| 2008-03-06 12:06:55 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLANS ARE REQUIRED TO SHOW THE FOLLOWING |
| | MINIMUM CODES. THERE ARE REFERENCES TO NUMEROUS OTHER |
| | CODES WHICH DO NOT APPLY. |
| | FBC 2004 W/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER PER |
| | FLORIDA STATUTES 471.023 AND FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.002. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 3) NOTE: PLEASE SEE FS 471.003 AS AN ARCHITECT MAY NOT |
| | PERFORM THE ELECTRICAL FOR 277/480V SYSTEMS. |
| | |
| | 4) NOTE: PLEASE KNOW THE LOCATION OF THE GENERATOR |
| | NEEDS TO BE REVIEW AND GONE OVER WITH THE FIRE MARSHAL. |
| | PLANS DO NOT SHOW ANY SHUT DOWN OF GENERATOR AS |
| | REQUIRED PER 230.72, 445.18. |
| | ** EXAMPLE, FIRE DEPARTMENT PERSONNEL NEEDS TO SHUT |
| | DOWN POWER IN AN EMERGENCY YET THE GENERATOR WILL START |
| | UP RE-FEEDING POWER INTO THE BUILDING. HOW WILL THIS |
| | POWER BE TURNED OFF? |
| | ** FYI, SHUNT TRIPS ARE NOT PERMITTED**. |
| | 230.76, 230.79 |
| | |
| | 5) NOTE: PLEASE PROVIDE A LAYOUT OF THE ROOM SHOWING |
| | ALL DIMENSIONS FOR UNIT AND LOCATION OF NEW TRANSFER |
| | SWITCH. BASED ON THE LOCATIONOF THE EXISTING |
| | EQUIPMENT THIS DOES NOT MEET 110.26 OR REQUIRED |
| | CLEARANCES PER NFPA-110CHAPTER 7. |
| | PLEASE SEE PLANS WHICH SHOW THE GENERATOR DIRECTLY |
| | IN-FRONT OF EQUIPMENT WHICH IS NOT PERMITTED. |
| | PLEASE SEE ALL OF CHAPTER & MORE SPECIFICALLY LOCATION |
| | IN 7.2 |
| | PLEASE PROVIDE LIGHTING LEVELS PER 7.3.3 FOR MINIMUM OF |
| | 30FT CANDLES AND ALSO AN EMERGENCY BATTERY BACK UP |
| | FIXTURE MEETING MINIMUM LIGHTING LEVELS. |
| | 700.12F, 700.16 ETC |
| | |
| | 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST, SET UP, CRANE SERVICE ETC. |
| | THE VALUE AS APPLIED AT $24K IS LOW FOR ALL WORK AS |
| | SHOWNAND WORK REQUIRED BUT NOT IN DESIGN. |
| | FBC 108.3 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE SEE NFPA-110 7.10.3 AND PROVIDE MORE |
| | INFORMATION ON EXHAUST SYSTEM. BASED ON THE PIPING |
| | SHOWN EXISTING AND NEW THERE IS NOT ENOUGH INFORMATION |
| | FOR REVIEW AND THE ITEMS LISTED IN SECTION ABOVE ARE |
| | NTO SHOWN. EXAMPLE: FLEXIBLE CONNECTION, RAIN-CAP ETC |
| | |
| | 8) NOTE: PLEASE PROVIDE WHAT ELECTRICAL SYSTEMS THIS |
| | GENERATOR FEEDS. PLEASE PROVIDE RUN TIMES FOR ANY LIFE |
| | SAFETY OR LEGALLY REQUIRED LOADS. |
| | 700, 701, NFPA-110 CHAPTER 4 ETC |
| | AS NO INFORMATION WAS SUBMITTED IT IS UNCLEAR WHAT |
| | CODES MAY OR MAY NOT APPLY. NOT ENOUGH TO GO ON AT THIS |
| | TIME. |
| | |
| | 9) NOTE: PLEASE PROVIDE RISER DIAGRAM AND HOW THIS UNIT |
| | WILL BE WIRED IN. WHAT SIZE OF UNIT? CONDUCTORS ETC? |
| | PLANS SHOW RANGES FOR EQUIPMENT AND DOE NOT PROVIDE ANY |
| | DETAILS. |
| | NEC 2005 |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 10) NOTE: PLEASE BE AWARE THAT A GC MAY NOT PERFORM |
| | ELECTRICAL SCOPE OF WORK. PLEASE KNOW THAT ELECTRICAL |
| | CONTRACTOR MAY REFERENCE PLANS ONCE ISSUED FOR PERMIT. |
| | |
| | PLEASE SEE BUILDING REVIEW COMMENTS WITH RESPECT TO |
| | STRUCTURAL COMMENTS OFADDING NEW FLOOR LOADS. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE |
| | MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |