Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By btrobaug Date 2008-02-19 Time 16:20 Rev Time 0.00
Received By btrobaug Date 2008-02-19 Time 12:18 Sent To ENG
Notes
2008-02-19 15:32:55 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE IF ANY OF THE LIGHT POLES SHOWN ARE NEW,
 AND IF SO SUBMIT MANUFACTURERS SPECIFICATIONS AND WIND
 LOAD CALCULATIONS FOR REVIEW. IF ALL ARE EXISTING,
 PLEASE NOTE SAME ON THE PLAN.
  
 2} LOCATE THE "EXISTING SERVICE POINT"ON THE PLAN.
  
 3} CIRCUITS LE-6, 10,14, AND 16 ARE MISCALCULATED IN
 THE PANEL SCHEDULE PER 22014(I) SHOULD BE 3 AMPS.SEE
 CIRCUITING SHEET E-1.
  
 4} CIRCUITS LW-2, 6,8 AND 12 ARE MISCALCULATED IN THE
 PANEL SCHEDULE, SHOULD BE 6,6,3 AND 6 AMPS
 RESPECTIVELY,SEE SHEET E-2 AND PANEL SCHEDULE, SHEET
 E-4. 220.14(I).
  
 5} CIRCUITS L-2 SHOULD BE CALCULATED AT 1.5 AMPS IN THE
 SCHEDULE, SEE SHEET E-2.220.14(I).
  
 6} CIRCUIT LW-4 IS CALCULATED CORRECTLY ASSUMING THOSE
 CIRCUITS ON SHEET E-2, NORTH WEST CORNER, LABELED
 "L-4", ARE IN FACT "LW-4. PLEASE CORRECT.
  
 7} THERE ARE 2 CIRCUIT HOME RUNS LABELEDL-8 ON SHEET
 E-2, ONE AT 3 AMPS AND ONE AT 1.5 AMPS. THE PANEL
 SCHEDULE, SHEET E-5, LISTS THAT CIRCUIT AS 3AMPS.,
 CORRELATE SAME.
  
 8} IN THE "SERVICE POINT DATA" CALCULATIONS, SHEETS
 E-3,4 AND 5, THERE IS NO RECEPTACLE LOAD INCLUDED
 .220.14(I).
  
 9) COULD NOT FIND BRANCH CIRCUIT L-14 ON THE PLANS.
  
 10} CIRCUIT L-19 IS LISTED AS A SPARE IN THE PANEL
 SCHEDULE, BUT SHOWN FEEDING THREE RECEPTACLES ON SHEET
 E-2.
  
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-02-20 Cont ID  
Sent By rchokshi Date 2008-02-20 Time 14:28 Rev Time 0.00
Received By rchokshi Date 2008-02-20 Time 14:22 Sent To  
Notes
2008-02-20 14:27:57FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A DETAIL DRAWING SHOWING THE LOCATION
 OF THE LIGHTING POLES.
  
 2. YOU MAY BE PUTTING A POLES IN THE CITY'S RIGHT OF
 WAY. THEREFORE, YOU NEED CITY'S RIGHT OF WAY APPROVAL
 FROM WINDEL PALMER 494-1040, 1000 45TH STREET, ENG
 DEPT.ONCE WE HAVE AN APPROVAL FROM WINDEL PALMER, WE
 WILL REVIEW YOUR DRAWINGS.
  
 3. MUST MEET CITY'S CONSTRUCTION STANDARDS FOR THE
 POLES AND ITS LOCATION.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 09:33 Sent To  
Notes
2008-02-11 09:34:02TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved