| 2008-02-27 16:31:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | **THE SUBMITTED ISOMETRIC GAS RISER DOES NOT INDICATE |
| | THE CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | THE ONLY DEMENTIONS BEING INDICATED ARE 50' TOTAL |
| | DEVELOPED LENGTH. DOES THAT INCLUDE THE EXISTING GAS? |
| | GAS PLAN REVIEW NEEDS TO HAVE EACH CUT SECTION OF PIPE |
| | FOR THE PROPOSED GENERATOR INDICATED AS WELL AS THE |
| | LONGEST LENGTH OF THE EXISTING SYSTEM. |
| | |
| | 2. CLEARLY INDICATE THETYPE OF GAS, (LP OR NATURAL) |
| | BEING USED. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **THIS INCLUDES THE EXISTING BTU LOADS TO THE HOUSE AS |
| | WELL AS THE PROPOSED BTU LOAD OF THE GENERATOR. A GAS |
| | PLAN REVIEW CAN NOT BE DONE WITHOUT A TOTAL BTU LOAD OF |
| | THE SYSTEM BEING KNOWN. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **THIS INCLUDES THE EXISTING SYSTEM DISTANCE TO THE |
| | HOUSE AS WELL AS THE PROPOSED GENERATOR'S DISTANCE. GAS |
| | PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING THE LONGEST |
| | LENGTH OF THE SYSTEM |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | **A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT KNOWING |
| | THE PRESSURE TO THE SYSTEM. |
| | |
| | 6. REFERENCE MECHANICAL COMMENT #1 AND COMPLY. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |