Plan Review Details - Permit 08020250
Plan Review Stops For Permit 08020250
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By rmcdouga Date 2008-03-07 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2008-03-07 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By rmcdouga Date 2008-02-21 Time 12:17 Rev Time 0.00
Received By rmcdouga Date 2008-02-21 Time 12:17 Sent To  
Notes
2008-02-21 12:17:182004 FBC W/2007 REVISIONS
 INSTALL GENERATOR
  
 DENIED BY BUILDING
  
 1)NO PERMIT PERTAINING TO A GENERATOR
 SHALL BE ISSUED UNTIL AN APPLICATION FOR
 THE GENERATOR, WITH A REVIEW FOR THE
 GENERATOR, BY BUILDING, ELECTRIC,
 MECHANICAL, AND ZONING PLAN REVIEWERS.
 THE BUILDING REVIEW WILL BE FOR SLAB AND ANCHORING,
 (SUBMIT A DETAIL) SEE FBC 1609.1.3, ELECTRICAL
 REVIEW WILL BE FOR THE TRANSFER SWITCH,
 (SUBMIT MANUF. SPECIFICATION SHEETS -
 MUST BE LISTED AND APPROVED), MECHANICAL
 REVIEW FOR THE EXHAUST, (PROVER
 CLEARANCES FROM OPENINGS IN HOUSES
 INCLUDING ADJOINING IF APPLICABLE), AND
 ZONING, (SHOWING DISTANCE FROM PROPERTY
 LINE ECT. - SURVEY REQUIRED).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-05 Cont ID  
Sent By btrobaug Date 2008-03-05 Time 14:26 Rev Time 0.00
Received By btrobaug Date 2008-03-05 Time 14:08 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By btrobaug Date 2008-02-15 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2008-02-15 Time 14:06 Sent To G
Notes
2008-02-15 14:21:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, METER ENCLOSURE, DISCONNECTS, ATS AND
 PANELS, SO THAT COMPLIANCE WITH ARTICLES 225 AND 230
 CAN BE REVIEWED.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS FROM STUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By mperson Date 2008-03-07 Time 10:10 Rev Time 0.00
Received By mperson Date 2008-03-07 Time 10:10 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By mperson Date 2008-02-15 Time 14:44 Rev Time 0.00
Received By mperson Date 2008-02-15 Time 14:44 Sent To B
Notes
2008-02-15 14:55:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY
 INDICATING ALL DIMENSIONS OF THE PROPOSED GENERATOR
 FROM PROPERTY LINES AND STRUCTURES. PER *106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC FUEL GAS
 SECTION *401.1 SCOPE.
  
 2. SUBMIT TWO COPIES OF PROPOSED GENERATOR
 MANUFACTURER'S SPECIFICATION OR INSTALLATION
 INSTRUCTIONS INDICATING RECOMMENDED SETBACKS TO
 STRUCTURES.
  
 3. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/RES
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION. (NOTE: FAILED ZONING 2/13/08)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 09:54 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 09:54 Sent To Z
Notes
2008-03-04 09:54:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-21 Cont ID  
Sent By rmcdouga Date 2008-02-21 Time 12:17 Rev Time 0.00
Received By rmcdouga Date 2008-02-12 Time 08:56 Sent To  
Notes
2008-02-12 08:57:08TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By tgordon Date 2008-03-07 Time 11:23 Rev Time 0.30
Received By tgordon Date 2008-03-07 Time 11:23 Sent To B
Notes
2008-03-07 11:24:59*** PROVISO ***
 1) GENERATOR TO REMAIN A MIN. OF 18" FROM BUILDING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By tgordon Date 2008-02-14 Time 09:31 Rev Time 0.25
Received By tgordon Date 2008-02-14 Time 09:30 Sent To E
Notes
2008-02-14 09:34:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW ON SITE PLAN THE DISTANCE BETWEEN THE GENERATOR
 AND THE BUILDING. SEE NFPA 37.
  
 2) SEE ZONING REVIEW NOTE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-04 Cont ID  
Sent By choops Date 2008-03-04 Time 13:12 Rev Time 0.00
Received By choops Date 2008-03-04 Time 13:12 Sent To E
Notes
2008-03-04 13:13:08***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By choops Date 2008-02-13 Time 15:03 Rev Time 0.00
Received By choops Date 2008-02-13 Time 15:03 Sent To E
Notes
2008-02-13 15:04:16***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720