| 2008-02-14 16:54:27 | COMMERCIAL SIGN, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- DESIGN CRITERIA NEEDS TO BE UPDATED. USING ASCE |
| | 7-98. NEED TO USE ASCE 7-02 AS ADOPTEDIN THE FBC |
| | 2004. |
| | ***NOTE: REVISE ORIGINAL DRAWINGS. HANDWRITTEN |
| | REVISIONS OVER EXISTING NUMBERARE NOT ALLOWED. |
| | |
| | 2-MISSINGSTRUCTURAL INFORMATION (SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE |
| | WIND LOADS OF SEC. 1609 FBC 2004): |
| | |
| | A) THERE ARE NOT SPECS FOR TYPE AND SIZE OFANCHOR |
| | TO BE USED TO HOLD LETTERS TO ALUMINUM RACEWAY. |
| | |
| | B) WHAT'S THE THICKNESS OF 2"X2" L BRACKET THAT |
| | HOLDS ALUMINUM RACEWAY TO EXISTING STRUCTURE. |
| | |
| | C) "MOUNTING PLATES W/ HARDWARE APPROP. TO WALL |
| | TYPE"ARE NOTSPECIFICATIONS.HOW CAN ENGINEER |
| | DETERMINE THAT SIGN WILLWITHSTAND 140MPH WIND LOADS |
| | IF SPECIFIC ANCHOR IS NOT SPECIFIED. |
| | |
| | D) WHAT'S THE SPACING FOR THE 3/8" THRU BOLT |
| | W/LOCKNUT & WASHER SPECIFIED.COORDINATE WITH ITEM |
| | 2(C) ABOVE. |
| | |
| | E)IT'S NOT CLEAR IF THE SIGN IS TO BE ATTACHED TO |
| | THE "DRYVIT" FASCIA OR TO THE STRUCTURAL MEMBERS THAT |
| | HOLD THE FASCIA.COORDINATE WITH ITEM 2(C) ABOVE. |
| | NOTE: FASCIA ALONE MAY NOT BE USED AS A STRUCTURAL |
| | SUPPORT OF THE SIGN. |
| | |
| | 3- VALUATION DECLARED INTHE PERMIT APPLICATION IS TOO |
| | LOW.UPDATE VALUATION TO INCLUDE TOTAL COST FOR THE |
| | INSTALLATION OF THE SIGN, INCLUDING THE ENGINEERING |
| | FEES.ALSO,VALUATION TO INCLUDE REMOVAL OF EXISTING |
| | AWNING AS INDICATED ON PLANS. IF SIGN COMPANY IS NOT |
| | DOING THE REMOVAL, THEN A SEPARATE PERMIT IS REQUIRED. |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- NOTICE OF COMMENCEMENT IS REQUIRED BY SEC. 713.13 |
| | FLORIDA STATUTE. |
| | |
| | NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS OFFICE |
| | TOBE SEND TO THE BOARDOF ENGINEERS FOR REVIEW. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |