| 2008-02-15 12:26:12 | *** DENIEDREVIEW*** |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| | RELEVANT CODES. |
| | PLEASE SEE CODE STATED ON PLANS FOR 2006 NFPA-101 AND |
| | 2007 NFPA-72IS NOT YET ADOPTED BY THE STATE. |
| | PLANS SHOULD REFLECT. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | FBC 106.1.2, 106.3.5.1.2, 106.5 |
| | FS 553.73 |
| | FBC CHAPTER 35 FOR REFERENCE STANDARDS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE NOT SIGNED WITH SIGNATURE |
| | AS ON FILE WITH THE CITY OF WEST PALM BEACH. |
| | PLEASE ADJUST AS PER FS 471.025/ FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE SUBMITTED PERMIT APPLICATION IS FOR |
| | WORK IN SUITE #802 YET THE PLANS SHOWS A NEW |
| | DISCONNECT, TRANSFORMER AND PANEL FOR A SUITE #803. |
| | PLEASE CLARIFY WHERE THE SCOPE OF WORK IS BEING DONE |
| | AND COORDINATE PLANS. |
| | FBC 106.1.2 COORDINATION |
| | |
| | 4) NOTE: PLEASE SEE THAT THE CIRCUITING ON PANEL |
| | SCHEDULES FOR NEW ARE TO BE SPECIFIC TO ROOMS AND AREAS |
| | IN WHICH THE FEED. |
| | FOR EXAMPLE> OFFICE RECEPTS 102, ETC |
| | 408.4, FBC 106.1.2, 106.5 |
| | |
| | 5) NOTE: PLEASE CLARIFY NEW OR EXISTING LIGHTING |
| | CONTROLS BEING INSTALLED. PLEAS KNOW IF ANY OF THESE |
| | ARE NEW THEY ARE REQUIRED TO MEET FBC 13-415.1.ABC.1.1, |
| | .1.2, .1.3. |
| | FBC 13-101. PLEASE KNOW AT THIS TIME DETERMINATION OF |
| | ACTUAL SCOPE IS NOT CLEAR. |
| | |
| | 6) NOTE:PLEASE BE SURE TO INCLUDE EAST TOWER ON |
| | PLANS. ON ANY SHEETS WHICH DO NOT NEED TO RE-PRINTED |
| | THIS CAN BE ADDED BY HAND. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |