Plan Review Details - Permit 08020130
Plan Review Stops For Permit 08020130
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-05-15 Cont ID  
Sent By mperson Date 2008-05-15 Time 13:06 Rev Time 0.00
Received By mperson Date 2008-05-15 Time 13:06 Sent To PC
Notes
2008-05-15 13:07:18NOTE: "OK" DUPLICATE PERMIT WITH TANKLESS WATER HEATER
 SUBMITTAL.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-13 Cont ID  
Sent By mperson Date 2008-02-13 Time 11:13 Rev Time 0.00
Received By mperson Date 2008-02-13 Time 11:13 Sent To PC
Notes
2008-02-13 11:23:13****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 PER FBC FUEL GAS SECTION 404.8 GALVANIZED PIPING
 UNDERGROUND IS UNACCEPTABLE. GALVANIZED PIPING
 INDICATED ON PLANS APPROVED FOR ABOVE GROUND ONLY.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-07 Cont ID  
Sent By mperson Date 2008-02-07 Time 11:36 Rev Time 0.00
Received By mperson Date 2008-02-07 Time 11:36 Sent To PC
Notes
2008-02-07 11:44:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 **THE SUBMITTED ISOMETRIC IS NOT INDICATING THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 REFERENCE THE RED CIRCLED AREAS WITH THE YELLOW HIGH
 LIGHTER OF THE PIPES WITH NO MEASUREMENTS.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **LONGEST LENGTH (RUN) NEEDS TO BE CORRELATED WITH
 COMMENT #1.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-13 Cont ID  
Sent By mperson Date 2008-02-13 Time 11:24 Rev Time 0.00
Received By mperson Date 2008-02-13 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-13 Cont ID  
Sent By mperson Date 2008-02-07 Time 11:45 Rev Time 0.00
Received By mperson Date 2008-02-07 Time 10:20 Sent To  
Notes
2008-02-07 10:20:55TO "G" BOX