| 2008-02-15 14:59:43 | RESIDENTIAL SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE THE FOLLOWING INFORMATION IN THE SHUTTERS |
| | INSTALLATION SCHEDULE AND REVISE INFORMATION AS |
| | REQUIRED.(SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO |
| | VERIFY COMPLIANCE WITH SEC. R301.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND COMPLIANCE WITH THE PRODUCT |
| | APPROVAL SUBMITTED): |
| | A) SPECIFY SHUTTER MOUNTING CONDITIONS. EG: WALL |
| | MOUNTED, BUILD-OUT MOUNTED, ETC.NO INFORMATION WAS |
| | SUBMITTED. AND,MARK/CIRCLE SPECIFIC MOUNTING |
| | CONDITIONS ON NOA 06-0823.06. |
| | |
| | B) SHUTTER GLASS SEPARATION(2 1/2",2" AND 3") |
| | SPECIFIED ONINSTALLATION SCHEDULE DON'T COMPLY WITH |
| | TABLE 2 SHOWN ON SHEET 4 OF 4 OF NOA SUBMITTED. REVISE |
| | AS REQUIRED. |
| | |
| | C) SPECIFY SHUTTER SPAN. NO INFORMATION WAS |
| | SUBMITTED. |
| | NOTE: THIS INFORMATION NEEDS TO BE COORDINATEDWITH |
| | COLUMN FOR OPENING SIZE, COLUMN FOR SHUTTER |
| | INSTALLATION (VERTICAL OR HORIZONTAL)AND COLUMN FOR |
| | MINIMUM EDGE DISTANCE. |
| | |
| | D) SPECIFY ANCHOR TYPE (SEE NOTE 1 ON INSTALLATION |
| | SCHEDULE FOOTNOTE). NO INFORMATION WAS PROVIDED.AND, |
| | MARK/CIRCLE ON PRODUCT APPROVAL SPECIFIC ANCHOR. |
| | |
| | E) SPECIFY MINIMUM EDGE DISTANCE. NO INFORMATION WAS |
| | SUBMITTED. |
| | NOTE: THIS INFORMATION NEEDS TO BE COORDINATED WITH |
| | SUBSTRATE COLUMN (CONCRETE, CONCRETE BLOCK OR WOOD |
| | FRAME). |
| | |
| | F)SPECIFY SUBSTRATE STRUCTURE TO BE ATTACHED TO ( |
| | CONCRETE BLOCK, CONCRETE OR WOOD FRAMED). NO |
| | INFORMATION WAS SUBMITTED. |
| | NOTE:TOP OF FORM INDICATESWOOD FRAME AND CONCRETE |
| | CONSTRUCTION.NEED TO INDICATE SPECIFIC SUBSTRATE FOR |
| | EACH OPENING TO VERIFY COMPLIANCE WITH PROPOSED ANCHOR |
| | TYPE AND SPACING. |
| | |
| | 2- PROVIDE 2 COPIES OF EVERYTHING, INCLUDING |
| | INSTALLATION SCHEDULES AND KEY PLANS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |