Plan Review Details - Permit 08020137
Plan Review Stops For Permit 08020137
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-02 Cont ID  
Sent By jwitmer Date 2008-12-02 Time 14:59 Rev Time 0.77
Received By jwitmer Date 2008-12-02 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 16:30 Rev Time 0.55
Received By jwitmer Date 2008-10-20 Time 16:30 Sent To  
Notes
2008-10-20 16:41:55BUILDING PLAN REVIEW
 PERMIT: 08020137
 ADD: 9847 OKEECHOBEE BLVD
 CONT: TRINITY RETAIL CONSTRUCTION
 TEL: (772)834-8021
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 OCT.20,2008
 3RD REVIEW
 ACTION: DENIED
  
  
 1) COMPLIED.
  
 2A) 3RD REQUEST, PLEASE REVIEW ALL SHEETS OF THE PLANS
 AND AND ENERGY CALCULATIONS, CORRECT THE ADDRESS OF THE
 JOBSITE, MANY INDICATE WORK TO BE COMPLETED UNDER THIS
 PERMIT IS AT 4354 OKEECHOBEE BLVD.
  
 2B) THE SQUARE FOOTAGE OF THE BUILDING AND THE ENERGY
 CALCULATIONS DO NOT MATCH.
  
 2C) IN THE INPUT DATA REPORT THE EXTERIOR SQUARE
 FOOTAGE FOR DOORS IS LEFT BLANK.
  
 2D) IN THE IINPUT DATA REPORT THE REPORT INDICATES THE
 WALLS ARE A A .5 INCH EXTERIOR PLYWOOD, 3 5/8 INCH
 METAL STUD, R-11 INSULATION AND A 1/2 INCH GYPSUM
 DRYWALL, UNDER SHELL PERMIT# 0710-650, THE WALLS ARE
 INDICATED AS EIGHT INCH BLOCK WITH 2 INCH STYROFOAM
 INSULATION PLEASE UPDATE THE INPUT DATA REPORT TO
 REFLECT THE ACTUAL EIGHT INCH MASONARY WALL SYSTEM,
 METHOD A DOES ALLOW FOR TRADE OFFS FOR INSULATION
  
 2E) THE INPUT DATA REPORT ALSO INDICATES TO BE A METAL
 BUILDING TYPE ROOF WITH R-19 BATTS, AGAIN THE SHELL
 BUILDING ROOF WAS BUILT WITH (2) LAYERS OF RIGID
 INSULATION 2 1/4" POLYISOCYRATE FOAM W/ TOP LAYER OF
 3/4" RIGID FIBERGLASS PLEASE CORRECT THE ENRGY CALCS TO
 REFLECT THE ACTUAL ROOFING ASSEMBLIES.
  
 3) COMPLIED.
  
 5) BUILDING PROVISO NOTE, SIGN PERMITS UNDER A SEPARATE
 PERMIT.WEST PALM BEACH ADMINISTRATIVE CODE
 105.1.
  
 6-9) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-27 Cont ID  
Sent By jwitmer Date 2008-08-27 Time 13:04 Rev Time 1.22
Received By jwitmer Date 2008-08-27 Time 13:04 Sent To  
Notes
2008-08-27 13:18:20BUILDING PLAN REVIEW
 PERMIT: 08010137
 ADD: 9847 OKEECHOBEE BLVD
 CONT: TRINITY RETAIL CONSTRUCTION
 TEL: (772)834-8021
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 AUGUST 27,2008
 2ND REVIEW
 ACTION: DENIED
  
  
 1A) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL ONLY.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) 2ND REQUEST, PLANS SUBMITTED FOR PERMIT (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE
 UPDATE PLANS COVERSHEET STILL INDICATES THE 2006
 SUPPLEMENTS..
  
 2) 2ND REQUEST, PLEASE REVIEW ALL SHEETS OF THE PLANS
 AND AND ENERGY CALCULATIONS, CORRECT THE ADDRESS OF THE
 JOBSITE, MANY INDICATE WORK TO BE COMPLETED UNDER THIS
 PERMIT IS AT 4354 OKEECHOBEE BLVD.
  
 3) THE SHELL PERMIT IS A ISSUED PERMIT. WHEN THE
 BUILDING SHELL TEAM IS DIFFERENT FROM THE INTERIOR FIT
 UP , A SHOP DRAWING STAMP OF APPROVAL FROM THE BASE
 BUILDING DESIGN TEAM IS REQUIRED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) THE BASE BUILDING CONTRACTOR WILL ALSO NEED TO
 PROVIDE A LETTER TO ALLOW THE TENANT FIT UP CONTRACTOR
 TO START WORK BEFORE THE ISSUANCE OF A CERTIFICATE OF
 COMPLETION THIS WILL BE REQUIRED TO BE NOTARIZED
 LETTER.
  
 5) NOTE, SIGN PERMITS UNDER A SEPARATE PERMIT.WEST PALM
 BEACH ADMINISTRATIVE CODE
 105.1.
  
 6)2ND REQUEST, SHEET A-6 DETAIL# 14 INDICATES THE USE
 OF WOOD BUCKS, PLEASE NOTE THE BUILDING CLASSIFICATION
 TYPE II-B SECTION 603.1 (1) FIRE RETARDANT TREATED WOOD
 CAN BE USED IN NON-BEARING PARTITIONS, PLEASE CORRECT
 WOOD BUCKS TO FIRE RETARDANT TREATED WOOD.
  
 7) SHEET A-6 PARTITION GENERAL NOTE (6) INDICATES THE
 USE OF WATER RESISTANT GYPSUM BOARD ALL WET AREAS,
 PLEASE SEE 1210.2 FOR WALLS WITHIN 2?-0? OF WATER
 CLOSETS, URINALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE TO A HEIGHT OF 4?-0?.
  
 8) 2ND REQUEST, NOTE THE MEP SHEETS THE ENGINEERING
 FIRM (JORDON & SKALA ENGINEERS, INC) IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION. FLORIDA S. S. 471.023
 CERTIFICATE OF AUTHORIZATION. THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 9) 2ND REQUEST, CODE DATA COVER SHEET INDICATES AN
 OCCUPANT LOAD OF 124 REQUIRING 2 EXITS ASA STATED IN
 THE CODE ANALYSIS, PLEASE LOOK AT SHEET A-3 INDICATING
 AT THE REAR OF THE SHOW ROOM AN EXIT LIGHT FOR THE 2ND
 EXIT. PLEASE CORRECT NOTE ON SHEET A-1 REAR SET OF
 DOORS REMOVE ENTRY /EXIT HARDWARE AND LOCK SHUT!!!!!!!
 TABLE 1014.1 MERCANTILE OCCUPANT LOADS >50 REQUIRE 2
 MEANS OF EGRESS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By jwitmer Date 2008-02-11 Time 22:53 Rev Time 1.55
Received By jwitmer Date 2008-02-11 Time 22:53 Sent To  
Notes
2008-02-11 22:55:15BUILDING PLAN REVIEW
 PERMIT: 08010137
 ADD: 9847 OKEECHOBEE BLVD
 CONT: TRINITY RETAIL CONSTRUCTION
 TEL: (772)834-8021
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND
  
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE UPDATE
 PLANS.
  
 2) PLEASE REVIEW ALL SHEETS OF THE PLANS AND CORRECT
 THE ADDRESS OF THE JOBSITE, MANY INDICATE WORK TO BE
 COMPLETED UNDER THIS PERMIT IS AT 4354 OKEECHOBEE
 BLVD.
  
 3) THE SHELL PERMIT IS NOT YET RECEIVED A ISSUED
 PERMIT. PLEASE SEE THE ELECTRICAL COMMENT NUMBER ONE
 WHICH DEALS WITH DIFFERENT DESIGN TEAMS FROM THE BASE
 BUILDING AND SHOP DRAWING STAMP APPROVAL FROM THE BASE
 BUILDING DESIGN TEAM.
  
 4) THE BASE BUILDING CONTRACTOR WILL ALSO NEED TO
 PROVIDE A LETTER TO ALLOW THE TENANT FIT UP CONTRACTOR
 TO START WORK BEFORE THE ISSUANCE OF ACERTIFICATE OF
 COMPLETIONTHIS WILL BE REQUIRED TO BE NOTARIZED
 LETTER.
  
 5) NOTE, SIGN PERMITS UNDER A SEPARATE PERMIT.WEST PALM
 BEACH ADMINISTRATIVE CODE
 105.1.
  
 6)SHEET A-6 DETAIL# 14 INDICATES THE USE OF WOOD BUCKS,
 PLEASE NOTE THE BUILDING CLASSIFICATION TYPE II-B
 SECTION 603.1 (1) FIRE RETARDANT TREATED WOOD CAN BE
 USED IN NON-BEARING PARTITIONS, PLEASE CORRECT WOOD
 BUCKS TO FIRE RETARDANT TREATED WOOD.
  
 7) SHEET A-6 PARTITION GENERAL NOTE (6) INDICATES THE
 USE OF WATER RESISTANT GYPSUM BOARD ALL WET AREAS,
 PLEASE SEE 1210.2 FOR WALLS WITHIN 2?-0? OF WATER
 CLOSETS, URINALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE TO A HEIGHT OF 4?-0?.
  
 8)NOTE THE MEP SHEETS THE ENGINEERING FIRM IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION. FLORIDA S. S.
 471.023 CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK
 FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 9) CODE DATA COVER SHEET INDICATES AN OCCUPANT LOAD OF
 124 REQUIRING 2 EXITS ASA STATED IN THE CODE ANALYSIS,
 PLEASE LOOK AT SHEET A-3 INDICATING AT THE REAR OF THE
 SHOW ROOM AN EXIT LIGHT FOR THE 2ND EXIT.PLEASE
 CORRECT NOTE ON SHEET A-1 REAR SET OF DOORS REMOVE
 ENTRY /EXIT HARDWARE AND LOCK SHUT!!!!!!! TABLE 1014.1
 MERCANTILE OCCUPANT LOADS >50 REQUIRE 2 MEANS OF
 EGRESS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 08:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 09:44 Sent To PC
Notes
2008-12-23 09:45:07** DENIED**
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEWS. BASE
 BUILDING HAS YET TO OBTAIN CO OR CC. THIS WAS GONE OVER
 WITH OWNER REPRESENTATIVE, CONTRACTOR AND DESIGN TEAM.
 PLANS WILL NOT BE STAMPED AND PROCESSED UNTIL SUCH
 TIME. CALLED AND SPOKE TO OMAR AS LISTED ON COVER
 SHEET.
 FEE BALANCE IS STILL DUE BEFORE PERMIT CAN BE ISSUED.
 PLANS WILL BE PLACED OUT FRONT UNDER ?T? ON HOLD.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-12-03 Cont ID  
Sent By dpalmer Date 2008-12-03 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2008-12-03 Time 12:49 Sent To  
Notes
2008-12-03 12:49:54 
 ** DENIED 4TH REVIEW**
  
 *THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW WHICH
 HAVE NOT BEEN ADDRESSED.
  
  
  
 1) NOTE: THE BASE BUILDING IS NOT COMPLETE AND STILL
 DOES NOT HAVE A CERTIFICATE OF COMPLETION. THE BASE
 BUILDING AS GIVEN ON THE LAST THREE REVIEWS ARE STILL
 IS STILL UNDER THE RESPONSIBILITY OF THE BASE BUILDING
 DESIGN TEAM. ALL PLANS FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADE REVIEW ARE REQUIRED
 TO CONTAIN A *SHOP DRAWING REVIEW STAMP* FROM THE BASE
 BUILDING DESIGNERS BEFORE PERMIT MAY BE ISSUED.
 WHEN WORK ON THE SAME BUILDING AND SAME SPACE IS TO
 TAKE PLACE A LETTER OF UNDERSTANDING BETWEEN EACH
 LICENSE CONTRACTOR IS REQUIRED.
 FS 481, 471, 489
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE STILL NOT CODE COMPLIANT. THERE ARE STILL SPECIFIC
 ITEMS WHICH WERE GIVEN ON THE PREVIOUS REVIEWS WHICH
 ARE STILL THE EXACT SAME.
 ONE EXAMPLE IS THE EXTERIOR LIGHTING WHICH IS STILL IN
 FACT *BLANK* ON THE INPUT DATA REPORT. THERE IS NO
 LIGHTING AT ALL PLACED INTO THE INPUT DATA REPORT. THIS
 IS NOT POSSIBLE WHEN THE PLANS DO HAVE EXTERIOR
 LIGHTING SHOWN. PLEASE SEE 13-415.2.ABC.1.3. THE
 SUBMITTED METHOD OF CALCULATION IS A METHOD FOR *WHOLE
 BUILDING*. THIS METHOD CAN NOT BE USED UNLESS ALL
 COMPONENTS REQUIRED FOR MINIMUM COMPLIANCE IS
 MET.13-400.3.A.
 PLEASE SEE ANOTHER EXAMPLE IS *PIPING* ON THE IDR. THIS
 IS ALSO BLANK. THIS IS ALSO NOT POSSIBLE WHEN SECTION
 13-411.1.ABC.2 REQUIRES MINIMUM VALUES.
  
 ** PLEASE BE SURE TO GO OVER CALCULATIONS AND PLANS.
 PLEASE BE SURE TO COORDINATE ALL ITEMS AS PREVIOUSLY
 REQUESTED.13-400.3.A, 13-101.1.6, 13-101.1,
 13-415.2.ABC.1.1,.1.2.
  
 3) NOTE: PANEL BOARD *A* STILL NOTES THE ENTIRE SECTION
 ONE AND TWO AS EXISTING WHEN RISER SHOWS SECTION TWO AS
 NEW. IN SECTION ONE OF PANEL THIS SHOWS A SEPARATE
 100AMP FEED TO NEW SECTION.
 THIS WOULD NOT BE A SECTION TWO PANEL IF IT HAS A
 SEPARATE SUB-PANEL BREAKER AND FEEDERS. THIS WOULD BE A
 SUB PANEL.
 A SECTION TWO FOR ANY PANEL BOARD IS TYPICALLY
 EQUIPMENT WITH THE SAME RATING WITH FEED-THRU LUGS.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 10:06 Sent To PC
Notes
2008-10-28 10:06:39 
 ** DENIED 3RD REVIEW**
  
  
 1) NOTE: PLEASE KNOW THE SHELL PERMITTED BUILDING IS
 NOT COMPLETE AS OF THIS REVIEW. UNTIL THE SHELL PERMIT
 HAS BEEN CLOSED OUT THE BASE BUILDING DESIGN TEAM IS
 RESPONSIBLE FOR BUILDING AND SHALL STAMP SAID BUILD OUT
 PLANS AS *SHOP DRAWINGS*.
  
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLIANT AND DO NOT CONFORM TO THE
 REQUIREMENTS OF THE FLORIDA ENERGY CODE FOR METHOD *A*
 *WHOLE* BUILDING.
 THERE ARE SOME ITEMS STILL SHOWN BLANK WITH NO
 INFORMATION ON THE INPUT DATA REPORT. THIS IS NOT
 POSSIBLE FOR THIS BUILDING AND USING A WHOLE BUILDING
 METHOD.
 ONE EXAMPLE IS THE EXTERIOR LIGHTING WHICH IS BLANK.
 ANOTHER WOULD BE THE NO DOORS.
 ANOTHER WOULD BE NO VALUE/KW FOR WATER HEATER.
  
  
 ***ADDRESS ON THE CALCULATIONS STILL SHOW A LOCATION
 WHICH IS NOT WITHIN THIS JURISDICTION.
 PLEASE BE SURE TO COMPLETE THE CALCULATIONS WITH ALL
 COMPONENTS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 AND .1.3.
 PLEASE SEE 13-400.3.A, 13-101.1.6, 13-101.1.1 ETC
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.1.1, 106.5
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FAC
 61G15-23.002 WHICH REQUIRES ALL INFORMATION AS LISTED
 ON THE TITLE BLOCKS FOR ENGINEERING FIRMS. THE FLORIDA
 STATUTE WHICH REQUIRES THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SAID FIRM IS FS 471.023. THE TITLE BLOCKS
 WERE REVISED HOWEVER THEY LIST THE * FLORIDA STATUTE
 NUMBER 471.023 INSTEAD OF THE FIRM LICENSE NUMBER. ????
 PLEASE KNOW IF THIS HAD BEEN THE ONLY COMMENT THE TITLE
 BLOCKS WOULD HAVE BEEN REDLINED WITH THE CORRECT
 LICENSE INFORMATION AS THE MECHANICAL AND PLUMBING
 REVIEWERS HAVE DONE. AS THIS IS NOT THE ONLY COMMENT
 PLEASE REVISE THE PLANS CORRECTLY WITH THE REQUIRED
 NUMBER.
 THE FLORIDA ADMINISTRATIVE CODES GIVEN REQUIRE THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF ENGINEER AND
 THE PRINTED FIRM LICENSE NUMBER ALONG WITH ADDRESS ETC.
 ** THIS IS REQUIRED FOR ALL TRADES AND ON ALL SHEETS
 WHETHER OR NOT COMMENT HAS BEEN MADE BY THAT TRADE.
 THIS HAS BEEN A REQUIREMENT SINCE 1977.
  
 4) NOTE: PLEASE SEE CIRCUITING WILL BE REQUIRED TO BE
 REVISED TO BE SPECIFIC.
 HOW CAN THE PANEL SCHEDULE LABEL ALL AS EXISTING
 PANELBOARD WHEN THE RISER SAYS NEW?
 408.4
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-03 Cont ID  
Sent By dpalmer Date 2008-09-03 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2008-09-03 Time 15:10 Sent To  
Notes
2008-09-03 15:10:18 
  
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON NEW
 INFORMATION AND/OR DOCUMENTS AS SUBMITTED.
  
 1) NOTE: PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED
 HOWEVER IS MOST HELPFUL IN ANY REVIEW PROCESS OF PLANS.
  
 2) NOTE: THE BASE BUILDING HAS NOT OBTAINED ANY
 CERTIFICATE OF COMPLETION AT THIS TIME. PLEASE SEE THIS
 NOTE FROM THE PREVIOUS REVIEW. AS STATED PREVIOUSLY THE
 BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL C OF C.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW THE BUILDING IN WHICH THE APPLIED SCOPE OF
 WORK IS BEING APPLIED IS NOT PERMITTED AT THIS TIME.
 PLEASE ALSO KNOW ONCE THE SHELL BUILDING IS ISSUED AND
 THE BUILD OUT SCOPE OF WORK IS BEING DONE IN THIS SHELL
 WHICH DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY THE
 BUILD OUT PLANS SHALL CONTAIN A STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD FOR EACH
 TRADE SHEET. THIS BUILDING WOULD STILL BE UNDER THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM AND ANY
 BUILD OUT WORK WOULD NEED TO BE NOTED. THIS STAMP WOULD
 BE A *SHOP DRAWING * REVIEW STAMPED OR OTHER MEANS
 WHICH MAY BE GONE OVER.
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWER(S)
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
 THE BASE BUILDING PERMIT # IS 07100650 WHICH AS OF THIS
 REVIEW ON 2/9/08 HAS COMMENTS TO BE ADDRESSED BEFORE
 ISSUANCE.
  
 3) NOTE: THIS NOTE ALSO STILL REMAINS FROM PREVIOUS
 REVIEW AS THERE ARE DOCUMENTS STILL SUBMITTED WITH ANY
 ADDRESS OF 4354.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ADDRESS OF PROJECT. PLEASE SEE THE
 COVER SHEET OF THE SUBMITTED PLANS CONTAINS 9847
 OKEECHOBEE BLVD, YET THE OTHER TITLE BLOCKS IN SETS
 CONTAIN 4354 OKEECHOBEE BLVD.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.5 ADMIN SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 *FOR COORDINATION AND ADDITIONAL INFORMATION.
  
 4) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW. PLANS
 STILL DO NOT INDICATE ALL CODES AS GIVEN ON PREVIOUS
 REVIEW **
  
 **PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS. (PLANS SHOW 2006 REVISIONS)
 2005 NFPA-70
 2003 NFPA-101
  
 ** THIS IS REQUIRED ON ELECTRICAL SHEETS AS WELL AS
 ARCHITECTURAL COVER PAGE.
 FBC 106.5, 106.1.2
  
 5) NOTE: ** THIS NOTE REMAINS FROM PREVIOUS REVIEW.
 PLEASE SEE PLANS IN FACT CONTAIN THE PREVIOUS
 *PHOTO-COPIED* FORM *C* AND NOW NEW METHOD *A*
 CALCULATIONS. PLEASE PROVIDE THE REQUIRED CALCULATIONS.
 PLEASE ONLY SUBMIT THE *ONE* WHICH MEETS CODE. HOW CAN
 METHOD *A* BE SUBMITTED WHEN THERE ARE SEVERAL ITEMS IN
 THE INPUT DATA REPORT WHICH ARE BLANK. THE METHOD *A*
 IS FOR *WHOLE BUILDING* COMPLIANCE. HOW CAN THIS BE
 SUBMITTED WHEN THERE ARE ITEMS ON THE IDR WHICH ARE
 BLANK? JUST ONE EXAMPLE OF THIS IS THE FACT THE
 EXTERIOR LIGHTS ON PLANS ARE LEFT BLANK ON THE IDR.
 THIS IS NOT THE ONLY ITEM. PLEASE ALSO SEE OTHER ITEMS
 FOR OTHER TRADES.
 13-415.2.ABC.1.1, .1.2 AND .1.3
  
 ** PREVIOUS REVIEW NOTE **
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2
 PLEASE BE AWARE IF THE INTERIOR SCOPE OF WORK IS
 PERMITTED BEFORE C OF O, THE BASE BUILDING METHOD B
 CALCULATIONS WILL BE REQUIRED TO BE REVISED WITH KNOWN
 AS THIS IS CURRENTLY BASED ON ASSUMPTIONS ON SHELL
 PLANS AND CALCULATIONS.
 PLEASE SEE THE METHOD C* FORM SUBMITTED IS NOT
 COMPLETE. THE LIGHTING DENSITIES ARE NOT FILLED OUT AND
 ALL INFORMATION IS MISSING.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR INTERIOR
 AND EXTERIOR LIGHTING. NOT ALL EXTERIOR LIGHTS AS SHOWN
 ON PLANS ARE ON THE SHELL BUILDING PLANS. FOR EXAMPLE
 THE OCTAGONAL NOTE #4 DOES NOT APPLY TO BASE PLANS.
 PLEASE SEE THE FORMS SUBMITTED ARE ALSO PHOTO-COPIES,
 NOT SIGNED, DATED OR SEALED WITH ORIGINAL SIGNATURES AS
 REQUIRED PER FBC 13-103.1.1.1
 FAC 61G15-23.002
 FS 481.221/ 471.025
  
 ** AS LIGHTING PERFORMANCE CALCULATIONS ARE NOT
 COMPLETE OR SUBMITTED NO FULL REVIEW FOR CODE
 COMPLIANCE COULD BE DONE AT THIS TIME. THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 6) NOTE: ON THE PREVIOUS REVIEW NOTE #5 AS NOTED THE
 COMMENT WAS THAT THE CERTIFICATE OF AUTHORIZATION
 NUMBER WAS MISSING. THE PLANS NOW CONTAIN THIS NUMBER
 AND IT HAS BEEN REVIEWED WITH THE STATE OF FLORIDA
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 SITE. THE ADDRESS ON THE SITE DOES NOT COORDINATE WITH
 THE PLANS. PLEASE BE SURE THE ADDRESS COORDINATES AS
 SHOWN ON THE STATE SITE. IF THERE IS MORE THAN ONE
 LOCATION OF BUSINESS, THEN MORE THAN ONE MAY BE LISTED.
 FAC 61G15-23.002
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE BLOCKS
 FOR ENGINEERING FIRM ETC ON MECHANICAL, PLUMBING AND
 ELECTRICAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 PLEASE SEE MISSING PRINTED NAME, MISSING PRINTED
 LICENSE NUMBER AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 7) NOTE: PLEASE SEE COMMENT FROM PREVIOUS REVIEW WITH
 RESPECT TO THE NUMBER OF NIGHT LIGHTS LEFT ON. THE
 AMOUNT OF LIGHTING AS SHOWN DOES NOT MEET THE INTENT OF
 THE FLORIDA ENERGY CODE AND IS NOT PERMITTED BY THIS
 AHJ.
 PLEASE VERIFY THE LIGHTING CONTROLS ON PLANS. PLANS
 STATE OVER RIDES YET OVER RIDES OF ANY SYSTEM WOULD BE
 AUTOMATED NOT A SINGLE POLE SWITCH . EXAMPLE: AN
 OCCUPANT COMES INTO WORK WHEN THE NORMAL TIME OF DAY
 SCHEDULING IS OFF. THAT PERSON WOULD BE ABLE TO OVER
 RIDE THE TIMED SCHEDULING. THE PERSON LEAVES AN HOUR
 LATER. IF THE OVER WAS A STANDARD SINGLE POLE SWITCH
 THE LIGHTS WOULD REMAIN ON. THERE ARE NOTES ON SYMBOL
 LEGEND WHICH SEEMED TO INDICATE THERE ARE TO BE
 OCCUPANCY SENSORS HOWEVER SEPARATE SPACES SUCH AT THE
 BATHROOMS ONLY SHOW STANDARD SINGLE POLE DEVICES.
 ** PLEASE EXPLAIN SYSTEM.
  
 ** SEE COMMENTS FROM PREVIOUS REVIEW NOTE #6.
 PLEASE KNOW BASED ON NOTE #4 ABOVE. PLEASE KNOW THE
 INTENT OF THE ENERGY CODE IS TO CONSERVE ENERGY. PLEASE
 SEE 13-415.1.ABC.1 WHICH REQUIRES ALL LIGHTING TO BE
 TURNED OFF WHEN NOT IN USE. THIS AHJ DOES NOT HAVE AN
 ISSUE WITH PERMITTING *NIGHT LIGHTS* FOR THE REASON OF
 LIFE SAFETY OR SECURITY HOWEVER THIS IS TO BE TO A
 MINIMUM OF 1FT CANDLE WHICH THE LIFE SAFETY CODE
 REQUIRES FOR EGRESS UNDER NORMAL AND EMERGENCY
 CONDITIONS ON FLAT WALKING SURFACES. (NFPA-101 7.8/7.9
 PLEASE PROVIDE PHOTO-METRICS LEVELS FOR EGRESS PATHS
 UNDER THE NORMAL AND EMERGENCY CONDITIONS FOR THE NIGHT
 LIGHT FIXTURES AE. PLEASE KNOW IF THE LIGHTING LEVELS
 ARE OVER, THEN DESIGN WILL BE REQUIRED TO ADJUSTED.
 PLEASE SEE BOTH CHAPTER 10 OF THE FBC AND LIFE SAFETY
 CODE 7.8.1.2.2ALLOWS THE USE OF OCCUPANCY SENSORS ON
 THESE FIXTURES.
 THE OTHER ALLOWANCE WOULD BE FOR EACH FIXTURE WHICH IS
 3 LAMPS TO REMAIN ON WITH 1-LAMP OR TWO TO MEET THE 1FT
 CANDLE MINIMUM. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3 AS LIGHTING CONTROLS ARE NOT COMPLETE WITH ALL
 LIGHTING ON PLANS.
 FOR EXAMPLE: PLEASE SEE SEPARATE SPACES WHICH REQUIRES
 LIGHTING TO BE ABLE TO OVER RIDE THE LIGHTING CONTROLS,
 AND REQUIRES A MAXIMUM OVER RIDE TIME. PLANS INDICATE A
 MANUAL OVER RIDE HOWEVER DOES NOT INDICATE THE MAXIMUM
 OVER RIDE TIME.
 PLEASE SEE THE SEPARATE SPACES AS BATHROOMS ETC ONLY
 SHOW A STANDARD SWITCH WHICH DOES NOT MEET THESE
 SECTIONS OF THE CODE.
 PLEASE SEE THE REAR OFFICE/WORK ROOM WHICH SHOWS A SR
 YET THE SYMBOL LEGEND DOES NOT CONTAIN THIS DEVICE OR
 INFORMATION ON WHAT TYPE OF DEVICE IT IS?? PLEASE ALSO
 SEE THE OCTAGONAL NOTE #2 WHICH STATES OCCUPANCY SENSOR
 YET COULD NOT LOCATE ANY MAXIMUM TIMES.
 ** PLEASE CALL TO GO OVER IF NEEDED.
  
 8) NOTE: PLEASE SEE NOTE #7 FROM PREVIOUS REVIEW. MAY
 NOT HAVE THE EMERGENCY/EXIT LIGHTS ALL ON ONE CIRCUIT
 UNLESS MEETING THE EXCEPTIONS IN THE CODE. THE LIGHTING
 IS REQUIRED TO BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT. THAT IS THE CODE, THE *EXCEPTION* IS IF YOU
 MEET THE ITEMS LISTED UNDER 700.12F. BASED ON THE PLANS
 AND INFORMATION SUBMITTED, THE LIGHTING DOES *NOT* MEET
 THE EXCEPTION AND CIRCUITING NEEDS TO BE REVISED.
  
 ** PREVIOUS REVIEW COMMENT **
 PLEASE SEE 700.12F WHICH REQUIRES EMERGENCY AND EXIT
 LIGHTS TO BE CONNECTED TO THE LOCAL LIGHTING BRANCH
 CIRCUIT. THERE IS EXCEPTIONS FOR MULTIPLE CIRCUITS IN
 UNINTERRUPTED AREAS, HOWEVER PLEASE SEE PLANS WHICH
 SHOW FIXTURES IN OTHER SPACES STILL ON THE DEDICATED
 CIRCUIT WHICH IS NOT PERMITTED.
  
 9) NOTE: SAME COMMENT AS PREVIOUS REVIEW. MAY NOT USE
 *LIGHTING* OR *RECEPTACLES* IN GENERAL. THE PANEL
 SCHEDULE STILL INDICATES THIS.
 THIS WAS REVISED UNDER THE 2005 CODE
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE PANEL SCHEDULE CIRCUITS SHALL BE
 SPECIFIC TO CIRCUITS. FOR EXAMPLE: THE SHOW WINDOW
 RECEPTACLES ARE REQUIRED TO BE LABELED AS SUCH. MAY NOT
 LABEL ALL AS *GENERAL LIGHTS* OR GENERAL RECEPTACLES*.
 PLEASE SEE 408.4, 210.62.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE SEE NOTE #9 FROM PREVIOUS REVIEW. THE
 PLANS STILL DOE NOT CONTAIN ANY LOAD CALCULATIONS
 MEETING THE MINIMUM CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOAD CALCULATIONS BASED ON NEC. PLEASE
 SEE THE SHOW WINDOWS FOR EXAMPLE NEED TO SHOW HOW THESE
 LOADS WERE FIGURED PER 220.43
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, 230.42 ETC
  
 11) NOTE: ALL TITLE BLOCKS ON ALL SHEETS WHICH CONTAIN
 THE TITLE BLOCK FOR THE ARCHITECT SHALL CONTAIN THE
 INFORMATION AS REQUIRED PER FAC 61G1-16.004.
 ** MISSING PRINTED LICENSE NUMBER*
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY THOSE OTHER TRADES.
  
 12) NOTE: THIS IS THE SAME NOTE AS PREVIOUSLY NOTED IN
 #11. THE PLANS STILL SHOW EQUIPMENT OUTSIDE YET RISER
 AND PLANS DO NOT INDICATE THIS EQUIPMENT. PLEASE SEE
 POWER PLANS. THERE IS SOMETHING ON PLANS OUTSIDE. WHAT
 IS IT?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO SHOW PANELS OUTSIDE. ARE
 THESE INSIDE OR OUTSIDE. PLEASE COORDINATE WITH BASE
 SHELL DESIGNER.
  
 13) NOTE: PLEASE SEE PLAN REVIEW NOTES. MOST OF THE
 NOTES ARE THE SAME AS PREVIOUS REVIEW. PLEASE SEE
 FLORIDA STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR MINIMUM CODE COMPLIANCE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-09 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 09:03 Sent To  
Notes
2008-02-11 09:04:18** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW THE BUILDING IN WHICH THE APPLIED
 SCOPE OF WORK IS BEING APPLIED IS NOT PERMITTED AT THIS
 TIME.
 PLEASE ALSO KNOW ONCE THE SHELL BUILDING IS ISSUED AND
 THE BUILD OUT SCOPE OF WORK IS BEING DONE IN THIS SHELL
 WHICH DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY THE
 BUILD OUT PLANS SHALL CONTAIN A STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD FOR EACH
 TRADE SHEET. THIS BUILDING WOULD STILL BE UNDER THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM AND ANY
 BUILD OUT WORK WOULD NEED TO BE NOTED. THIS STAMP WOULD
 BE A *SHOP DRAWING * REVIEW STAMPED OR OTHER MEANS
 WHICH MAY BE GONE OVER.
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWER(S)
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
 THE BASE BUILDING PERMIT # IS 07100650 WHICH AS OF THIS
 REVIEW ON 2/9/08 HAS COMMENTS TO BE ADDRESSED BEFORE
 ISSUANCE.
  
 2) NOTE: PLEASE CORRELATE ADDRESS OF PROJECT. PLEASE
 SEE THE COVER SHEET OF THE SUBMITTED PLANS CONTAINS
 9847 OKEECHOBEE BLVD, YET THE OTHER TITLE BLOCKS IN
 SETS CONTAIN 4354 OKEECHOBEE BLVD.
 PLEASE COORDINATE.
 FBC 106.1.2, 106.5 ADMIN SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 *FOR COORDINATION AND ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON PLANS.
 2004 FBC W/2007 REVISIONS. (PLANS SHOW 2006 REVISIONS)
 2005 NFPA-70
 2003 NFPA-101
  
 ** THIS IS REQUIRED ON ELECTRICAL SHEETS AS WELL AS
 ARCHITECTURAL COVER PAGE.
 FBC 106.5, 106.1.2
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2
 PLEASE BE AWARE IF THE INTERIOR SCOPE OF WORK IS
 PERMITTED BEFORE C OF O, THE BASE BUILDING METHOD B
 CALCULATIONS WILL BE REQUIRED TO BE REVISED WITH KNOWN
 AS THIS IS CURRENTLY BASED ON ASSUMPTIONS ON SHELL
 PLANS AND CALCULATIONS.
 PLEASE SEE THE METHOD C* FORM SUBMITTED IS NOT
 COMPLETE. THE LIGHTING DENSITIES ARE NOT FILLED OUT AND
 ALL INFORMATION IS MISSING.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR INTERIOR
 AND EXTERIOR LIGHTING. NOT ALL EXTERIOR LIGHTS AS SHOWN
 ON PLANS ARE ON THE SHELL BUILDING PLANS. FOR EXAMPLE
 THE OCTAGONAL NOTE #4 DOES NOT APPLY TO BASE PLANS.
 PLEASE SEE THE FORMS SUBMITTED ARE ALSO PHOTO-COPIES,
 NOT SIGNED, DATED OR SEALED WITH ORIGINAL SIGNATURES AS
 REQUIRED PER FBC 13-103.1.1.1
 FAC 61G15-23.002
 FS 481.221/ 471.025
  
 ** AS LIGHTING PERFORMANCE CALCULATIONS ARE NOT
 COMPLETE OR SUBMITTED NO FULL REVIEW FOR CODE
 COMPLIANCE COULD BE DONE AT THIS TIME. THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 5) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ENGINEERING FIRM ETC ON MECHANICAL,
 PLUMBING AND ELECTRICAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 PLEASE SEE MISSING PRINTED NAME, MISSING PRINTED
 LICENSE NUMBER AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED ON ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 6) NOTE: PLEASE KNOW BASED ON NOTE #4 ABOVE. PLEASE
 KNOW THE INTENT OF THE ENERGY CODE IS TO CONSERVE
 ENERGY. PLEASE SEE 13-415.1.ABC.1 WHICH REQUIRES ALL
 LIGHTING TO BE TURNED OFF WHEN NOT IN USE. THIS AHJ
 DOES NOT HAVE AN ISSUE WITH PERMITTING *NIGHT LIGHTS*
 FOR THE REASON OF LIFE SAFETY OR SECURITY HOWEVER THIS
 IS TO BE TO A MINIMUM OF 1FT CANDLE WHICH THE LIFE
 SAFETY CODE REQUIRES FOR EGRESS UNDER NORMAL AND
 EMERGENCY CONDITIONS ON FLAT WALKING SURFACES.
 (NFPA-101 7.8/7.9
 PLEASE PROVIDE PHOTO-METRICS LEVELS FOR EGRESS PATHS
 UNDER THE NORMAL AND EMERGENCY CONDITIONS FOR THE NIGHT
 LIGHT FIXTURES AE. PLEASE KNOW IF THE LIGHTING LEVELS
 ARE OVER, THEN DESIGN WILL BE REQUIRED TO ADJUSTED.
 PLEASE SEE BOTH CHAPTER 10 OF THE FBC AND LIFE SAFETY
 CODE 7.8.1.2.2ALLOWS THE USE OF OCCUPANCY SENSORS ON
 THESE FIXTURES.
 THE OTHER ALLOWANCE WOULD BE FOR EACH FIXTURE WHICH IS
 3 LAMPS TO REMAIN ON WITH 1-LAMP OR TWO TO MEET THE 1FT
 CANDLE MINIMUM. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3 AS LIGHTING CONTROLS ARE NOT COMPLETE WITH ALL
 LIGHTING ON PLANS.
 FOR EXAMPLE: PLEASE SEE SEPARATE SPACES WHICH REQUIRES
 LIGHTING TO BE ABLE TO OVER RIDE THE LIGHTING CONTROLS,
 AND REQUIRES A MAXIMUM OVER RIDE TIME. PLANS INDICATE A
 MANUAL OVER RIDE HOWEVER DOES NOT INDICATE THE MAXIMUM
 OVER RIDE TIME.
 PLEASE SEE THE SEPARATE SPACES AS BATHROOMS ETC ONLY
 SHOW A STANDARD SWITCH WHICH DOES NOT MEET THESE
 SECTIONS OF THE CODE.
 PLEASE SEE THE REAR OFFICE/WORK ROOM WHICH SHOWS A SR
 YET THE SYMBOL LEGEND DOES NOT CONTAIN THIS DEVICE OR
 INFORMATION ON WHAT TYPE OF DEVICE IT IS?? PLEASE ALSO
 SEE THE OCTAGONAL NOTE #2 WHICH STATES OCCUPANCY SENSOR
 YET COULD NOT LOCATE ANY MAXIMUM TIMES.
 ** PLEASE CALL TO GO OVER IF NEEDED.
  
 7) NOTE: PLEASE SEE 700.12F WHICH REQUIRES EMERGENCY
 AND EXIT LIGHTS TO BE CONNECTED TO THE LOCAL LIGHTING
 BRANCH CIRCUIT. THERE IS EXCEPTIONS FOR MULTIPLE
 CIRCUITS IN UNINTERRUPTED AREAS, HOWEVER PLEASE SEE
 PLANS WHICH SHOW FIXTURES IN OTHER SPACES STILL ON THE
 DEDICATED CIRCUIT WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SEE THAT THE PANEL SCHEDULE CIRCUITS
 SHALL BE SPECIFIC TO CIRCUITS. FOR EXAMPLE: THE SHOW
 WINDOW RECEPTACLES ARE REQUIRED TO BE LABELED AS SUCH.
 MAY NOT LABEL ALL AS *GENERAL LIGHTS* OR GENERAL
 RECEPTACLES*.
 PLEASE SEE 408.4, 210.62.
 FBC 106.3.5.1.2, 106.1.2
  
 9) NOTE: PLEASE SHOW THE LOAD CALCULATIONS BASED ON
 NEC. PLEASE SEE THE SHOW WINDOWS FOR EXAMPLE NEED TO
 SHOW HOW THESE LOADS WERE FIGURED PER 220.43
 PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, 230.42 ETC
  
 10) NOTE: PLEASE SEE OCTAGONAL NOTE #4 AS MENTIONED
 ABOVE FOR LIGHTING PERFORMANCE, HOWEVER PLEASE SEE AS
 THESE ARE NOT PART OF BASE SHELL PLEASE COMPLETE WITH
 FIXTURE INFORMATION AND CONTROL.
 PLANS MENTIONS BACK UP FOR EMERGENCY ILLUMINATION
 HOWEVER NOT CLEAR ON THIS.
 FBC 106.1.2, FOR ADDITIONAL INFORMATION AS WELL AS
 CHAPTER 13 FOR EXTERIOR LIGHTING CONTROLS AND LIGHTING
 PERFORMANCE CALCULATIONS.
 13-415.1.ABC.1.4, 13-415.2 (SECTIONS GIVEN ABOVE).
  
 11) NOTE: PLEASE SEE PLANS APPEAR TO SHOW PANELS
 OUTSIDE. ARE THESE INSIDE OR OUTSIDE. PLEASE COORDINATE
 WITH BASE SHELL DESIGNER.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-8056717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-05 Cont ID  
Sent By mwennerg Date 2008-12-05 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2008-12-05 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-10-24 Cont ID  
Sent By mwennerg Date 2008-10-24 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2008-10-24 Time 11:03 Sent To  
Notes
2008-10-24 11:03:41***DENIED***
  
 ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER
 INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS.
 THE FOLLOWING WAS TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW:
  
 1) PLEASE SEE ELECTRICAL COMMENT REGARDING ADDRESSING
 ON PLANS. ADDITIONALLY, PLEASE INDICATE SUITE NUMBER IF
 APPLICABLE. ADDRESS CHARACTERS TO COMPLY WITH THE CITY
 OF WEST PALM BEACH STANDARDS WITH REGARD TO SIZE AND
 APPEARANCE.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A, B OR C.
  
 3) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By mwennerg Date 2008-09-10 Time 13:15 Rev Time 0.00
Received By mwennerg Date 2008-09-10 Time 13:15 Sent To  
Notes
2008-09-10 13:21:11***DENIED***
  
 ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER
 INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED WOULD HELP EXPEDITE THE PLAN REVIEW PROCESS.
 THE FOLLOWING WAS TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW:
  
 1) PLEASE SEE ELECTRICAL COMMENT REGARDING ADDRESSING
 ON PLANS. ADDITIONALLY, PLEASE INDICATE SUITE NUMBER IF
 APPLICABLE. ADDRESS CHARACTERS TO COMPLY WITH THE CITY
 OF WEST PALM BEACH STANDARDS WITH REGARD TO SIZE AND
 APPEARANCE.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A, B OR C.
  
 3) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By mwennerg Date 2008-03-13 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2008-03-13 Time 15:49 Sent To  
Notes
2008-03-13 15:57:12***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT REGARDING ADDRESSING
 ON PLANS. ADDITIONALLY, PLEASE INDICATE SUITE NUMBER IF
 APPLICABLE. ADDRESS CHARACTERS TO COMPLY WITH THE CITY
 OF WEST PALM BEACH STANDARDS. WITH REGARD TO SIZE AND
 APPEARANCE.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B OR C.
  
 3) A MINIMUM OF (2) EXITS ARE REQUIRED. ALL MEANS OF
 EGRESS TO REMAIN ACCESSIBLE AND FREE OF OBSTRUCTIONS.
 MEANS OF EGRESS TO COMPLY WITH NFPA 101, CHAPTER 7.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 10:47 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 10:47 Sent To E
Notes
2008-12-17 10:48:11TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 14:35 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 14:35 Sent To  
Notes
2008-11-17 14:35:17TO "COMM" BD#17

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-06 Cont ID  
Sent By shill Date 2008-10-06 Time 16:51 Rev Time 0.00
Received By shill Date 2008-10-06 Time 16:51 Sent To  
Notes
2008-10-06 16:54:36TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 10:41 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 10:41 Sent To  
Notes
2008-08-21 10:45:51TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-08-21 Cont ID  
Sent By hmoser Date 2008-03-18 Time 17:33 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 10:52 Sent To  
Notes
2008-02-07 10:56:02TO "COMM" BD#4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-08 Cont ID  
Sent By tgordon Date 2008-10-08 Time 14:01 Rev Time 0.45
Received By tgordon Date 2008-10-08 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-09-08 Cont ID  
Sent By tgordon Date 2008-09-08 Time 09:30 Rev Time 1.30
Received By tgordon Date 2008-09-08 Time 09:30 Sent To  
Notes
2008-09-08 10:09:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) MECHANICAL PLAN M-1 GENERAL NOTES #1 REFERENCES THE
 2006 FLORIDA INTERNATIONAL MECHANICAL CODE, ETC. THE
 STATE OF FLORIDA AND THE CITY OF W. P. B. IS UNDER THE
 2004 FLORIDA BUILDING CODE WITH THE 2007 SUPPLEMENTS.
 PLEASE CORRECT PLAN TO REFLECT THIS.
  
 2) VENTILATION AIR CALCULATIONS NOTE #3 STATES NET
 SQUARE FOOTAGE DOES NOT INCLUDE DISPLAY AREA OR BEDS
 WHICH ARE NOT OCCUPIABLE SPACES. AS THERE IS NO
 PERMANENT STRUCTURE BETWEEN THE SPACES THEN ALL THE
 FLOOR SPACE MUST BE INCLUDED IN THE CALCULATIONS. SEE
 2004 FBC/M TABLE 403.3 FOOT NOTE 'E'. IF YOU CAN
 REFERENCE A FLORIDA BUILDING CODE THAT SUPPORTS YOUR
 CALCULATION PLEASE SUBMIT IT IN DETAIL, BE SPECIFIC
  
 3) SEE BUILDING REVIEW NOTES 3 AD 8, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By hmoser Date 2008-03-18 Time 17:11 Rev Time 0.00
Received By hmoser Date 2008-03-18 Time 17:11 Sent To  
Notes
2008-03-18 17:27:51PLAN DENIED
 1) PLEASE PROVIDE DETALS ON CURB TIEDOWN TO ROOF AND
 AIR CONDITIONING TIEDOWN TO CURB ON THE PLANS.
 2) PLEASE SHOW LOCATION AND TERMINATION OF A/C
 CONDENSATE DRAIN .
 3) PLEASE SUBMIT ENERGY CALCULATIONS WITH THE PLANS.
 4) PLEASE SUBMIT MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE AIR CONDITIONING UNITS WITH THE
 PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-15 Cont ID  
Sent By mperson Date 2008-10-15 Time 14:38 Rev Time 0.30
Received By mperson Date 2008-10-15 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-25 Cont ID  
Sent By mperson Date 2008-08-25 Time 08:52 Rev Time 0.00
Received By mperson Date 2008-08-25 Time 08:52 Sent To  
Notes
2008-08-25 09:30:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WAS NO COMMENT RESPONSE FROM THE
 DESIGNER.
  
 1. NOTE: PLEASE CORRELATE THE CORRECT ADDRESS ON
 RESUBMITTED PLANS. THE COVER SHEET IS INDICATING 9847
 OKEECHOBEE BLVD, HOWEVER SHEETS A-0.1 THRU P-1 ARE
 INDICATING THE ADDRESS AT 4354 OKEECHOBEE BLVD. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 **PREVIOUS COMMENT NOT ADDRESSED. THE RESUBMITTED
 PLANS SHEET P-1 STILL HAS THE WRONG ADDRESS ON IT PER
 THE COVER SHEET. PLEASE CORRELATE AND CORRECT THE
 ADDRESS ON THIS SHEET. PER (W.P.B. AS AMENDED) SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SHEET P-1 IS MISSING REQUIRED INFORMATION ON TITLE
 BLOCK FOR ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 AND FLORIDA STATUTES 471.023.
 NOTE: TITLE BLOCK IS MISSING THE FOLLOWING: PRINTED
 NAME AND PRINTED LICENSE NUMBER OF THE PERSON SIGNING
 AND SEALING SHEET. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER IS MISSING FROM JORDAN & SKALA
 ENGINEERS, INC..
 NOTE:THIS IS REQUIRED ON ALL MEP PLAN SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 **PREVIOUS COMMENT NOT ADDRESSED. RESUBMITTED SHEET
 P-1 IS STILL MISSING THE TITLE BLOCK INFORMATION. TITLE
 BLOCK IS STILL MISSING THE PRINTED NAME AND PRINTED
 LICENSE NUMBER OF THE PERSON SIGNING AND SEALING SHEET.
 ALSO THE CERTIFICATE OF AUTHORIZATION NUMBER IS MISSING
 FROM THE FIRM JORDAN & SKALA ENGINEERS, INC.. PER FAC
 61G15-23.002 AND FS 471.023.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. SHEET P-1, WATER RISER DIAGRAM: THE COLD WATER TO
 THE DRINKING FOUNTAIN IS MISSING. PLEASE ADD THIS ON
 THE RESUBMITTAL. PER FBC PLUMBING, SECTION *601.1 SCOPE
 AND CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.3.5.1.3 PLUMBING (3)(13).
  
 **PREVIOUS COMMENT NOT ADDRESSED. RESUBMITTED SHEET
 P-1 IS STILL MISSING THE COLD WATER TO THE DRINKING
 FOUNTAIN. PER FBC-2004 PLUMBING SECTION 601.1 SCOPE AND
 (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(13).
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 5. ONLY ONE SHEET P-1 WAS IN THE RESUBMITTAL. PER
 (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR PERMIT.
  
 6. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 (4) TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By mperson Date 2008-02-13 Time 16:28 Rev Time 0.00
Received By mperson Date 2008-02-13 Time 10:28 Sent To  
Notes
2008-02-12 16:55:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: PLEASE CORRELATE THE CORRECT ADDRESS ON
 RESUBMITTED PLANS. THE COVER SHEET IS INDICATING 9847
 OKEECHOBEE BLVD, HOWEVER SHEETS A-0.1 THRU P-1 ARE
 INDICATING THE ADDRESS AT 4354 OKEECHOBEE BLVD. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.2
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SHEET P-1 IS MISSING REQUIRED INFORMATION ON TITLE
 BLOCK FOR ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002
 AND FLORIDA STATUTES 471.023.
 NOTE: TITLE BLOCK IS MISSING THE FOLLOWING: PRINTED
 NAME AND PRINTED LICENSE NUMBER OF THE PERSON SIGNING
 AND SEALING SHEET. ALSO THE CERTIFICATE OF
 AUTHORIZATION NUMBER IS MISSING FROM JORDAN & SKALA
 ENGINEERS, INC..
 **THIS IS REQUIRED ON ALL MEP PLAN SHEETS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE REVIEWS.
  
 3. THE WATER HEATER SHALL BE COMPLIANT WITH CHAPTER 13
 ENERGY EFFICIENCY SECTION TABLE 13-612.1.ABC.3.2
 MINIMUM PERFORMANCE STANDARDS WATER HEATING EQUIPMENT
 AND THE HOT WATER PIPE SHALL BE COMPLIANT WITH TABLE
 611.1.ABC.1 MINIMUM PIPE INSULATION.
  
 4. SHEET P-1, WATER RISER DIAGRAM: THE COLD WATER TO
 THE DRINKING FOUNTAIN IS MISSING. PLEASE ADD THIS ON
 THE RESUBMITTAL. PER FBC PLUMBING, SECTION *601.1 SCOPE
 AND CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.3.5.1.3 PLUMBING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-26 Cont ID  
Sent By jroach Date 2008-02-26 Time 09:13 Rev Time 0.00
Received By jroach Date 2008-02-26 Time 09:13 Sent To  
Notes
2008-02-26 09:13:49***ZONING REVIEW NOT REQUIRED....INTERIOR MODIFICATIONS
 ONLY***