Plan Review Details - Permit 08020254
Plan Review Stops For Permit 08020254
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 15:24 Rev Time 0.00
Received By shill Date 2008-05-08 Time 15:24 Sent To  
Notes
2008-05-08 15:27:54IMPACT FEES PAID; 0810781, PLANS/RECEIPT FILED WITH
 08010506 ALSO

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-06 Cont ID  
Sent By shill Date 2008-05-06 Time 15:56 Rev Time 0.00
Received By shill Date 2008-05-06 Time 15:56 Sent To  
Notes
2008-05-06 16:05:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. AS DISCUSSED, THE STOREFRONT GLASS RENOVATION
 PORTION OF THIS PROJECT WAS PERMITTED SEPARATELY UNDER
 PERMIT 08010506.IMPACT FEES MAY BE DUE TO PALM BEACH
 COUNTY.THE FLOOR PLAN IS TO BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 17:21 Rev Time 0.00
Received By shill Date 2008-04-02 Time 15:56 Sent To  
Notes
2008-04-02 17:22:01STAMPED SHEETS A201, 202, 701, 801
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By jwitmer Date 2008-02-12 Time 21:37 Rev Time 2.22
Received By jwitmer Date 2008-02-12 Time 21:36 Sent To  
Notes
2008-02-12 22:35:56BUILDING PLAN REVIEW
 PERMIT: 08020254
 ADD: 700 S ROSEMARY # 118
 CONT: SOUTHEAST CONTRACTING
 TEL: (561)640-7422
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE THE
 CODE ANALYSIS.
  
 2) NOTE THIS PACKAGE WAS SUBMITTED UNDER PRIVATE
 PROVIDER WHICH ALSO INCLUDES NOTICE TO THE BUILDING
 OFFICIAL FOR PRIVATE PROVIDER INSPECTIONS AS WELL AS
 PLAN REVIEW. NOTE THERE HAS BEEN DOCUMENTATION AS TO
 THE QUALIFICATIONS AND LICENSURE OF THE INSPECTOR.
 PLEASE PROVIDE WHEN THE PACKAGE IS RESUBMITTED. FL S S
 553.791.
  
 3) THE COVER SHEET INDICATES THIS TO BE A TWO STORY
 BUILDING. SHEETA.201 INDICATES THIS IS A TYPE II NOT
 LISTING A OR B TYPE, PLEASE TAKE NOTE THAT THE (5)
 STORY PARKINGGARAGE AND ?B? BLOCK RETAIL ARE
 CONSIDERED ?ONE? BUILDING, MAKING THISA 5 STORY
 BUILDING. IN CONSIDERING THE MOST RESTRICTIVE OCCUPANCY
 IN THIS BUILDING, ?A3?THE MINIMUM BUILDING TYPE WOULD
 BE A TYPE I-B, PLEASE CORRECT ANALYSIS.
  
 4) THE PERMIT APPLICATION INDICATES THE GROSS SQUARE FT
 AREA TO BE 1635 SQ FT, THE PLANS INDICATE THE NET AS
 1513 SQ FT. TABLE 1004.1.2 FOR MERCANTILE TAKES THE
 GROSS SQ FOOTAGE WHICH WOULD BE AN OCCUPANT LOAD OF 55
 CREATING AN?A-2? ASSEMBLY. PLEASE CORRECT THE CODE
 ANALYSIS AS WELL AS OCCUPANCY DATA..
  
 5) WITH THE ABOVE A-2 ASSEMBLY OCCUPANCYPLEASE SEE
 TABLE 302.3.2FOR THE REQUIRED SEPARATION BETWEEN
 OCCUPANCY GROUPS, PLEASE PROVIDE WHAT TYPE OF OCCUPANCY
 IS LOCATED ON EACH SIDE OF THIS TENANT. IF OTHER THAN
 ANOTHER A-2 OCCUPANCY PLEASE PROVIDE THE OCCUPANCIES
 AND REQUIRED HR RATING OF THE OCCUPANCY SEPARATION
 WALL.
  
 6)SHEET A.201 INDICATES A RAISED PLATFORM BUT THERE
 IS NO MENTION AS WHAT TYPE OF MATERIAL THE PLATFORM
 SHALL BE CONSTRUCTED FROM?PLEASE SEE 410.4. PLATFORM
 CONSTRUCTION.
 NOR THE FLOOR LOADING?
  
 7) THE PLANS ALSO DO NOT PROVIDE A NUMBERING SCHEDULE
 FOR THE DOORS NOR IS THERE ANY SIZE PROVIDED TO SEE IF
 THE DOORS COMPLY WITH 1008.1.1 AND11-4.13.5. PLEASE
 PROVIDE SO CODE COMPLIANCE CAN BE DETERMINED .
  
 8) PLANS DO NOT INDICATE IF THIS IS A CHANGE OF
 OCCUPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION.
 106.1.2. IF THIS IS A CHANGE OF OCCUPANCY CHAPTER 8 OF
 THE FLORIDA EXISTING BUILDING CODEWOULD NEED TO BE
 REVIEWED FOR ADDITIONAL REQUIREMENTS AND IF GOING INTO
 A MORE STRINGENT OCCUPANCY CLASSIFICATION.
  
 9) POSSIBLY IF A CHANGE OF OCCUPANCY PLANS WILL NEED TO
 GO TO PALM BEACH COUNTY FOR
 REVIEW FOR IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-10-20 Cont ID  
Sent By dpalmer Date 2008-10-20 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2008-10-20 Time 11:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-08-11 Cont ID  
Sent By dpalmer Date 2008-08-11 Time 08:38 Rev Time 0.00
Received By dpalmer Date 2008-08-11 Time 08:38 Sent To PC
Notes
2008-08-11 08:38:31 
 **DENIED REVISION**
  
 1) NOTE: PLEASE SEE SECTIONS 13-415.1.ABC.1.1, .1.2,
 .1.3. THESE SECTIONS ARE STATED AND QUOTED ON PLANS
 HOWEVER THE REVISED PLANS NOW SHOW A LIGHTING CONTROL
 PANEL WITH RELAYS HOWEVER NO OVER RIDES AT LOCATIONS
 REQUIRED BY THE CODE IS SHOWN.
 PLEASE INDICATE THE OVER RIDES.
 PLEASE INDICATE THE LOCATIONS AS THE OCCUPANT MUST BE
 ABLE TO SEE ALL LIGHTING WHICH IS BEING CONTROLLED OR
 MEET THE EXCEPTION IN THE CODE.
 PLEASE SHOW THE LOCATIONS OF THE OVER RIDE WHERE THE
 OCCUPANT ENTERS A SPACE.
 QUOTING THE SECTIONS OF THE CODE IN LIEU OF SHOWING
 MINIMUM CODE COMPLIANCE IS NOT PERMITTED.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-09 Cont ID  
Sent By btrobaug Date 2008-05-09 Time 15:16 Rev Time 0.00
Received By btrobaug Date 2008-05-09 Time 15:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 16:51 Sent To  
Notes
2008-05-04 16:52:29** DENIED 3RD AUDIT **
  
  
 1) NOTE: PLEASE SEE THE DATES ON THE PRIVATE PROVIDER
 AFFIDAVITS DO NOT COORDINATE WITH THE SIGNED DATED AND
 SEALED PLANS.
 PLEASE SEE THE SIGNED DATED PLANS IN EACH SET OF PLANS
 IS NOT TEH SAME. IN FACT THERE ARE DIFFERENT DATES IN
 EACH ONE.
 PLEASE SEE FOR EXAMPLE.
 E-1 ON AFFIDAVIT STATES PLANS DATED 3/16/08 YET THE E-1
 SUBMITTED IS CLEARLY DATED 4/18/08.
 E-2 ON AFFIDAVIT STATES PLANS DATED 3/5/08 YET THE E-2
 SUBMITTED IS CLEARLY DATED 1/28/08.
 E-3 ON AFFIDAVIT STATES PLANS DATED 3/20/08 YET THE E-3
 SUBMITTED IS CLEARLY DATED 4/18/08
 FS 553.791
  
 2) NOTE: PLEASE BE SURE ALL SEALS RAISED AND CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL. THE RAISED
 SEAL ON E-1 AND E-2 IS VERY FAINT AND NOT EASILY READ.
 FS471.025
 PLEASE KNOW THIS OFFICE HAS NOT RECEIVED THE SIGNATURE
 VERIFICATION LETTER FOR DESIGNER OF RECORD ON
 ELECTRICAL PLANS.
 PLEASE SEE THE TWO SETS SUBMIT *STILL* CONTAIN TWO
 DIFFERENT SIGNATURES. THE SEALS ARE NOT VISBLE
 *CLEARLY* IN BOTH SETS ON ALL SHEETS.
 AS PLANS SUBMITTED TO THIS OFFICE CONTAIN MULTIPLE
 SIGNATURES THIS IS REQUIRED. PLEASE BE SURE THE LETTER
 IS ORIGINAL, SIGNED, DATED, SEALED AND IS CORRECTLY
 NOTARIZED.
 PLEASE KNOW THE SIGNATURE VERIFICATION LETTER WILL NOT
 ACCEPTABLE WITH MULTIPLE SIGNATURES ON PLANS AND
 SHEETS. PLEASE BE SURE ALL COORDIANTE WITH LETTER TO BE
 SUBMITTED.
 FS 471.023, FS117.05
  
 3) NOTE: PLEASE SEE THERE ARE NOW ATTACHED LIGHTING
 SUBMITTALS WHICH APPEAR TO BE COPIES OF MANUFACTURES
 SPECS/CUT SHEETS FOR SOME OF THE FIXTURES. THIS IS OK,
 HOWEVER ONLY SOME OF THESE CONTAIN STAMPS FROM THE
 PRIVATE PROVIDER AND NONE ARE LISTED ON THE AFFIDAVITS.
 THE SHEETS WERE NOT REQUIRED BY THIS OFFICE AND WERE
 NOT REQUIRED ON PREVIOUS AUDIT. IF THE INTENT IS TO
 HAVE THESE DOCUMENTS PART OF THE RECORD SET OF PLANS
 AND DOCUMENTS PLEASE MAKE SURE STATEMENTS ADD THESE
 SHEETS AND CONTAIN THE STAMPS FROM THE PRIVATE
 PROVIDER. IF NOT PLEASE REMOVE.
 FS 553.791
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-27 Cont ID  
Sent By dpalmer Date 2008-03-27 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2008-03-27 Time 17:36 Sent To  
Notes
2008-03-27 17:42:01** DENIED2ND AUDIT**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LIGHTING CONTROLS FOR
 COMPLIANCE WITH FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS NOW NOTE A LIGHTING CONTROL PANEL
 HOWEVER NO DETAILS WERE PROVIDED FOR THIS PANEL.
 PLEASE SEE NO OVER RIDES AS REQUIRED WERE SHOWN.
 PLEASE SEE NO MAXIMUM TIMES WERE SHOWN ON OVER RIDES.
 PLEASE SEE LOCATIONS OF THE OVER RIDES WHICH ARE
 REQUIRED TO BE SHOWN MUST BE LOCATED SO THE OCCUPANT
 CAN SEE THE LIGHTING WHICH IS BEING CONTROLLED.
 ** THE PLANS SHOW SWITCHES HOWEVER THESE ARE ONLY SHOWN
 AS STANDARD SWITCHES PER SYMBOL LEGEND.
  
 2) NOTE: PLEASE SEE THE LIGHTING CALCULATIONS BASED ON
 THE FIXTURES SHOWN ON FIXTURE LEGEND DOES NOT MEET
 13-415.2.ABC.1.1, .1.2.
 RESPONSE LETTER IN FACT STATES THE CODE DOES NOT APPLY.
 PLEASE SEE THE CODE SECTIONS GIVEN AS THE CODE IS FOR
 ALL LIGHTING WITH IN A *BUILDING* GREATER THAN 5K SQ
 FT. THIS *BUILDING* IS GREATER THAN 5K SQ FT AND
 AUTOMATEDLIGHTING CONTROL REQUIREMENTS AS SET FORTH
 IN THE FLORIDA BUILDING CODE DOES APPLY. THIS CAN BE
 CONFIRMED BY THE DEFINITIONS IN CHAPTER 2 OF THE FBC
 AND DEFINITIONS IN CHAPTER 13 SECTION 202.
 ANY FURTHER CONFIRMATION CAN BE GIVEN BY THE FLORIDA
 BUILDING COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS.
 DEC STATEMENTS HAVE BEEN ISSUED BY THE ABOVE ON
 PREVIOUS OCCASIONS.
 PLEASE SEE THE CODE SECTIONS REFERENCED ABOVE WHICH
 REQUIRES THE MINIMUM LEVELS TO BE FIGURED FOR EACH
 FIXTURE SHALL BE BASED ON THE FIXTURE VA RATING, NOT
 THE SIZE OF THE LIGHT BULB BEING INSTALLED.
 FOR EXAMPLE:
 THE FIXTURES AS SPECIFIED ON LEGEND FOR FIXTURE *B* IS
 SHOWN AS 100 WATTS ON PLANS, YET THIS FIXTURE IS A
 300WATT FIXTURE BASED ON THE CATALOG NUMBER AND FIXTURE
 INFORMATION GIVEN PER MANUFACTURE.
 PLEASE SEE THE FIXTURE *C* IS ACTUALLY A 150W FIXTURE
 PER MANUFACTURE BASED ON PLANS AND YET THE WATTAGE
 FIGURED IS 100 WATTS ONCE AGAIN.
 THIS WAS GONE OVER IN MEETING HELD BEFORE PLANS WERE
 RE-SUBMITTED AS THE CODE REQUIRES THE WATTAGE OF
 FIXTURE.
 PLEASE VERIFY FIXTURE *A*, AS THIS DOES NOT COORDINATE
 WITH THE MANUFACTURE'S LISTED PRODUCTS. PLEASE OBTAIN
 INFORMATION ON THESE UNITS.
 PLEASE SEE THE LIGHTING CALCULATIONS STATE J-BOX FOR
 LED LIGHTS, YET NO INFORMATION WAS PLACED ON FIXTURE
 LEGEND. HOW ARE THESE FED? LOW VOLTAGE?LINE VOLTAGE?
 LISTED, FIXTURE TYPE ON LEGEND? ETC.
 AS NO INFORMATION WAS SHOWN FOR THESE FIXTURES NO
 REVIEW OF THESE CAN BE DONE.
 FBC 106.1.2, 106.3.5.1.2
 ** IMPORTANT** PLEASE BE SURE ALL OF THESE FIXTURES AS
 NOTED ABOVE CONTAIN A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL) AS ADOPTED BY OSHA
 IN THE UNITED STATES. ONLY ONE FIXTURE AS NOTED ABOVE
 WAS FOUND TO SHOW INFORMATION AS BEING LISTED BY
 UNDERWRITERS LABORATORIES. (UL). (NEC 110.3)
 PLEASE SEE 13-415.2 AND SECTION ABOVE AND SUBMIT
 MINIMUM LIGHTING PERFORMANCE CALCULATIONS.
 I HAVE ATTACHED SOME PRINT OUTS OF THE FIXTURES FROM
 THE MANUFACTURE'S ON-LINE SPECS.
  
 3) NOTE: PLEASE KNOW OF THE ELECTRICAL PLANS NOW
 SUBMITTED SHEET E-1 NOW CONTAINS A COMPLETELY DIFFERENT
 SIGNATURE FOR THE ENGINEER OF RECORD THAN THAT OF SHOWN
 ON E-2 AND E-3.
 THESE ARE ALSO DIFFERENT FROM THE FIRST SET OF
 ELECTRICAL PLANS SUBMITTED.
 PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002. PLANS MAY ONLY BE
 SIGNED BY THE ENGINEER.
 AS SIGNATURES NOW DIFFER FROM MULTIPLE SHEETS PLEASE
 SUBMIT A SIGNATURE VERIFICATION LETTER WITH LEGAL AND
 ORIGINAL SIGNATURE ALONG WITH RAISED SEAL AND DATE.
 PLEASE BE SURE LETTER IS CORRECTLY NOTARIZED PER FS
 117.05.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 ** PLEASE BE SURE RAISED SEAL ON ALL PLANS AND
 DOCUMENTS IS CLEAR AND VISIBLE WITH ALL INFORMATION ON
 RAISED SEAL. SOME OF THESE ARE VERY FAINT AND NOT
 EASILY READ.
  
 ** ONE SET OF ELECTRICAL PLANS FOR BOTH THE ORIGINAL
 AND NEW SUBMITTED SHEETS ARE BEING RETAINED BY THIS
 OFFICE FOR FURTHER POSSIBLE ACTION.
  
 4) NOTE: PLEASE PLACE MECHANICAL DETAIL AND INFORMATION
 ON THE M SHEETS. PLEASE SEE THE SWORN AFFIDAVIT FROM
 PRIVATE PROVIDER STATES CODE COMPLIANCE FOR SHEET M-1
 HAS BEEN MET, YET SOME OFTHE MECHANICAL INFORMATION
 IS ACTUALLY ON THE ELECTRICAL SHEETS. HOW IS THIS
 POSSIBLE?
 PLEASE ADJUST PLANS FOR NEW SHEETS. THEMECHANICAL
 REVIEWER HAS MADE NOTE TO THIS AND IS AWARE OF THE NEED
 FOR CHANGE.
  
 5) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME. PLEASE BE SURE TO
 ADDRESS ALL COMMENTS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By dpalmer Date 2008-02-12 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2008-02-12 Time 10:11 Sent To  
Notes
2008-02-12 10:11:54*** DENIED***
  
 1) NOTE: PLEASE KNOW AS PACKAGE WAS SUBMITTED FOR
 PRIVATE PROVIDER WHICH ALSO INCLUDED A NOTICE TO
 BUILDING OFFICIAL FOR INSPECTIONS AS WELL AS PLANS
 REVIEW NO INSPECTION QUALIFICATIONS/CERTIFICATION
 DOCUMENTS WERE LOCATED IN PACKAGE.
 PLEASE BE SURE TO SUBMIT THESE IN COMPLETE PACKAGE WHEN
 RESUBMITTING PLANS.
 FS 553.791
  
 2) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 LATEST ADOPTED CODES RELEVANT TO PROJECT AND DESIGN.
 SOME ARE ALREADY SHOWN HOWEVER PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-72
 FBC 106.1.2, 106.5, FS 553.73
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AND EXISTING TO DETERMINE NEW
 LIGHTING LEVELS BEING ADDED TO EXISTING AREAS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1..1, .1.2.
  
 4) NOTE: PLEASE INDICATE THE LIGHTING CONTROLS FOR NEW
 BEING INSTALLED PER FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THIS IS ONLY REQUIRED FOR NEW BEING
 INSTALLED MEETING THE PRESCRIPTIVE REQUIREMENTS OF THE
 CODES GIVEN.
 THIS DOES NOT REQUIRE EXISTING TO REMAIN TO BE MODIFIED
 ONLY NEW BEING INSTALLED. 13-101, 13-400.2
 PLEASE INCLUDE NOTES FOR 13-413.1.ABC.2
  
 5) NOTE: PLEASE SEE THE 75KVA TRANSFORMER SHALL NOT BE
 PERMITTED ABOVE CEILING PER 450.13B. RISER STATES TO
 REMOVE CEILING TILES WHICH IS NOT ACCEPTABLE.
 THIS CONTRADICTS SHEET E-1 WHICH STATES THERE ARE NO
 TILES OR CEILING GRID. WHICH ONE IS IT?
  
 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS ON EXISTING
 TENANT GUTTER AND MAIN SERVING GUTTER WITH EXISTING
 LOADS ALONG WITH NEW LOADS BEING ADDED.
 NEC 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE 210.8B2 WHICH REQUIRES ALL 15/20AMP
 120V RECEPTACLES IN KITCHEN/SERVING AREAS TO BE GFI/
 GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT THESE
 RECEPTACLES ARE SERVING KITCHEN/SERVING COUNTER
 SPACES.
 THE PLANS ON E-1 DO CONTAIN A NOTE WHICH STATES THEY
 ARE TO BE GFCI, HOWEVER THE NEITHER THE DEVICES OR THE
 BREAKERS INDICATE THIS REQUIRED PROTECTION.
 THE PANEL SCHEDULES DO CONTAIN AN * ASTERISK NEXT TO
 MANY OF THESE HOWEVER THE PANEL SCHEDULE DOES NOT
 PROVIDE ANY DETAIL OR SYMBOL LEGEND FOR THE SINGLE
 ASTERISK WHICH STATES THIS IS FOR GFCI TYPE BREAKER.
 THIS SAME SINGLE ASTERISK IS NOTED ON 2-POLE CIRCUITS
 ALSO?
  
 8) NOTE: PLEASE COORDINATE THE FEEDERS TO PANEL *C*
 WHETHER THEY ARE NEW OR ARE ALREADY EXISTING. PLEASE
 SEE PANEL *C* WHICH STATES ON THE BOTTOM OF PANEL THE
 FEEDERS ALREADY EXIST, HOWEVER AS PANEL *C* IS NEW,
 TRANSFORMER IS NEW AND FEEDERS ON RISER ARE NEW, HOW
 CAN THESE BE EXISTING?
 PLEASE COORDINATE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 10:00 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 10:00 Sent To  
Notes
2008-05-09 10:01:17NEW SHEET FP-1 WAS STAMPED, SIGNED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 16:24 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 16:24 Sent To  
Notes
2008-05-06 16:24:36*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED. PLAN SHEETS A-201 AND A-202 WERE
 STAMPED, INITIALED, AND DATED, HOWEVER SHEET E-1 TO BE
 FIRE-STAMPED ONCE THE OTHER PLAN REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By mawillia Date 2008-04-03 Time 15:43 Rev Time 0.00
Received By mawillia Date 2008-04-03 Time 15:13 Sent To  
Notes
2008-04-03 15:31:53*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED. PLAN SHEETS A-201 AND A-202 WERE
 STAMPED, INITIALED, AND DATED, HOWEVER SHEET E-1 TO BE
 FIRE-STAMPED ONCE THE OTHER PLAN REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-22 Cont ID  
Sent By mwennerg Date 2008-02-22 Time 11:05 Rev Time 0.00
Received By mwennerg Date 2008-02-22 Time 11:05 Sent To  
Notes
2008-02-22 11:19:07***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENT #4 WHICH HAS
 DIRECT IMPACT ON THIS REVIEW.
  
 2) COOKING THAT PRODUCES GREASE LADEN VAPOR IS
 PROHIBITED WITHOUT PROTECTION BY HOOD/SUPPRESSION
 SYSTEM.
  
 3) CLEARLY IDENTIFY THE LOCATION(S) OF REQUIRED
 EMERGENCY LIGHT FACILITIES.
  
 4) PLEASE IDENTIFY LOCATION(S) OF REQUIRED 2A-10B,C
 RATED FIRE EXTIGUISHER(S).
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 10:48 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 10:48 Sent To E
Notes
2008-10-15 10:48:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 12:28 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 12:28 Sent To E
Notes
2008-08-01 12:29:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 16:49 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 16:49 Sent To M
Notes
2008-07-11 16:49:24TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 16:10 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 16:10 Sent To M
Notes
2008-06-05 16:11:08TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 16:46 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 16:46 Sent To  
Notes
2008-04-29 16:47:27TO "COMM" BD#43**PRIVATE PROVIDER** NEW SHEETS
 SUBMITTTED--ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 10:55 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 10:55 Sent To  
Notes
2008-03-25 10:56:02TO "COMM" BD#5--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-22 Cont ID  
Sent By mwennerg Date 2008-02-22 Time 11:21 Rev Time 0.00
Received By mwennerg Date 2008-02-11 Time 16:51 Sent To  
Notes
2008-02-11 16:52:05TO "COMM" BD#14--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-07-15 Cont ID  
Sent By tgordon Date 2008-07-15 Time 10:44 Rev Time 0.45
Received By tgordon Date 2008-07-15 Time 10:44 Sent To  
Notes
2008-07-15 10:47:48REVISION, RECEIVED NOA FOR PRE-ENGINEERED A/C CONDENSER
 STAND AND ENGINEERING FOR CONDENSER UNIT TIE DOWN.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-06-06 Cont ID  
Sent By tgordon Date 2008-06-06 Time 09:55 Rev Time 0.30
Received By tgordon Date 2008-06-06 Time 09:55 Sent To  
Notes
2008-06-06 10:02:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** SUBMITTAL FOR CONDENSER STANDS **
 *** DENIED ***
 1) ALL SUBMITTALS AND REVISIONS MUST BE REVIEWED BY THE
 PRIVATE PROVIDER BEFORE COMING TO THIS OFFICE, PER FS
 553.791.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-09 Cont ID  
Sent By tgordon Date 2008-05-09 Time 08:19 Rev Time 0.30
Received By tgordon Date 2008-05-09 Time 08:19 Sent To FIRE
Notes
2008-05-09 08:29:355-9-08 PLANS SENT TO LUIS M.,TG.
2008-05-09 08:22:25** NOTICE **
 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) REMOTE ROOFTOP CONDENSER UNITS FOR GELATO AND
 PASTRY MACHINES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-05-06 Cont ID  
Sent By tgordon Date 2008-05-05 Time 08:35 Rev Time 1.00
Received By tgordon Date 2008-05-05 Time 08:35 Sent To  
Notes
2008-05-05 08:38:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ELECTRICAL PLAN E.2 STILL SHOWS ITEM #7 OVEN-STEAMER
 TO BE INSTALLED, PLEASE CORRECT.
  
 2) MECHANICAL PLAN SHOWS ALL MECHANICAL AS EXISTING,
 ELECTRICAL PLAN E.2 NOTE 1 STATES FOUR COMPRESSORS TO
 BE INSTALLED ON ROOF. THIS ALSO NEEDS TO BE STATED ON
 MECHANICAL PLAN M.1 AS IT IS NEW MECHANICAL WORK TO BE
 DONE, SEE 2004 FBC 106.1.1 AND 106.3.5.
  
 3) MECHANICAL PLAN M.1 NOTE #2 REFERENCES A NEW
 DISHWASHER EXHAUST DUCT, PLEASE SHOW ON PLAN OR REMOVE
 NOTE, SEE 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 11:07 Rev Time 0.30
Received By tgordon Date 2008-03-26 Time 11:07 Sent To  
Notes
2008-03-26 11:09:04MECHANICAL WORK TO BE DONE. INSTALL 4 CONDENSER UNITS
 ON ROOF.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By tgordon Date 2008-02-19 Time 16:04 Rev Time 0.30
Received By tgordon Date 2008-02-19 Time 16:04 Sent To  
Notes
2008-02-19 16:23:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN PAGE M-1 STATES 'NEW DISHWASHER
 EXHAUST HOOD ON TOP OF DISHWASHER'. PAGES P.201, E.2,
 FS1, FS2, AND FS3 STATE THIS APPLIANCE IS TO BE A
 OVEN-STEAMER. PLEASE CORRECT PLANS TO COINCIDE AS A
 PROPER REVIEW MAY NOT BE ACCURATE AT THIS TIME.
  
 2) PLEASE SEE 2004 FBC/M 508.1 REGARDING MAKEUP AIR,
 PLEASE ADDRESS.
  
 3) PLEASE STATE ON MECHANICAL PLAN IF THE EXISTING
 12X10 EXHAUST DUCT IS SERVING ANYTHING ELSE, SEE 2004
 FBC/M 506.4.
  
 4) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 NEW IN-LINE EXHAUST FAN, SEE 2004 W.P.B. AMEND.
 106.1.2..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-02 Cont ID  
Sent By kstevens Date 2008-05-02 Time 16:06 Rev Time 0.00
Received By kstevens Date 2008-05-02 Time 16:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-25 Cont ID  
Sent By kstevens Date 2008-03-25 Time 17:17 Rev Time 0.00
Received By kstevens Date 2008-03-25 Time 17:17 Sent To  
Notes
2008-03-25 17:51:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE APPROVED GREASE INTERCEPTOR SHALL BE VERIFIED BY
 THE UTILITY DEPT, INDUSTRIAL PRETREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 644-1821, OR BY FAX (561) 822-2287, OR BY E-MAIL
 [email protected]. A WRITTEN APPROVAL/DETERMINATION SHALL
 BE SUBMITTED WHEN RESUBMITTING FOR REVIEW AT THE CITY
 WPB.
 ****RESPONSE NOTED, BUT BECAUSE THE GREASE INTERCEPTOR
 IS EXISTING, THAT DOES NOT MEAN IT HAS BEEN APPROVED.
 PLEASE CONTACT MR. COMPO FOR APPROVAL AND VERIFICATION
 THAT THE INTERCEPTOR IS IN WORKING ORDER. I ALSO WILL
 WORK ON THIS END TO CONTACT MR. COMPO FOR APPROVAL.
  
 3. OK
 4. OK
  
 5. SHT P.202ITEM 42, DISHWASHER SHALL DISCHARGE INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM. ARTICLE III
 SECTION 90-124(7)(B). PLEASE SHOW THE DISHWASHER
 CONNECTING TO THE SANITARY AS REQUIRED.
 ****RESPONSE NOTED, BUT THE CITY ORDINANCE PROHIBITS
 DISHWASHERS FROM DISCHARGING INTO THE GREASE WASTE
 SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By kstevens Date 2008-02-19 Time 12:07 Rev Time 0.00
Received By kstevens Date 2008-02-15 Time 16:51 Sent To  
Notes
2008-02-19 12:40:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION, (DBR), DIVISION OF HOTEL &
 RESTAURANT FOOD SERVICE LICENSE PRIOR TO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. MINIMUM TWO SETS OF PLANS
 REQUIRED WITH THE REVIEWED/STAMPED DBR REVIEW WITH
 SPECIFICATIONS SHEETS ATTACHED TO EACH SET OF PLANS.
 SECTION 102.2.1.
  
 2. THE APPROVED GREASE INTERCEPTOR SHALL BE VERIFIED BY
 THE UTILITY DEPT, INDUSTRIAL PRETREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 644-1821, OR BY FAX (561) 822-2287, OR BY E-MAIL
 [email protected]. A WRITTEN APPROVAL/DETERMINATION SHALL
 BE SUBMITTED WHEN RESUBMITTING FOR REVIEW AT THE CITY
 WPB.
  
 3. PLEASE INDICATE THE WALL FINISH FOR THE TOILET
 ROOMS. PER SECTION 1210.2 ALL WALLS WITHIN 2 FEET OF A
 WATER CLOSET SHALL BE A FINISH THAT IS SMOOTH, HARD &
 NONABSORBENT UP TO 4 FEET. PAINTED WALLS DO NOT COMPLY
 WITH THE "HARD" REQUIREMENT OF THIS SECTION.
  
 4. SHT P.201 PLUMBING FIXTURE CONNECTION SCHEDULE SHOWS
 EQUIPMENT ITEM NUMBERS 2 & 3 UNDER COLD WATER ROUGH-IN
 "FLOOR SINK" PLEASE CLARIFY. ALSO ITEMS 26, 34, 43 & 46
 INDICATE 2" DIRECT DRAIN SIZE, BUT ALSO INDICATE
 INDIRECT DRAIN ROUGH-IN. PLEASE CLARIFY. SECTIONS
 106.1.1, 802.3 & 802.3.2.
  
 5. SHT P.202ITEM 42, DISHWASHER SHALL DISCHARGE INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM. ARTICLE III
 SECTION 90-124(7)(B). PLEASE SHOW THE DISHWASHER
 CONNECTING TO THE SANITARY AS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved