Plan Review Details - Permit 08020369
Plan Review Stops For Permit 08020369
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-14 Cont ID  
Sent By amorse Date 2008-04-14 Time 16:40 Rev Time 0.00
Received By amorse Date 2008-04-14 Time 16:40 Sent To Z
Notes
2008-04-14 16:51:03 
  
 DENIED
  
 1)SCOPE OF WORK HAS CHANGED AND A STRUCTURE IS NOW
 BEING BUILT AS SUCH THE REVISION WILL REQUIRE ZONING
 APPROVAL
  
 2)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 &
 2007AMENDMENTS PER 106.1.1 FBC*
  
 3)DRAWINGS SHALL SHOW THE LOCATION OF ALL
 WORK, INCLUDING THE PROPOSED BUILDING(S) OR
 STRUCTURE(S), AND ALL EXISTING MAN-MADE IMPROVEMENTS
 AND EVERY EXISTING SURVEY, OR OTHER SPECIAL SURVEY,
 PREPARED BY A QUALIFIED
 SURVEYOR. PER 106.3.4 FBC*
  
 4)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 5)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION,NATURE, AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC*
  
 6)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC
  
 7)PER R301 FBC RES.THE FOLLOWING DESIGN CRITERIA IS
 REQUIRED ON THE CONSTRUCTION DOCUMENTS SUBMITTED FOR
 PERMIT, BUILDINGS AND STRUCTURES, AND ALL PARTS
 THEREOF, SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL
 LOADS, INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS,
 FLOOD LOADS AND WIND LOADS AS PRESCRIBED BY THIS CODE.
 THE CONSTRUCTION OF BUILDINGS AND STRUCTURES SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 CAPABLE OF TRANSFERRING ALL LOADS FROM THEIR POINT OF
 ORIGIN THROUGH THE LOAD-RESISTING ELEMENTS TO THE
 FOUNDATION
  
 8)CONSTRUCTION DOCUMENTS SHALL SHOW THE SIZE, SECTION
 AND RELATIVE LOCATIONS OF STRUCTURAL MEMBERS WITH FLOOR
 LEVELS, COLUMN CENTERS AND OFFSETS FULLY DIMENSIONED.
 THE DESIGN LOADS AND OTHER INFORMATION PERTINENT TO THE
 STRUCTURAL DESIGN REQUIRED BY SECTIONS 1603.1.1 THROUGH
 1603.1.8 SHALL BE CLEARLY INDICATED ON THE CONSTRUCTION
 DOCUMENTS FOR PARTS OF THE BUILDING OR STRUCTURE, PER
 1603.1 FBC.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-15 Cont ID  
Sent By amorse Date 2008-03-15 Time 11:26 Rev Time 0.00
Received By amorse Date 2008-03-15 Time 11:26 Sent To PC
Notes
2008-03-15 11:28:07 
  
 PASSED REVISION TO ADD STEPS AND HANDRAIL TO RAMP AND
 LANDING

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-01 Cont ID  
Sent By amorse Date 2008-03-01 Time 10:05 Rev Time 0.00
Received By amorse Date 2008-03-01 Time 10:05 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By amorse Date 2008-02-21 Time 15:23 Rev Time 0.00
Received By amorse Date 2008-02-21 Time 15:23 Sent To PC
Notes
2008-02-21 15:36:49 
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF WORK SHALL
 BE THE TOTAL REPLACEMENT COST EXCLUDING LAND VALUE,
 THIS INCLUDES MATERIALS,LABOR, PERMIT FEES, ETC. OUR
 VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES PER 108.3 FBC*
  
 2)RESIDENTIAL RAMPS SHALL COMPLY WITH SECTION R311.6
 FBC RES., THE HANDRAIL REQUIREMENTS OF R311.5.6.3 FBC
 RES. AND GUARDSSECTION R312 FBC RES.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 11:39 Sent To B
Notes
2008-04-07 11:39:46TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 08:57 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 08:57 Sent To Z
Notes
2008-03-10 08:57:29TO"Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 08:51 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 08:51 Sent To Z
Notes
2008-02-28 08:51:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-02-21 Time   Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 08:25 Sent To  
Notes
2008-02-19 08:27:12TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status F Date 2008-04-17 Cont ID  
Sent By choops Date 2008-04-17 Time 08:23 Rev Time 0.00
Received By choops Date 2008-04-17 Time 08:23 Sent To  
Notes
2008-04-17 08:24:48***FAILED - REVISION - REMOVING RAMP, REPLACING WITH
 STAIRCASE AND OVERHANG***
  
  
 1)CLARIFY SCOPE OF WORK, ORIGINAL PERMIT WAS TO
 INSTALL HANDICAP RAMP...REVISION SHEET INDICATES
 REMOVAL OF RAMP AND INSTALLATION OF STAIRCASE/OVERHANG.
 IF NO RAMP IS PROVIDED FOR ADA ACCESS, THE HEIGHT OF
 THE RAILING (INCLUDING THE PLATFORM) SHALL NOT EXCEED 4
 FEET IN HEIGHT.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-302(B)(1):
 MAXIMUM HEIGHT.IN RESIDENTIAL DISTRICTS, FENCES OR
 WALLS SHALL NOT BE IN EXCESS OF 48 INCHES IN HEIGHT
 WITHIN THE REQUIRED FRONT SETBACK.
  
 2)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE PROPOSED IMPROVEMENTS WITH DIMENSIONS AND SETBACK
 DIMENSIONS TO ALL PROPERTY LINES.
  
 NOTE:ANY NEW CONSTRUCTION OF A STRUCTURE SHALL MEET
 CURRENT SETBACK REQUIREMENTS.
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDINGS.
 FRONT: 25 FEET;
 REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
 SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By choops Date 2008-03-11 Time 09:50 Rev Time 0.00
Received By choops Date 2008-03-11 Time 09:50 Sent To B
Notes
2008-03-11 09:51:29***APPROVED - REVISION - ADDING STEPS TO RAMP, COSMETIC
 VARIATION TO RAILING.***
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 11:18 Rev Time 0.00
Received By choops Date 2008-02-28 Time 11:18 Sent To B
Notes
2008-02-28 11:19:36***APPROVED - RESUB #1***
  
 RAILING EXCEEDS 4 FOOT MAXIMUM, OK PER ADA
 REQUIREMENTS.
  
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 11:21 Rev Time 0.00
Received By choops Date 2008-02-19 Time 11:21 Sent To B
Notes
2008-02-19 11:29:30***FAILED***
  
  
 1)INDICATE HEIGHT OF RAMP AND LANDING, MEASURED FROM
 GRADE.PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS, SECTION 94-305(B)(7):
 STEPS AND PORCHES.STEPS, OPEN UNCOVERED PORCHES OR
 STOOPS, AND OPEN TERRACES WHICH ARE THREE FEET OR LESS
 ABOVE GRADE MAY ENCROACH INTO ANY REQUIRED SETBACK AREA
 TO A POINT NOT CLOSER THAN TWO FEET TO THE PROPERTY
 LINE. ANY GRADE DIFFERENTIAL BETWEEN THE ENCROACHING
 STEP, PORCH, STOOP, OR TERRACE AND ADJACENT PROPERTY
 SHALL BE STRUCTURALLY RETAINED AND POSITIVELY DRAINED
 IN A MANNER THAT WILL PREVENT ANY DRAINAGE DISCHARGE TO
 ANY PROPERTY CONTIGUOUS TO THE SIDE OR REAR PROPERTY
 LINES.
  
 2)INDICATE HEIGHT OF RAILING, MEASURED FROM GRADE.
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-302(B)(1): MAXIMUM
 HEIGHT.IN RESIDENTIAL DISTRICTS, FENCES OR WALLS
 SHALL NOT BE IN EXCESS OF 48 INCHES IN HEIGHT WITHIN
 THE REQUIRED FRONT SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "B" - MISC. 2