Plan Review Details - Permit 08020216
Plan Review Stops For Permit 08020216
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-07 Cont ID  
Sent By shill Date 2008-04-07 Time 07:59 Rev Time 0.00
Received By shill Date 2008-04-07 Time 07:59 Sent To  
Notes
2008-04-07 08:02:07REVISION, VENT NOA

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 17:57 Rev Time 0.00
Received By shill Date 2008-03-19 Time 17:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By rmcdouga Date 2008-02-11 Time 10:28 Rev Time 0.00
Received By rmcdouga Date 2008-02-11 Time 10:35 Sent To  
Notes
2008-02-11 10:28:412004 FBC W/2007 REVISIONS
 RE-ROOF
  
 DENIED BY BUILDING
  
 1) SPECIFY THE ROOF SLOPE AND THE MEAN ROOF HEIGHT OF
 THE STRUCTURE. FBC 106.1.1* CITY AMENDMENTS.
  
 2) THE CARLISLE WIP 100 SELF- ADHESIVE UNDERLAYMENT
 DOES NOT MEET THE REQUIREMENTS OF THE SECONDARY WATER
 BARRIER. THE RULE THAT IS IN EFFECT REQUIRES A
 SELF-ADHERING POLYMER MODIFIED BITUMEN CAP SHEET. SEE
 FS 553.844 AND RULE 9B-3.0475.
  
 3) A NOTICE OF COMMENCEMENT WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]