Plan Review Details - Permit 08020399
Plan Review Stops For Permit 08020399
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-12-01 Cont ID  
Sent By shill Date 2008-12-01 Time 10:14 Rev Time 0.00
Received By shill Date 2008-12-01 Time 10:14 Sent To  
Notes
2008-12-01 10:15:02REVISION #10 & 11
 A0.2, A0.2, A1, A2, A3, A4, A5, A6, A7, A8, A9, A10

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-12-01 Cont ID  
Sent By shill Date 2008-12-01 Time 10:05 Rev Time 0.00
Received By shill Date 2008-12-01 Time 09:14 Sent To  
Notes
2008-12-01 10:14:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. A LETTER REGARDING INSPECTIONS WAS INCLUDED WITH THE
 REVISION. THE LETTER WAS NOT SEALED AND DATED BY THE
 ENGINEER, AND IT IS NOT CLEAR WHY IT WAS INCLUDED WITH
 THIS REVISION AS INSPECTIONS ARE USUALLY HANDLED BY THE
 INSPECTORS (NOT PLAN REVIEW). PLEASE COORDINATE WITH
 THE BUILDING INSPECTOR OR CLARIFY PURPOSE OF THE
 LETTER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-11 Cont ID  
Sent By shill Date 2008-07-11 Time 09:38 Rev Time 0.00
Received By shill Date 2008-07-11 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 09:32 Rev Time 0.00
Received By shill Date 2008-07-01 Time 09:32 Sent To  
Notes
2008-07-01 16:02:26APPLICATION SUBMITTED AT FRONT COUNTER
  
 BUILDING REVIEW PASSED; HOWEVER, AS ELECTRIC FAILED, A
 NEW BUILDING REVIEW WILL BE REQUIRED WHEN NEW ENERGY
 CALCS ARE SUBMITTED ADDRESSING ELECTRIC COMMENTS.
2008-07-01 09:34:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A PERMIT APPLICATION IS REQUIRED.THE OLD SHEETS
 AND PERMIT APPLICATION WERE NOT SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By shill Date 2008-06-02 Time 11:07 Rev Time 0.00
Received By shill Date 2008-06-02 Time 11:07 Sent To  
Notes
2008-06-02 11:18:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE A1, CONDITION TYPE P8, STATES PLYWOOD TO 8' IN
 ELECTRIC ROOM, WHICH IS IN CONFLICT WITH A9, PARTITION
 TYPE 3A AND 3B.PLEASE CORRELATE.
  
 2.THE MEP SHEETS STILL SHOW THE COMPANY NAME OF
 STEVEN L COHEN & ASSOCIATES PA.THIS NAME IS ALSO
 INCLUDED ON THE COVER SHEET.PLEASE INCLUDE THE
 CERTIFICATE OF AUTHORIZATION FS481 OR REMOVE THE NAME
 AS DISCUSSED.
  
 3.SEE THE PREVIOUS LIST IN REGARDS TO ENERGY CALCS.
 THE PREVIOUS LIST STATED THAT THE HOT WATER HEATER WAS
 NOT INCLUDED IN THE INPUT DATA REPORT; THIS DOES NOT
 APPEAR ON THE NEW ENERGY CALCS.PLEASE CONFIRM THAT
 ALL BUILDING COMPONENTS ARE INCLUDED AND CORRELATE WITH
 THE PLANS.
  
 4.PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By shill Date 2008-04-09 Time 11:47 Rev Time 0.00
Received By shill Date 2008-04-09 Time 11:47 Sent To  
Notes
2008-04-09 11:48:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE
 ARCHITECTURE THROUGH A COMPANY, FS481.219(2).
 APPLICATION IS IN PROGRESS; THIS MUST BE APPROVED AND
 THE CERTIFICATE OF AUTHORIZATION NUMBER PRINTED ON EACH
 SHEET PRIOR TO PERMIT ISSUANCE FAC61G1-16.004.
  
 2. THE VALUE HAS BEEN ADJUSTED.ALSO NOTE THAT THE
 VALUE OF THE SHELL BUILDING HAS BEEN ADJUSTED BASED ON
 ICC VALUATION TABLES, SEE ATTACHED.ADDITIONAL FEES
 ARE REQUIRED FOR BOTH THE SHELL BUILDING AND THIS
 PERMIT; PLEASE PAY IMMEDIATELY.NOTE THAT INSPECTIONS
 CANNOT BE SCHEDULED FOR THE ISSUED PERMIT UNTIL FEES
 ARE PAID.THE VALUATION DECLARED BY ORIGINAL
 CONTRACTOR WAS TOO LOW.
  
 3. A1, NOTE N1, NOTE IS INCOMPLETE.
  
 4. A1, CONDITION TYPES, STATES THAT PLYWOOD WILL BE
 INSTALLED 6IN ABOVE THE CEILING.SEE FBC603,
 COMBUSTIBLES NOT PERMITTED IN TYPE I AND II BUILDINGS.
 THIS DOES NOT APPEAR TO FALL UNDER ANY OF THE
 EXEMPTIONS.
  
 5. EXISTING ENTRY RAMP, SPECIFY SLOPE, FBC11-4.3.
  
 6. ELEVATION 5 A6 WATER FOUNTAIN CONFLICTS WITH 3A17
 AND FLOOR PLAN.
  
 7. 8 17, URINAL, SEE FBC11-4.18.2, SHOULD BE 17INCHES.
 SEE PLUMBING COMMENTS.
  
 8. THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE OF
 COMPLETION; THE CONTRACTOR FOR THIS TENANT SPACE IS
 DIFFERENT FROM THE BASE BUILDING AND WILL REQUIRE A
 LETTER FROM THE BASE BUILDING CONTRACTOR ALLOWING THE
 TENANT BUILDOUT CONTRACTOR TO START WORK ON THIS TENANT
 SPACE BEFORE THE C OF C FOR THE BASE BUILDING HAS BEEN
 ISSUED.THE DEVELOPER AND BOTH CONTRACTORS WILL BE
 REQUIRED TO SUBMIT A LETTER STATING THAT THEY
 UNDERSTAND THAT ANY DISPUTE OVER RESPONSIBILITY DOES
 NOT RELIEVE THEM FROM THE JOINT RESPONSIBILITY TO
 COMPLY WITH THE BUILDING CODE.
  
 9. FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).PLEASE ADVISE IF A FIRE SPRINKLER PERMIT
 HAS ALREADY BEEN ISSUED.
  
 10. DECLARE MAXIMUM RACK HEIGHT ON THE PLAN.
  
 11.SEE ELECTRIC COMMENTS REGARDING ENERGY CALC
 VERSION.PLEASE CONFIRM ALL BUILDING COMPONENTS SUCH
 AS WINDOWS, DOORS, HOT WATER HEATER, INSULATION, ETC.
 FOR INSTANCE, NO HOT WATER HEATER IS SHOWN AND GLASS
 STOREFRONT IS NOT REFLECTED IN THE ENERGY CALC DOOR AND
 WINDOW DATA.THIS IS A STATUTORY AND FLORIDA BUILDING
 CODE REQUIREMENT.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 11:21 Sent To PC
Notes
2008-12-24 11:21:52REV, E1, 7

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-09 Cont ID  
Sent By dpalmer Date 2008-12-09 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2008-12-09 Time 13:27 Sent To  
Notes
2008-12-09 13:27:40 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE REVISE ALL CIRCUITING ON PLANS WHICH
 WILL CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. THE
 USE OF GENERAL RECEPTACLES OR GENERAL LIGHTING IS NOT
 ACCEPTABLE. PLEASE SEE 408.4 WHICH STATES ALL
 CIRCUITING SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED.
 PLEASE ALSO SEE ITEMS SUCH AS ROOF-TOP GFI FOR A/C
 EQUIPMENT.210.63 THE FOLLOWING IS BASED ON COMMENTARY
 TAKEN DIRECTLY FROM THE NEC HANDBOOK IN SECTION 408.4.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.**
  
  
 2) NOTE: PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2.
 PLEASE REVISE LIGHTING PERFORMANCE CALCULATIONS FOR
 ITEMS REVISED ON PLANS.
 PLEASE SEE AREAS SUCH AS STORAGE WHICH INDICATES AN
 ALLOWANCE GREATER THAN THE ALLOWANCES LISTED ON TABLE
 13-415.2.B.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 09:51 Sent To  
Notes
2008-07-03 09:52:23NO GROSS ERRORS ON ELECTRICAL PART OF THE ENERGY
 CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-01 Cont ID  
Sent By dpalmer Date 2008-07-01 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2008-07-01 Time 14:18 Sent To  
Notes
2008-07-01 14:19:26** TEMPORARY DENIED REVIEW **
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS FOR BUILD
 OUT ARE SHOWING LIGHTING WHICH IS PART OF THE SHELL.
 ONLY THE LIGHTING FROM THE BUILD OUT SERVICE IS TO BE
 ON THE INPUT DATA REPORT.
 CALLED THE ENGINEER TWICE FOR ELECTRICAL AS WELL AS
 MECHANICAL AND THEY WILL SEND REVISED SIGNED, DATED AND
 SEALED CALCULATIONS. WENT OVER THE FACT OF REVISED
 CALCULATIONS FOR EXTERIOR LIGHTS WHICH ARE SHOWN ON
 STAPLES BUILD OUT INPUT DATA REPORT ARE NOT ACCURATE
 AND IS STRONGLY SUGGESTED THESE BE GONE OVER BEFORE
 SENDING REVISED TO THIS OFFICE.
  
 2) NOTE: ORIGINAL PERMIT APPLICATION NOT IN PACKAGE.
 NEED APPLICATION. CALLED AND LEFT ON MESSAGE ON
 CONTRACTOR'S CELL PHONE VOICE MAIL.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-29 Cont ID  
Sent By dpalmer Date 2008-05-29 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2008-05-29 Time 09:15 Sent To  
Notes
2008-05-29 09:15:12** DENIED 2ND REVIEW **
  
 ** SECOND REVIEW UNDER NEW PERMIT APPLICATION.
  
 ** PLEASE SEE SOME OF THE NOTES FROM THE PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING. PLEASE SEE SOME
 NEW COMMENTS BASED ON REVISED PLANS, REVISED SCOPE OF
 WORK AT LOCATION.
  
 1) NOTE: PLEASE KNOW AS STATED ON PREVIOUS ELECTRICAL
 REVIEW THE BASE BUILDING/SHELL PLANS HAVE NOT BEEN
 ISSUED FOR PERMITTING OF BASE BUILDINGS ELECTRICAL
 SYSTEMS. THIS MAY AFFECT THE BUILD OUT PLANS FOR
 ELECTRICAL DESIGNATIONS OF EQUIPMENT ETC.
 PLEASE BE SURE ALL COORDINATION IS ADDRESSED BETWEEN
 PERMITS. ANY REVISIONS MADE TO BASE BUILDING NEED TO BE
 COORDINATED WITH BUILD OUT PLANS AND VICE-VERSA.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK FOR BUILD OUT HAS STILL NOT BEEN ADJUSTED. THIS
 SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN
 COSTS ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THIS SHALL INCLUDE LIGHTING, LIGHTING
 SYSTEMS, EQUIPMENT ETC.
 FBC 108.3
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2.ABC.1.1,
 .1.2, .1.3 AND 13-415.2.
 AS STATED ON ALL PREVIOUS REVIEWS, PLEASER BE SURE
 *ALL* INFORMATION ON PLANS WITH RESPECT TO LIGHTING AND
 ALL OTHER BUILDING COMPONENTS COORDINATES WITH THE
 INPUT DATA REPORT/ SUMMARY SHEETS OF THE SUBMITTED
 ENERGY CALCULATIONS. THE INPUT DATA REPORT WILL BE
 NOTED AS IDR FOR THE REMAINDER OF THIS COMMENT.
 THE INFORMATION ON THE IDR STILL DOES CORRELATE WITH
 PLANS. THERE WILL BE SOME EXAMPLES GIVEN BELOW. HOWEVER
 THESE ARE ONLY SOME EXAMPLES. THIS IS NOT AN
 EXHAUSTIVE/EXHAUSTED LIST.
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTS FOR SPACES CALLED OUT AS
 UTILITY ROOMS. IT SEEMS ALL THREE OF THESE ROOMS ARE
 BEING LUMPED INTO ONE SPACE DESIGNATION WHICH IS OK TO
 DO. HOWEVER HOW IS THIS POSSIBLE WHEN ALL THREE
 FIXTURES ARE DIFFERENT AND CONTAIN DIFFERENT WATTAGES?
 PLEASE SEPARATE SPACES IF ALL FIXTURES ARE NOT GOING TO
 BE THE SAME.
 METHOD B, PER TABLE 13-415.2.B SPACE BY SPACE IS TO BE
 SHOWN AS SPACE BY SPACE.
 FOR EXAMPLE:
 PLEASE EXPLAIN WHERE SOME FIXTURES ON PLANS ARE LOCATED
 IN THE IDR. ONE FIXTURE IS THE DOCK LIGHT WHICH IS A
 90W FIXTURE. THERE ARE NO 90W FIXTURES SHOWN ON THE
 IDR.
 FOR EXAMPLE:
 PLEASE SEE ROOMS 105/107 WHICH ARE SEPARATE ROOMS. BOTH
 OF THESE ROOMS AND FIXTURES ARE LISTED ON THE IDR IN
 ONE SPACE.
 FOR EXAMPLE:
 PLEASE SEE THE RETAIL SALES AREA. PLEASE SEE THE COUNT
 OF THE FIXTURES LISTED AS *B* ARE LOWER ON THE IDR THAN
 THE NUMBER OF FIXTURES ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE EXTERIOR LIGHTS AS THE *J* FIXTURES AS
 LISTED ON THE FIXTURE LEGEND AND ON PLANS DOES NOT
 APPEAR IN THE IDR AT ALL. IN FACT THERE ARE NO 175W
 FIXTURES.
 FOR EXAMPLE:
 PLEASE EXPLAIN THE ELECTRICAL SYMBOL LEGEND ON SHEET
 E-8 WHICH CONTAINS DIFFERENT FIXTURES AND DESIGNATIONS
 THAN THAT OF THE FIXTURES ON THE SAME PAGE ON LIGHTING
 LEGEND.
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH DOES NOT CONTAIN ANY
 ELECTRICAL WATER HEATER YET THE PLANS MOST CERTAINLY
 DOES SHOW A WATER HEATER. THE IDR IS ACTUALLY *BLANK*
 FOR THE SECTIONS FOR WATER HEATERS.
 ** IMPORTANT, PLEASE BE SURE TO SEE ALL OTHER BUILDING
 COMPONENTS. THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO
 PLEASE BE SURE TO CORRELATE ALL ITEMS ON PLANS WITH
 THAT OF THE IDR.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR
 INTERIOR AND PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR.
  
 4) NOTE: PLEASE SEE SHEET E-4 WHICH STATES THE NEW OVER
 HEAD FEEDERS WILL BE GOING TO A MAIN ELECTRICAL ROOM.
 PLEASE ADJUST AND COORDINATE PLANS AS THE MAIN
 ELECTRICAL ROOM WHICH USED TO BE ON THE BASE BUILDING
 IS NO LONGER PART OF THE BASE BUILDING DESIGN.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS BEING
 GIVEN AT THIS TIME. THIS IS ONLY A NOTICE.
  
 6) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN
 THE LEFT HAND SIDE OF PLANS. THESE SHOULD BE PLACED IN
 BINDER(S)/ FOLDERS IN A NEAT AND ORDERLY FASHION.
 AS STATED ON PREVIOUS REVIEW: PLEASE BE SURE TO REMOVE
 ALL DOCUMENTS FROM PREVIOUS EXPIRED PERMIT APPLICATION.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-07 Cont ID  
Sent By dpalmer Date 2008-03-07 Time 11:35 Rev Time 0.00
Received By dpalmer Date 2008-03-06 Time 17:56 Sent To  
Notes
2008-03-08 11:43:28** NOTE ADDED**
  
 1) NOTE: PLEASE VERIFY ALL PANELS WHICH ARE SHWON AS
 FEED-THRU LUGS. SOME PANELS ARE SHOWN AS FEED-THRU YET
 THERE ARE OCP DEVICES IN THOSE SAME PANELS FOR SUB
 PANELS. (P4)
2008-03-07 11:35:28** DENIED REVIEW **
  
 *** FIRST REVIEW UNDER NEW APPLIED PERMIT.
  
 2029 OKEECHOBEE BLVD.
  
 ** PLEASE KNOW A FULL AND COMPLETE REVIEW FOR MINIMUM
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME AS THERE
 ARE SEVERAL ITEMS STILL NEEDED TO BE COORDINATED WITH
 THE BASE BUILDING.
  
  
  
 1) NOTE: PLEASE KNOW AT THIS TIME NO PERMIT, PLANS ETC
 HAVE BEEN APPLIED FOR ANY ELECTRICAL SYSTEMS OR OTHER
 TRADES FOR ACTUAL SHELL. THE ONLY PERMIT APPLIED FOR
 AND ISSUED IS FOR STRUCTURAL OF SHELL ONLY AND NO OTHER
 WORK. NO WALLS, NO ELECTRICAL, NO PLUMBING ETC. THE
 SHELL OWNER AND CONTRACTOR HAVE BEEN NOTIFIED TO SUBMIT
 FOR PERMIT AND COMPLETE PLANS FOR SHELL.
 AS MANY ITEMS ON THESE PLANS ARE SHOWN AS EXISTING,
 THIS IS MOST DEFINITELY NOT THE CASE.
 NO BUILD OUT PLANS WILL BE ISSUED UNTIL BASE SHELL
 BUILDING PLANS AND PERMIT APPLICATION HAVE BEEN
 COMPLETED, SUBMITTED AND ISSUED FOR PERMIT.
 ** THIS WILL AFFECT OTHER ITEMS ON REVIEWS BELOW.
  
 2) NOTE: PLEASE SEE THESE PLANS ARE NOW BEING SUBMITTED
 UNDER COMPLETELY NEW PERMIT. MANY DOCUMENTS AND SHEETS
 IN PACKAGE STILL REFLECT PREVIOUS EXPIRED PERMIT.
 PLEASE ONLY SUBMIT RELEVANT DOCUMENTS FOR NEW PERMIT
 APPLICATION BEING MADE. PLEASE KNOW THAT SOMECOMMENTS
 FROM THE THREE PREVIOUS REVIEWS UNDER EXPIRED PERMIT
 ARE STILL ALSO IN NEED OF ADDRESSING AND HAVE BEEN
 REPEATED IN THIS REVIEW. PLEASE SEE FLORIDA STATUTES
 553.80(2)(B) WAS GIVEN ON TWO PREVIOUS REVIEWS WITH
 RESPECT TO REPEAT COMMENTS FOR MINIMUM CODE COMPLIANCE.
 THE RESPONSE LETTER MENTIONS TO BE HANDLED BY THE
 OWNER/CONTRACTOR. THIS IS THE SOLE RESPONSIBILITY OF
 THE DESIGNER AND NOT AN OWNER OR CONTRACTOR. THE
 FLORIDA STATUTE AND FINE GIVEN WAS TO THE DESIGNER AS
 REQUIRED UNDER THE STATUTE GIVEN AND IS NOT THAT FOR
 ANY OTHER INDIVIDUAL.
 IT IS IMPERATIVE THAT THE MINIMUM CODE COMPLIANCE
 COMMENTS ARE ADDRESSED FOR REVIEWS.
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR SCOPE OF WORK
 IS LOW. THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST ETC. FBC 108.3
 THIS INCLUDES ALL ELECTRICAL, LIGHTING FIXTURES,
 SERVICE EQUIPMENT ETC EVEN IF ANY OF THE ABOVE ITEMS
 ARE OWNER SUPPLIED.
  
 4) NOTE: PLEASE SEE THE ELECTRICAL SERVICE DOES NOT
 MATCH WITH ANY PLANS FOR BASE BUILDING IN PART OF THE
 FACT THAT NO PLANS HAVE BEEN SUBMITTED.
 PLEASE ALSO SEE THE SHEET E-7 SHOWS AN MSB PANEL WHICH
 SHOWS EACH TENANT BAY BEING FED FROM THIS MSB YET THE
 SAME SHEET SHOWS THIS TENANT FED FROM GUTTER AND ALSO
 FROM A SEPARATE RISER.
 PLEASE CORRELATE ALL SERVICE EQUIPMENT ONCE PLANS FOR
 BASE BUILDING ARE COMPLETED.
 230.70,230.71,230.72, 230.76, 230.79 ETC
  
 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT MEET THE MINIMUM REQUIREMENTS OF CHAPTER 13.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE METHOD *A*
 WHICH IS FOR WHOLE BUILDING. HOW IS THIS POSSIBLE WHEN
 THIS IS FOR A TENANT BUILD OUT?
 PLEASE SEE THE CALCULATIONS SUBMITTED IS NOT THE LATEST
 VERSION ADOPTED BY THE FBC 2004W /2007 SUPPLEMENTS. THE
 LATEST VERSION SHALL BE 2.5. (2.11 SUBMITTED)
 PLEASE SEE BLUE SHEETS UNDER THE ADOPTED CHANGES DATED
 DECEMBER 8TH, 2006.
 PLEASE SEE THE INPUT DATA REPORT WHICH WILL BE NOTED AS
 THE IDR ON HERE OUT DOES NOT CORRELATE WITH THE PLANS.
 FOR EXAMPLE:
 SEE ADDRESS ON CALCULATIONS SHOWS 2015 OKEECHOBEE BLVD
 WHEN APPLIED LOCATION IS 2015 OKEECHOBEE BLVD.
 THE INTERIOR LIGHTING CONTROLS FOR ALL AREAS ARE NOTED
 AS *MANUAL ON/OFF*. HOW IS THIS POSSIBLE WHEN THE
 LIGHTING IS AUTOMATICALLY CONTROLLED?
 THE EXTERIOR LIGHTING ON THE IDR SHOWS ABSOLUTELY NOT
 FIXTURES FOR EXTERIOR OF BUILDING. HOW IS THIS POSSIBLE
 WHEN THE PLANS CLEARLY SHOW LIGHTS?
 PLEASE SEE THE INTERIOR LIGHTING FIXTURES FOR ALL
 NUMBERS OF FIXTURES, TYPE OF FIXTURES AND WATTAGES NEED
 TO CORRELATE.
 13-400.3, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3
  
 6) NOTE: PLEASE SUBMIT COMPLETED INFORMATION FOR THE
 REQUIRED AND PROPOSED LIGHTING CONTROL SYSTEM PER
 13-415.1.ABC.1.1, .1.2 ,.1.3 AND .1.4.
 RESPONSE MENTIONS THERE WILL BE A PANEL AND SOME
 DEVICES ARE SHOWN AND NOTED ON PLANS, HOWEVER NOT ALL
 INFORMATION AS REQUESTED ON THE PREVIOUS THREE REVIEWS
 UNDER EXPIRED PERMIT WAS SUBMITTED.
 SHOW COMPLETE SYSTEM
 SHOW ALL OVER RIDE LOCATIONS.
 SHOW ZONES,
 SHOW ALL LOCATIONS FOR SEPARATE CONTROLS. THERE ARE
 STILL LOCATIONS ON PLANS IN WHICH NO SEPARATE SPACE
 CONTROLS ARE PROVIDED. (WOULD GIVE ROOM OR AREA
 LOCATIONS HOWEVER E-5 DOES NOT SHOW ANY DESIGNATIONS.)
 SHOW SCHEDULING.
 ETC.
 THE RESPONSE MENTIONS THE SYSTEM WILL MEET THE FBC
 HOWEVER MAY NOT QUOTE CODE IN LIEU OF SHOWING MINIMUM
 DETAILS.
 WHERE ARE CONTROLS FOR OUTSIDE LIGHTING MEETING SECTION
 NOTED ABOVE? TIME CLOCK? BATTERY BACK UP FOR TIME
 CLOCK?(MIN 10HRS)OR WILL ALL BE PHOTO-SENSOR?
  
 7) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN NOTES FOR
 CONSTRUCTION DOCUMENTS AS STATED IN 13-413.1.ABC.2.1,
 .2.2.
 PLEASE PLACE REQUIRED NOTES ON PLANS.
  
 8) NOTE: PLEASE INCLUDE AND SHOW ALL ROOM AND AREA
 DESIGNATIONS ON PLANS.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE PANEL P1 IS STILL BEING SHOWN ON
 RISER WITH A 150MCB AND ON PANEL SCHEDULE AS 100 MCB.
 THIS WAS NOTED ON PREVIOUS REVIEWS
  
 10) NOTE: PLEASE BE SURE TO LIST THE FOLLOWING CODES ON
 ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA- 70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED AND INCLUDED ON PLANS THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE
 MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2008-03-06 17:56:482008-03-06 17:56:48
  
 IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-10 Cont ID  
Sent By mawillia Date 2008-12-10 Time 13:12 Rev Time 0.00
Received By mawillia Date 2008-12-10 Time 12:37 Sent To  
Notes
2008-12-10 13:12:54*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A0.2, A1, A4, A10, AND FS-1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-02 Cont ID  
Sent By mwennerg Date 2008-07-02 Time 10:59 Rev Time 0.00
Received By mwennerg Date 2008-07-02 Time 10:59 Sent To  
Notes
2008-07-02 11:00:09STAMPED FS-1 AND FS-2 SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-04 Cont ID  
Sent By mwennerg Date 2008-06-04 Time 14:39 Rev Time 0.00
Received By mwennerg Date 2008-06-04 Time 14:39 Sent To  
Notes
2008-06-04 14:40:40PLANS STAMPED SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By mawillia Date 2008-03-24 Time 15:45 Rev Time 0.00
Received By mawillia Date 2008-03-24 Time 14:27 Sent To  
Notes
2008-03-24 15:44:54*****UNSAT*****
  
  
 1.STAPLES IS LISTED AS BAY 2;SINCE THERE ARE NO
 OTHER BAYS FOR 2029 OKEECHOBEE BOULEVARD, ELIMINATE
 REFERENCE TO BAY 2 ON DRAWINGS A0.1 THRU A10.THE USE
 OF SUITES/TENANTS/BAYS SHOULD ONLY BE USED WHEN THERE
 ARE MORE THAN ONE UNIT WITH THE SAME NUMERICAL ADDRESS.
  
  
 2.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OF CLASS II.
  
 3.CODE ANALYSIS, ON DRAWING A0.1, STATES THAT THIS
 CLASS B MERCANTILE OCCUPANCY WILL HAVE A FULL FIRE
 ALARM SYSTEM. PROVIDE A LAYOUT OF THE FIRE ALARM
 DEVICES AT THIS SITE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 14:14 Sent To  
Notes
2008-11-25 11:05:3611/25/08--PLANS WERE ON HOLD. REVIEWS STARTED BACK UP
 TODAY.
2008-11-14 14:15:00TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 15:54 Sent To  
Notes
2008-10-21 10:09:28TO "COMM" BD#7
2008-10-17 15:54:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 16:13 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 16:13 Sent To  
Notes
2008-06-10 16:19:32TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 11:21 Sent To  
Notes
2008-05-12 11:21:56TO "COMM" BD#32--PLANS ON RACK/LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-09 Cont ID  
Sent By shill Date 2008-04-09 Time 11:48 Rev Time 0.00
Received By shill Date 2008-02-20 Time 09:19 Sent To  
Notes
2008-02-20 09:19:57TO "COMM" BD#62

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 10:52 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 10:49 Sent To  
Notes
2008-12-06 10:49:46REVISED AC-1 AND AC-2 PREVIOUSLY PASSED BY TG ON
 10/24/08 FILED WITH PERMIT SET.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-10-24 Cont ID  
Sent By tgordon Date 2008-10-24 Time 12:00 Rev Time 1.00
Received By tgordon Date 2008-10-24 Time 12:00 Sent To  
Notes
2008-10-24 12:01:45REVISION TO PLAN AC-1 AND AC-2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By tgordon Date 2008-06-11 Time 09:05 Rev Time 1.00
Received By tgordon Date 2008-06-11 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-27 Cont ID  
Sent By tgordon Date 2008-05-27 Time 08:48 Rev Time 1.20
Received By tgordon Date 2008-05-27 Time 08:48 Sent To  
Notes
2008-05-27 08:49:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By tgordon Date 2008-03-05 Time 14:31 Rev Time 1.30
Received By tgordon Date 2008-03-05 Time 14:31 Sent To  
Notes
2008-03-05 14:45:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS SUBMITTED ARE THE WRONG VERSION,
 THEY NEED TO BE THE 2.5 VERSION, PER 2004 FBC
 13-400.3.A. AN ACCURATELY COMPLETED FORM 400A-04R
 (GENERATED BY THE FLA/COM-2004 COMPUTER PROGRAM,
 VERSION 2.5) DEMONSTRATING THAT CODE COMPLIANCE HAS
 BEEN ACHIEVED SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL FOR METHOD A COMPLIANCE. CALCULATIONS SHALL BE
 PERFORMED FOR THE CLIMATE ZONE IN WHICH THE BUILDING
 WILL BE LOCATED AND ACCORDING TO THE PROCEDURES
 SPECIFIED FOR METHOD A IN THIS SUB-CHAPTER
  
 2)A/C SYSTEM LISTED ON A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT THE MODEL NUMBERS OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1.
  
 3)A/C SYSTEM #5 RTU-5 LISTED ON A/C EQUIPMENT
 SCHEDULE SHOWS 10 SEER PER 2004 FBC ENERGY EFFICIENCY
 CHAPTER 13 TABLE 13-407.1.ABC.3.2A THE MINIMUM SEER FOR
 THIS SIZE SYSTEM IS 13, PLEASE CORRECT.
  
 4) UNITS RTU1 TO 4 REQUIRE SMOKE DETECTORS, PER 2004
 FBC/M 606.2.1. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-12-11 Cont ID  
Sent By kstevens Date 2008-12-11 Time 10:58 Rev Time  
Received By kstevens Date 2008-11-03 Time 16:04 Sent To  
Notes
2008-12-11 11:16:01REVISIONS OK -- SHTS P-1 & P-2 APPROVED 11-3-08 BUT
 WAITING FOR REVISION FEES TO BE PAID PRIOR TO PASSING
 IN COMPUTER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-26 Cont ID  
Sent By mperson Date 2008-06-26 Time 08:16 Rev Time 0.00
Received By mperson Date 2008-06-26 Time 08:16 Sent To  
Notes
2008-06-26 08:16:47****************PROVISO****************
 A} SHEET P-2 WATER RISER DIAGRAM: A SHUT OFF VALVE IS
 REQUIRED FOR EACH SILLCOCK (HOSE BIBB). PER FBC-2004
 PLUMBING SECTION 606.2(2). (REVISION REQUIRED)
  
 B} SHEET P-2 ELECTRIC WATER HEATER DETAIL: THE RELIEF
 VALVE DISCHARGE SHALL BE PER FBC-2004 PLUMBING SECTION
 504.6.1 AND THE WATER HEATER PAN DRAIN TERMINATION
 SHALL BE PER FBC-2004 PLUMBING SECTION 504.7.2.
 (REVISION REQUIRED)
  
 C} SHEET P-2 WATER RISER DIAGRAM: AIR CHAMBERS ARE NOT
 APPROVED, WATER-HAMMER ARRESTORS AS PER FBC- PLUMBING
 SECTION 604.9 ARE APPROVED AS NOTED ON BOTTOM OF SHEET
 P-2. (REVISION REQUIRED)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: MPERSON@WPB.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-05 Cont ID  
Sent By mperson Date 2008-06-05 Time 13:53 Rev Time 0.00
Received By mperson Date 2008-06-05 Time 13:53 Sent To PC
Notes
2008-06-05 13:59:51****************PROVISO****************
 A} A SHUT OFF VALVE IS REQUIRED FOR EACH SILLCOCK
 (HOSE BIBB). PER FBC-2004 PLUMBING SECTION 606.2(2).
  
 B} THE RELIEF VALVE DISCHARGE SHALL BE PER FBC-2004
 PLUMBING SECTION 504.6.1 AND THE WATER HEATER PAN DRAIN
 TERMINATION SHALL BE PER FBC-2004 PLUMBING SECTION
 504.7.2.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By mperson Date 2008-03-20 Time 08:50 Rev Time 0.00
Received By mperson Date 2008-03-20 Time 08:50 Sent To  
Notes
2008-03-20 11:07:23PLUMBING PLAN REVIEW:
 DENIED
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A0.1 CODE ANALYSIS IS INDICATING THE WRONG
 CODE CYCLE AS FBC-2004 W/06 REVISIONS. THE REVISIONS
 SHOULD BE 2007.
  
 2. SHEET A7 DETAIL 2, CLEARLY INDICATE THE REQUIRED
 CLEAR FLOOR SPACE FOR THE LAVATORIES (30" X 48" AND
 MAXIMUM 19" UNDER LAV.) IN THE MENS AND WOMENS HANDICAP
 STALLS. PER FBC CHAPTER 11, SECTION 11-4.19.3. NOTE:
 THE DOOR SWING CAN NOT BE IN THE CLEAR FLOOR SPACE. PER
 FBC CHAPTER 11, SECTION 11-4.22.2.
  
 3. SHEET A7 DETAIL 8, THE URINAL ELEVATION FOR THE
 MAXIMUM DISTANCE FOR THE URINAL RIM FROM FINNISH FLOOR
 IS BEING INDICATED WRONG AS 1'-7". THE CORRECT DISTANCE
 SHOULD BE 17". PER FBC CHAPTER 11, SECTION 11-4.18.2.
  
 4. SHEET P-1, STAPLES INDICATES EXISTING 6" AND 8" RD
 (ROOF DRAINS), HOWEVER PREVIOUS PERMIT INFORMATION
 INDICATES THE EXISTING BUILDING BEING DEMOLISHED. NOTE:
 PERMIT #07070444 PERMIT APPLICATION WHICH IS A
 FOUNDATION AND SHELL PERMIT FOR THIS "STAPLES" ALSO DID
 NOT INDICATE THE 6" AND 8" RD (ROOF DRAINS). PLEASE
 CORRELATE THE RESUBMITTED PLANS TO REFLECT WHAT IS
 ACTUALLY BEING BUILT. PER W.P.B. SECTION 106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHEET P-1, STAPLES INDICATES EXISTING 4" AND 3"
 SANITARY LINES IN A BUILDING THAT HAS BEEN DEMOED.
 HOWEVER THESE SANITARY LINES WERE ADDED ON A REVISION
 ON PERMIT #07070444 WHICH WAS SUBMITTED 3/13/08 WHICH
 IS AFTER THE SUBMITTED DATE (2/19/08) OF THIS INTERIOR
 BUILDOUT. PLEASE CORRELATE THE RESUBMITTED PLANS TO
 REFLECT WHAT IS ACTUALLY BEING BUILT AND TO WHICH
 PERMIT NUMBER THE EXISTING WORK WAS BUILT TO AVOID TIME
 CONSUMING PLAN REVIEW RESEARCH. PER W.P.B., SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. SHEET P-1, RTU CONDENSATE DRAIN LINES ARE BEING
 INDICATED AS DRAINING INTO EXISTING ROOF DRAINS (WHICH
 WERE DEMOED, SEE COMMENT #4). PER FBC PLUMBING SECTION
 314.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL
 COOLING COILS SHALL BE CONVEYED FROM THE DRAIN PAN TO
 AN APPROVED PLACE OF DISPOSAL. ROOF DRAINS ARE NOT AN
 APPROVED METHOD OF DISPOSAL. PLEASE INDICATE CONDENSATE
 DISPOSAL INTO A DRY WELL, CATCH BASIN, OR PLANTED AREA.
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-03-13 Cont ID  
Sent By kdfreema Date 2008-03-13 Time 14:08 Rev Time 0.00
Received By kdfreema Date 2008-03-13 Time 14:08 Sent To  
Notes
2008-03-13 14:09:04INTERIOR BUILDOUT ONLY.