| Plan Review Stops For Permit 08020250 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-03-07 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-03-07 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-02-21 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-02-21 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2008-02-21 12:17:18 | 2004 FBC W/2007 REVISIONS | | | INSTALL GENERATOR | | | | | | DENIED BY BUILDING | | | | | | 1)NO PERMIT PERTAINING TO A GENERATOR | | | SHALL BE ISSUED UNTIL AN APPLICATION FOR | | | THE GENERATOR, WITH A REVIEW FOR THE | | | GENERATOR, BY BUILDING, ELECTRIC, | | | MECHANICAL, AND ZONING PLAN REVIEWERS. | | | THE BUILDING REVIEW WILL BE FOR SLAB AND ANCHORING, | | | (SUBMIT A DETAIL) SEE FBC 1609.1.3, ELECTRICAL | | | REVIEW WILL BE FOR THE TRANSFER SWITCH, | | | (SUBMIT MANUF. SPECIFICATION SHEETS - | | | MUST BE LISTED AND APPROVED), MECHANICAL | | | REVIEW FOR THE EXHAUST, (PROVER | | | CLEARANCES FROM OPENINGS IN HOUSES | | | INCLUDING ADJOINING IF APPLICABLE), AND | | | ZONING, (SHOWING DISTANCE FROM PROPERTY | | | LINE ECT. - SURVEY REQUIRED). | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-05 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-05 |
Time |
14:08 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-15 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-15 |
Time |
14:06 |
Sent To |
G |
|
| Notes |
| 2008-02-15 14:21:34 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, METER ENCLOSURE, DISCONNECTS, ATS AND | | | PANELS, SO THAT COMPLIANCE WITH ARTICLES 225 AND 230 | | | CAN BE REVIEWED. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING | | | RECOMMENDED SETBACKS FROM STUCTURES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2008-03-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-07 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-07 |
Time |
10:10 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-15 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-15 |
Time |
14:44 |
Sent To |
B |
|
| Notes |
| 2008-02-15 14:55:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY | | | INDICATING ALL DIMENSIONS OF THE PROPOSED GENERATOR | | | FROM PROPERTY LINES AND STRUCTURES. PER *106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC FUEL GAS | | | SECTION *401.1 SCOPE. | | | | | | 2. SUBMIT TWO COPIES OF PROPOSED GENERATOR | | | MANUFACTURER'S SPECIFICATION OR INSTALLATION | | | INSTRUCTIONS INDICATING RECOMMENDED SETBACKS TO | | | STRUCTURES. | | | | | | 3. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/RES | | | PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE | | | GENERATOR LOCATION. (NOTE: FAILED ZONING 2/13/08) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-04 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-04 |
Time |
09:54 |
Sent To |
Z |
|
| Notes |
| 2008-03-04 09:54:50 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-02-21 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-02-12 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2008-02-12 08:57:08 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-07 |
Time |
11:23 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-03-07 |
Time |
11:23 |
Sent To |
B |
|
| Notes |
| 2008-03-07 11:24:59 | *** PROVISO *** | | | 1) GENERATOR TO REMAIN A MIN. OF 18" FROM BUILDING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-14 |
Time |
09:31 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-02-14 |
Time |
09:30 |
Sent To |
E |
|
| Notes |
| 2008-02-14 09:34:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SHOW ON SITE PLAN THE DISTANCE BETWEEN THE GENERATOR | | | AND THE BUILDING. SEE NFPA 37. | | | | | | 2) SEE ZONING REVIEW NOTE, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-04 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-04 |
Time |
13:12 |
Sent To |
E |
|
| Notes |
| 2008-03-04 13:13:08 | ***APPROVED - RESUB #1*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-02-13 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-02-13 |
Time |
15:03 |
Sent To |
E |
|
| Notes |
| 2008-02-13 15:04:16 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED | | | GENERATOR TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|