Plan Review Details - Permit 08020205
Plan Review Stops For Permit 08020205
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-02-13 Cont ID  
Sent By mjacobs Date 2008-02-13 Time 11:10 Rev Time 0.00
Received By mjacobs Date 2008-02-13 Time 07:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-03-06 Time 08:16 Rev Time 0.00
Received By btrobaug Date 2008-03-06 Time 07:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-11 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2008-02-11 Time 12:53 Sent To  
Notes
2008-02-11 12:53:58*** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 FBC ADMIN SECTION 106.1.2, 106.5, FS 553.73
  
 2) NOTE: PLEASE SEE THE TABLE *C* LIGHTING PERFORMANCE
 CALCULATIONS SHOWN ARE OVER THE MAXIMUM ALLOWANCES PER
 13-415.2.C.1.
 PLEASE ALSO SEE THE TOTAL ALLOWANCE PER TABLE *C* IS
 1.0 AND THE CALCULATIONS SHOW AN ALLOWANCE OF 1.1 WHICH
 IS OVER.
  
 3) NOTE: PLEASE STATE MAXIMUM TIMES ON OS DEVICES.
 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE VERIFY IF THERE ARE ANY SUITE/UNIT
 NUMBER(S) OR OF THIS TENANT IS THE ENTIRE FLOOR. THIS
 WAS APPLIED AS THE ENTIRE FLOOR.
 THIS IS TO BE CONFIRMED AND SUITE/UNIT NEEDS TO BE
 ADDED TO TITLEBLOCKS ONCE CONFIRMED.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS,
 PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION
 BELOW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-02-15 Cont ID  
Sent By mwennerg Date 2008-02-15 Time 11:31 Rev Time 0.00
Received By mwennerg Date 2008-02-15 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 09:00 Sent To M
Notes
2008-05-05 09:00:46TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 08:53 Sent To M
Notes
2008-04-30 08:53:55TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-27 Cont ID  
Sent By adarroug Date 2008-02-27 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-02-27 Time 16:17 Sent To  
Notes
2008-02-27 16:17:51TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-15 Cont ID  
Sent By mwennerg Date 2008-02-15 Time 11:31 Rev Time 0.00
Received By mwennerg Date 2008-02-11 Time 12:58 Sent To  
Notes
2008-02-11 12:58:52TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tgordon Date 2008-05-05 Time 11:24 Sent To  
Notes
2008-05-05 11:26:01REVISION TO MECH. PLAN M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By tgordon Date 2008-04-30 Time 09:05 Rev Time 0.30
Received By tgordon Date 2008-04-30 Time 09:05 Sent To  
Notes
2008-04-30 09:06:17REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By tgordon Date 2008-02-28 Time 16:16 Rev Time 0.20
Received By tgordon Date 2008-02-28 Time 16:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By tgordon Date 2008-02-11 Time 12:01 Rev Time 0.25
Received By tgordon Date 2008-02-11 Time 12:01 Sent To  
Notes
2008-02-11 12:11:24PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROVIDE OUT DOOR AIR CALCULATION FOR EACH HEAT PUMP
 UNIT ON MECHANICAL PLAN, SEE 2004 FBC/M 403.2.
  
 2) ADD TO A/C SPEC,S. NOTE D (1) 2004 FBC, ON
 MECHANICAL PLAN, SEE 2004 WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-12 Cont ID  
Sent By choops Date 2008-02-12 Time 15:48 Rev Time 0.00
Received By choops Date 2008-02-12 Time 15:48 Sent To  
Notes
2008-02-12 15:48:14*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.