFERENCE TO THE REQUIRED CLEARANCE FOR
 MAINTENANCE AND REPAIR WORK. INDICATE THE DISTANCE THE
 GENERATOR WILL BE PLACED FROM THE WALLS. IF THE NEW
 GENERATOR LOADS INCREASE, A STRUCTURAL ENGINEER SHALL
 PROVIDE ENGINEERED CALCULATIONS STATING THAT THE
 EXISTING FLOOR LOAD IS CAPABLE OF SUPPORTING THE WEIGHT
 OF THE GENERATOR. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND BE OF SUFFICIENT CLARITY TO INDICATE
 THE NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM THE PROVISIONS OF THE CODE
 AND RELEVANT LAWS, ORDINANCES RULES AND REGULATIONS.
 FBC 106.1.1.
  
 7)PLEASE INDICATE WHAT MATERIALS WILL BE USED TO
 ATTACH THE ACCESS LADDER TO THE EXISTING STRUCTURE.
 INDICATE THE FIRE RESISTANCE RATING OF THE ROOM WHERE
 THE GENERATOR IS INSTALLED.
  
 8)THE CLAIMED VALUE ON THE PERMIT IS LOW. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, MECHANICAL INTERIOR FINISH
 ARCHITECTURAL AND DESIGN FEES AND OVER HEAD AND PROFIT
 EXCLUDING LAND. FBC 108.3*.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By dpalmer Date 2008-03-06 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2008-03-06 Time 12:06 Sent To  
Notes
2008-03-06 12:06:55** DENIEDREVIEW **
  
 1) NOTE: PLANS ARE REQUIRED TO SHOW THE FOLLOWING
 MINIMUM CODES. THERE ARE REFERENCES TO NUMEROUS OTHER
 CODES WHICH DO NOT APPLY.
 FBC 2004 W/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER PER
 FLORIDA STATUTES 471.023 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FS 471.003 AS AN ARCHITECT MAY NOT
 PERFORM THE ELECTRICAL FOR 277/480V SYSTEMS.
  
 4) NOTE: PLEASE KNOW THE LOCATION OF THE GENERATOR
 NEEDS TO BE REVIEW AND GONE OVER WITH THE FIRE MARSHAL.
 PLANS DO NOT SHOW ANY SHUT DOWN OF GENERATOR AS
 REQUIRED PER 230.72, 445.18.
 ** EXAMPLE, FIRE DEPARTMENT PERSONNEL NEEDS TO SHUT
 DOWN POWER IN AN EMERGENCY YET THE GENERATOR WILL START
 UP RE-FEEDING POWER INTO THE BUILDING. HOW WILL THIS
 POWER BE TURNED OFF?
 ** FYI, SHUNT TRIPS ARE NOT PERMITTED**.
 230.76, 230.79
  
 5) NOTE: PLEASE PROVIDE A LAYOUT OF THE ROOM SHOWING
 ALL DIMENSIONS FOR UNIT AND LOCATION OF NEW TRANSFER
 SWITCH. BASED ON THE LOCATIONOF THE EXISTING
 EQUIPMENT THIS DOES NOT MEET 110.26 OR REQUIRED
 CLEARANCES PER NFPA-110CHAPTER 7.
 PLEASE SEE PLANS WHICH SHOW THE GENERATOR DIRECTLY
 IN-FRONT OF EQUIPMENT WHICH IS NOT PERMITTED.
 PLEASE SEE ALL OF CHAPTER & MORE SPECIFICALLY LOCATION
 IN 7.2
 PLEASE PROVIDE LIGHTING LEVELS PER 7.3.3 FOR MINIMUM OF
 30FT CANDLES AND ALSO AN EMERGENCY BATTERY BACK UP
 FIXTURE MEETING MINIMUM LIGHTING LEVELS.
 700.12F, 700.16 ETC
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST, SET UP, CRANE SERVICE ETC.
 THE VALUE AS APPLIED AT $24K IS LOW FOR ALL WORK AS
 SHOWNAND WORK REQUIRED BUT NOT IN DESIGN.
 FBC 108.3 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE NFPA-110 7.10.3 AND PROVIDE MORE
 INFORMATION ON EXHAUST SYSTEM. BASED ON THE PIPING
 SHOWN EXISTING AND NEW THERE IS NOT ENOUGH INFORMATION
 FOR REVIEW AND THE ITEMS LISTED IN SECTION ABOVE ARE
 NTO SHOWN. EXAMPLE: FLEXIBLE CONNECTION, RAIN-CAP ETC
  
 8) NOTE: PLEASE PROVIDE WHAT ELECTRICAL SYSTEMS THIS
 GENERATOR FEEDS. PLEASE PROVIDE RUN TIMES FOR ANY LIFE
 SAFETY OR LEGALLY REQUIRED LOADS.
 700, 701, NFPA-110 CHAPTER 4 ETC
 AS NO INFORMATION WAS SUBMITTED IT IS UNCLEAR WHAT
 CODES MAY OR MAY NOT APPLY. NOT ENOUGH TO GO ON AT THIS
 TIME.
  
 9) NOTE: PLEASE PROVIDE RISER DIAGRAM AND HOW THIS UNIT
 WILL BE WIRED IN. WHAT SIZE OF UNIT? CONDUCTORS ETC?
 PLANS SHOW RANGES FOR EQUIPMENT AND DOE NOT PROVIDE ANY
 DETAILS.
 NEC 2005
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 10) NOTE: PLEASE BE AWARE THAT A GC MAY NOT PERFORM
 ELECTRICAL SCOPE OF WORK. PLEASE KNOW THAT ELECTRICAL
 CONTRACTOR MAY REFERENCE PLANS ONCE ISSUED FOR PERMIT.
  
 PLEASE SEE BUILDING REVIEW COMMENTS WITH RESPECT TO
 STRUCTURAL COMMENTS OFADDING NEW FLOOR LOADS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-03-22 Time 20:38 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 20:12 Sent To  
Notes
2008-03-22 21:31:57*****DENIED*****
  
 1.PLEASE INDICATE THE USE OF THE NEW GENERATOR.IS
 IT FOR STANDBY POWER, EMERGENCY POWER, OR BOTH?
  
 2.SHOW THE LOCATION OF THE GENERATOR IN REFERENCE TO
 THE REST OF THE BUILDING.
  
 3.HOW IS MANUAL SHUT DOWM OF THE SYSTEM
 ACCOMPLISHED?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By mperson Date 2008-03-26 Time 13:46 Rev Time 0.00
Received By mperson Date 2008-03-26 Time 13:46 Sent To PC
Notes
2008-03-26 13:47:45NOTE: FUEL SUPPLY IS DIESEL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-26 Cont ID  
Sent By mperson Date 2008-03-26 Time 13:57 Rev Time 0.00
Received By mperson Date 2008-02-21 Time 12:09 Sent To  
Notes
2008-02-21 12:11:56TO "COMM" BD#14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By tgordon Date 2008-03-06 Time 07:57 Rev Time 0.45
Received By tgordon Date 2008-03-06 Time 07:57 Sent To  
Notes
2008-03-06 13:54:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE BACK WALL OF THE FUEL SPILL CONTAINMENT AREA
 APPEARS TO BE SHEET ROCK AND THAT WOULD ABSORB AND WICK
 ANY FUEL SPILL, PLEASE CORRECT, SEE NFPA 37 6.3.2.4.
  