Plan Review Details - Permit 08020128
Plan Review Stops For Permit 08020128
Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2009-09-29 Cont ID  
Sent By jwitmer Date 2009-09-29 Time 16:55 Rev Time 0.50
Received By jwitmer Date 2009-09-29 Time 16:55 Sent To  
Notes
2009-09-29 16:56:22BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVISION REVIEW
 ACTION: REVIEWED DATED 9-11-09
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2009-09-15 Cont ID  
Sent By jwitmer Date 2009-09-15 Time 13:02 Rev Time 0.50
Received By jwitmer Date 2009-09-15 Time 13:02 Sent To PC
Notes
2009-09-15 13:04:17BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVISION REVIEW
 ACTION: REVIEWED
 SHEET A020 REVISION DATED 9-04-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2009-08-20 Cont ID  
Sent By jwitmer Date 2009-08-20 Time 13:16 Rev Time 1.22
Received By jwitmer Date 2009-08-20 Time 13:16 Sent To  
Notes
2009-08-20 13:17:40SHOP DRAWINGS FOR PRECAST CONCRETE

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status F Date 2009-08-10 Cont ID  
Sent By jwitmer Date 2009-08-10 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2009-08-10 Time 16:29 Sent To  
Notes
2009-08-10 16:50:34BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 AUGUST 10,2009
 REVIEW : GATES PRECAST CONCRETE PRODUCTS SHOP-DRAWINGS
 ACTION: DENIED
  
  
 1) PLANS SUBMITTED HAVE A RUBBER STAMP SIGNATURE. THERE
 IS NO PRINTED NAME OF THE ENGINEER IN THE TITLE BLOCK
 EITHER.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002, ENGINEERS61G15-23.002(2)
 FL. ADMIN. CODE. PLANS SIGNED & SEALED BY A
 PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: NAME,
 ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, THE NAME
 AND LICENSE NUMBER OF THE ENGINEER AND THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER IS
 PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 NOTE THESE PLANS WILL BE RETAINED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2009-08-10 Cont ID  
Sent By jwitmer Date 2009-08-10 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2009-08-10 Time 16:30 Sent To  
Notes
2009-08-10 16:31:05STRUCTURAL ANALYSIS REPORT MUNTER ROOFTOP AIR HANDLERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2009-08-10 Cont ID  
Sent By jwitmer Date 2009-08-10 Time 16:14 Rev Time 0.75
Received By jwitmer Date 2009-08-10 Time 15:35 Sent To  
Notes
2009-08-10 16:15:25FABCO SHOP DRAWINGS:
 AB1, E1-E28 & E50

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-28 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2009-07-27 Time 14:09 Sent To  
Notes
2009-07-28 09:37:04REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2009-06-17 Cont ID  
Sent By jwitmer Date 2009-06-17 Time 09:30 Rev Time 0.77
Received By jwitmer Date 2009-06-17 Time 08:45 Sent To PC
Notes
2009-06-17 09:30:34BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW: ROOF HATCH
 ACTION: REVIEWED
  
 NYSTROM/ BABCOCK-DAVIS ROOF HATCH MANUFACTURED AT THE
 SAME PLANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2009-06-15 Cont ID  
Sent By jwitmer Date 2009-06-15 Time 12:30 Rev Time 0.55
Received By jwitmer Date 2009-06-15 Time 11:29 Sent To  
Notes
2009-06-15 12:31:39BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW: SUBMITTALS
 ACTION:REVIEWED
  
 REVISED METAL FRAMING DETAILS
 SHORING SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2009-04-21 Cont ID  
Sent By jwitmer Date 2009-04-21 Time 11:51 Rev Time 0.33
Received By jwitmer Date 2009-04-21 Time 11:51 Sent To PC
Notes
2009-04-21 11:54:44BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 STRUCTURAL ANALYSIS REPORT REVIEW
 ACTION: DENIED
  
 1) THE REPORT SUBMITTED IS ONLY THE COVERSHEET OR PAGE
 ONE OF TWELVE PAGES. INCOMPLETE PAPERWORK. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2009-04-21 Cont ID  
Sent By jwitmer Date 2009-04-21 Time 11:39 Rev Time 0.77
Received By jwitmer Date 2009-04-21 Time 11:39 Sent To  
Notes
2009-04-21 11:41:28BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 SUBMITTAL:ENGINEERED SHORING DRAWINGS REVIEW
 ACTION: REVIEWED
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2009-04-21 Cont ID  
Sent By jwitmer Date 2009-04-21 Time 11:24 Rev Time 0.77
Received By jwitmer Date 2009-04-21 Time 11:24 Sent To PC
Notes
2009-04-21 11:30:28BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 HILTI FIRESTOPPING SUBMITTAL REVIEW
 ACTION: REVIEWED/ PROVISO
  
 NOTE PER THRESHOLD/ SPECIAL INSPCTOR GUIDELINES COMMENT
 # 26; ASSURE THAT THE DESIGNER HAS REQUIRED ON THE
 PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED FORTHE
 FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2009-04-13 Cont ID  
Sent By jwitmer Date 2009-04-13 Time 10:47 Rev Time 0.77
Received By jwitmer Date 2009-04-13 Time 10:47 Sent To PC
Notes
2009-04-13 10:55:52BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 SHOP DRAWING REVIEW:
 08020128
 ACTION:REVIEWED/ PROVISO
  
 1)EXTERIOR METAL STUD FRAMING DETAIL: FRAMING DETAILS
 AS FAR AS THE FRAMING OK, AGAIN
 THE USE IN EXTERIOR GRADE PLYWOOD IS TO BE LIMITED TO:
  
 BUILDING PROVISO:
 1A) 603.1(1) (1.2) NONBEARING EXTERIOR WALLS WHERE NO
 FIRE RATING IS REQUIRED &
 1B) TABLE 602 FOR FIRE RATING OF EXTERIOR WALLS BASED
 ON FIRE SEPERAATION DISTANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM L
 OCAL OFFICIALS REGARDING CITY BUSINESS ARE PUBLIC
 RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2009-04-13 Cont ID  
Sent By jwitmer Date 2009-04-13 Time 10:43 Rev Time 0.77
Received By jwitmer Date 2009-04-13 Time 10:43 Sent To PC
Notes
2009-04-13 10:47:37BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 SUBMITTAL REVIEW:
 ACTION: REVIEWED
 DESIGN CRITERIA: THOMAS KELAHER P. E. STRUCTURAL
 CONSULTANT
 SHOP DRAWING STAMP BY TRC WORLDWIDE ENGINEERING
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2009-04-09 Cont ID  
Sent By jwitmer Date 2009-04-09 Time 14:45 Rev Time 0.33
Received By jwitmer Date 2009-04-09 Time 14:45 Sent To PC
Notes
2009-04-09 14:52:44BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 SHOP DRAWING REVIEW
 ACTION: DENIED
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2009-04-01 Cont ID  
Sent By jwitmer Date 2009-04-01 Time 15:41 Rev Time 0.77
Received By jwitmer Date 2009-04-01 Time 15:41 Sent To  
Notes
2009-04-01 15:50:07BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 SUBMITTAL REVIEW
 ACTION: REVIEWED
 CONCRETE MIX DESIGN
 EPOXY & GROUT SUBMITTALS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2009-04-01 Cont ID  
Sent By jwitmer Date 2009-04-01 Time 15:23 Rev Time 0.22
Received By jwitmer Date 2009-04-01 Time 15:23 Sent To  
Notes
2009-04-01 15:27:19BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 SUBMITTAL REVIEW
  
 ACTION: DENIED
  
 1) SUBMITTALS FOR IRRIGATION SYSTEM NOT REVIEWED,
 PLEASE SUBMIT FOR A IRRIGATION PERMIT. THIS IS A
 SEPERATE PERMIT, WITH ASSOCIATED REVIEWS AND FEES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2009-03-17 Time 13:35 Sent To  
Notes
2009-03-17 13:51:21BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW PANEL WIND LOAD CALCS FOR HEATCRAFT
 REFRIGERATION PRODUCTS,
 HCU, EXTENDED HCU AND HTS UNITS, NTC WIND RESISTANCE
 MODEL
 AND LSERIES UNITS
  
  
 ACTION: REVIEWED
2009-03-17 13:48:59BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW: WALKER ENG. WIND ANALYSIS FOR ROOFTOP EQUIPMENT
 ENCLOSURE
 ACTION: REVIEWED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 13:21 Rev Time 0.55
Received By jwitmer Date 2009-03-17 Time 13:21 Sent To PC
Notes
2009-03-17 13:26:28BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW DESIGN CRITERIA TARGET# T-2427
 ACTION: DENIED
  
 1) TRC WORLDWIDE ENGINEERING INC. SHOP DRAWING REVIEW
 STAMP IS STAMPED DIRECTLY OVER THE DESIGN WIND DESIGN
 CRITERIA, NOT LEGIBLE.
 (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE & EXTENT OF
 THE WORK PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM
 TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT
 INFORMATION ON THE COVER SHEET OR INDEX.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC
 RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST. YOUR
 E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO PUBLIC
 DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 13:15 Rev Time 0.22
Received By jwitmer Date 2009-03-17 Time 13:15 Sent To PC
Notes
2009-03-17 13:19:28BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW SIGNED AND SEALED ENGINEERED EDC SHORING DESIGN
 ACTION: DENIED
  
 1) 2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE & EXTENT OF
 THE WORK PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM
 TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 PLANS ARE SHRUNK AND NOT LEGIBLE FOR ELECTRONIC COPYING
 INTO RECORD RETENSION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 11:20 Rev Time 2.22
Received By jwitmer Date 2009-03-17 Time 11:20 Sent To  
Notes
2009-03-17 12:01:08BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 MARCH 17, 2009
 REVIEW EXTERIOR METAL STUD FRAMING DETAILS
 ACTION: DENIED
  
 1) MOST EXTERIOR DETAILS INDICATE USE OF GYPSUM
 SHEATHING IN THE DETAIL SHEET BUT WITHIN THE DETAIL
 SHEET THEY INDICATE SEE 1/SK-3.0 WHICH IS RED LINED 5/8
 PLYWOOD PANEL NOT THE GYPSUM SHEATHING AS INDICATED ON
 THE DETAIL SHEETS. PLEASE REVIEW SECTION 603.1 AND
 TABLE 601& 602 WHERE FIRE RETARDANT TREATED PLYWOOD CAN
 BE USED.
  
 2) THE EXTERIOR METAL STUD FRAMING DETAILS ALSO ARE
 MISSING THE WIND DESIGN CRITERIA THEY WERE DESIGNED
 TOO!
  
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 09:31 Rev Time 0.33
Received By jwitmer Date 2009-03-17 Time 09:31 Sent To PC
Notes
2009-03-17 09:35:14BUILDING PLAN REVIEW
 PERMIT: 08020128 MASTER PERMIT
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 REVIEW: CONCRETE SHORING AND FORMING DETAIL
 ACTION: DENIED
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-03-17 Cont ID  
Sent By jwitmer Date 2009-03-17 Time 08:29 Rev Time 3.00
Received By jwitmer Date 2009-03-17 Time 08:29 Sent To PC
Notes
2009-03-17 08:37:18BUILDING PLAN REVIEW
 PERMIT: 08020128 MASTER PERMIT
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 REVIEW: ROOFING PRODUCT APPROVALS & REVISION 1/16/09
 ACTION: REVIEWED
  
 1) NOTE THIS IS A REVISION UNDER THE MASTER PERMIT
 NUMBER, AT THIS TIME THERE HAS BEEN NO ROOFING
 CONTRACTOR APPLY FOR A ROOFING PERMIT.
  
 2004-FL# 9274-R1
 MANUFACTURER: SIKA SARNAFIL
 TABLE 2C-1 SYSTEM TYPE D
 SYSTEM # S-44
 ASCE 7-02
 ZONE 1 71PSF
 ZONE 2 108PSF
 ZONE 3 153 PSF
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-03-12 Cont ID  
Sent By jwitmer Date 2009-03-12 Time 15:49 Rev Time 1.55
Received By jwitmer Date 2009-03-12 Time 15:49 Sent To  
Notes
2009-03-12 15:53:28SHOP DRAWINGS FOR VISTAWALL ARCHITECTURAL PRODUCT
 "HR"251DG
 FL ST APPROVAL# 7129
 ALUMINUM WINDOW WALL LMI NOA 04-0308.02
  
 AUTOMATIC SLIDDING DOOR DURA-STORM 3000/ IMPACT
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-02-10 Cont ID  
Sent By jwitmer Date 2009-02-10 Time 12:39 Rev Time 1.55
Received By jwitmer Date 2009-02-10 Time 12:39 Sent To  
Notes
2009-02-10 12:41:12 
 BUILDING PLAN REVIEW
 PERMIT: 08020128
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW: ROOFING PRODUCT APPROVALS
 ACTION: DENIED
  
 1) NOTE THIS IS A REVISION UNDER THE MASTER PERMIT
 NUMBER, AT THIS TIME THERE HAS BEEN NO ROOFING
 CONTRACTOR APPLY FOR A ROOFING PERMIT.
  
 THE FOLLOWING COMMENTS ARE COPIED FROM A E-MAIL SENT TO
 BRETT NANSEN ABOUT THE ROOFING REVISIONS SUBMITTED
 WITHIN THE LAST ROUND OF REVISIONS.
  
 GOOD MORNING BRETT,
  
 I'VE BEEN REVIEWING YOUR REVISIONS (ARCHITECTURAL &
 STRUCTURAL) FOR THE TARGET STORE LOCATED AT 1760 PALM
 BEACH LAKES BLVD. AS FAR AS THE ROOFING REVISION
 SUBMITTED I DO HAVE A FEW ISSUES.
  
 YES, THE DESIGNER OF RECORD DOES NEED TO REVIEW ALL
 DOCUMENTS THAT PERTAIN TO THEIR DESIGN, COMPONENTS AND
 CLADDING. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 ON THE ARCHITECTURAL SHEET A001 YOU INDICATE REVISED
 PRODUCT APPROVALS, THIS IS A PROVISO, SINCE ALL PRODUCT
 APPROVALS WILL NEED TO BE REVIEWED ON AN INDIVIDUAL
 BASES. FOR EXAMPLE, FOR THE ROOF YOU HAVE SUBMITTED
 SIKASARNAFIL, INC. WITHTWO INDIVIDUAL REPORTS ONE A FL
 9274-R1 AND A SECOND A MIAMI-DADE NOA 07-0614.04. WE
 WILL ACCEPTEITHER REPORT BUT THE CONFUSION IS WHEN ON
 SHEET A001 THE REFERENCED SUB-SYSTEM IS FOUND IN THE
 MIAIMI- DADE NOAPAGE 22-23 SYSTEM(D-8) PATTERN # 2WHICH
 DOES HAVE THE SAME PRESSURES AS THE FLORIDA REPORT
 9274.1TABLE 2C-1 SYSTEM D S-44.THE DIFFERENCE BETWEEN
 THE TWO REPORTS ARE THE THIS MAY OR MAY NOT BE A
 FACTOR. ITMAY DEPEND ON THE INSULATION FACTOR. THE
 ENHANCED FASTENING BY C-BUCK ENGINEERING REFERENCES THE
 FL REPORT 9274.1 WITHIN THE DOCUMENT. WHICH REPORT
 WOULD YOU WANT US TO USE?
  
 IN NEITHER CASE DOES THE REPORT INDICATE WHICH TYPE OF
 INSULATION THAT CAN BE USED . THE FL.REPORT 9742.1
 UNDER INSULATION BOARD INDICATES TO ATTACH PER NOA. THE
 FL 9742.1 SUB-SYSTEM S-44 INDICATES ONE OR MORE LAYERS
 ANY COMBINATION, ATTACHMENT IS PRELIMINARILY ATTACHED,
 THE FIRST PAGE DOES LIST PRODUCTS THAT COULD BE
 INSTALLED. THE MIAMI-DADE REPORT UNDER THE FRONT
 HEADING OF COMPONENTS LIST ALL INSULATION SYSTEMS THAT
 CAN BE INSTALLED UNDER THE MIAIMI-DADE NOA. NO
 INFORMATION HAS BEEN SUBMITTED AT THIS TIME.
  
 THE REASON WE REQUEST A INSULATION SHOP DRAWING IS THAT
 THE MINIMUM AMOUNT OF INSULATION WILL BE AT THE ROOF
 DRAINS. THE NEW ENERGY INPUT DATA REPORT INDICATES THE
 R-VALUE OF 17.4. THE DESIGNER OF RECORD WOULD NEED TO
 PICK OUT THE INSULATION TYPE OR HAVE THE ROOFER PICK
 OUT THE TYPE OF INSULATION THAT WILL MEET THIS
 CRITERIA. THEN FROM THE ROOF DRAINS THE INSULATION WILL
 TAPER UP TO THE PARAPET WALLS AT A RATE REQUIRED BY
 CODE. THE ONE ISSUE WE HAVE SEEN WITH THIS SHOP DRAWING
 REVIEW IS THAT THE INSULATION MAY BECOME SO THICK THAT
 THE FASTENERS WILL NOT REACH THROUGH TO THE METAL DECK,
 THUS NEEDING TO CREATE MORE ROOF DRAINS.
  
 AT THIS TIME I BELIEVE THERE IS STILL ALLOT OF
 UNANSWERED QUESTIONS ABOUT THE ROOFING SYSTEM, DEPTH OF
 INSULATION REQUIRED AND THE ROOFING PACKAGE NOT BEING
 REVIEWED BY THE DESIGN PROFESSIONAL.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-02-10 Cont ID  
Sent By jwitmer Date 2009-02-10 Time 12:39 Rev Time 7.55
Received By jwitmer Date 2009-02-09 Time 07:45 Sent To  
Notes
2009-02-10 13:32:18BUILDING PLAN REVIEW
 PERMIT: 08020128
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVISION REVIEW
 ACTION:REVIEWED-OK
 SHEETS & REVISION NUMBER/ DATE
  
 A001 REV# 2 9-08-08
 PROVISO: HEADING PRODUCT APPROVALS:
 140 MPH/ 3 SECOND GUST
 INDIVIDUAL PRODUCT APPROVALS TO BE REVIEWED SEPERATELY
 A020 REV BID 7-31-08
 A021 REV# 2 9-08-08
 A110 REV# 3
 A121 REV#32 1-21-09
 A125 REV# 13/32 10-16-08/ 1-21-09
 A30 REV# BID 7-31-08
 A131 REV#32 1-21-09
 A141 REV# 32 1-21-09
 A151 REV# 21 11-21-08
 A152 REV# 30 11-19-08
 A161 REV# 33 1-16-09
 A201 REV# 1 8-21-08
 A211 REV# 22 11-21-08
 A212 REV# 22 11-21-09
 A213 REV# 22 11-21-09
 A214 REV# 22 11-21-08
 A215 REV#22 11-21-08
 A216 REV# 22 11-21-08
 A217 REV#1 8-28-08
 A231 REV#16
 A300 REV#15 11-15-08
 A301 REV# 29 1-08-09
 A302 REV#28 10-29-08/ REV#29 1-08-09
 A303 REV#8 10-29-08
 A305 REV#15 11-07-08
 A311 REV# 16 11-14-08
 A312 REV#18 11-14-08
 A313 REV# 9 10-09-08 REV 17 11-13-08
 A321 REV# 18 11-14-08
 A331 REV# 2 9-08-08
 A351 REV# 32 1-21-09
 A352 REV#32 1-21-09
 A361 REV 30-32 1-09-09/ 1/21/09
 A502 REV# 13 10-16-08 REV# 16 11-14-08
 A601
 A611
 A621
 A622
 A701
 A702 REV#19 11-18-08
 A801 REV# 1 8-24-08 REV# 16 11-14-08
 A851 REV# 6 9-12-08
 A891 REV# 15 11-07-08
 A892 REV# 15 11-07-08
 A893 REV#15 11-07-08
  
 S110 REV#16 12-15-08 REV# 32 1-21-09
 S111
 S141 REV#16 12-15-08 REV# 32 1-21-09
 S211 REV#16 12-15-08
 S212 REV#16 12-15-08
 S311
 S321 REV# 16 12-15-08
 S361 REV# 26 1-09-09
 S501 REV# 16 12-15-08
 S521 REV# 16 12-15-08
 S522 REV# 16 S522
 S531 REV#16 12-15-08
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-01-08 Cont ID  
Sent By jwitmer Date 2009-01-08 Time 14:22 Rev Time 1.33
Received By jwitmer Date 2009-01-08 Time 14:22 Sent To PC
Notes
2009-01-08 16:57:34BUILDING PLAN REVIEW
 PERMIT: 08020128
 ADD: 1760 PALM BEACH LAKES BLVD
 CONT: RYAN CO.
 TEL: (813)267-3281
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTALS REVIEW:PANEL WIND LOAD CALCULATIONS
 PREPARED BY BLANEY ENGINEERING INC.
 ACTION: DENIED
  
 1) THE DOCUMENT SUBMITTED BLANEY ENGINEERING HAS BEEN
 SUBMITTED ON A FEW PROJECTS AND DENIED IN ALL
 CASES.SHEET # 6 OF THIS DOCUMENT INDICATES THE SAFE
 ALLOWABLE LOADS THAT CAN BE APPLIED TO THIS FASTENER.
 SHEET # 4 IS REDUCING THE SAFETY FACTOR OF THE FASTENER
 ITSELI.
  
 1A)NOTE # 6 FROM THE STEEL STUD MANUFACTURERS
 ASSOCIATION PRODUCT TECHNICAL INFORMATION PACKET
 INDICATES, APPLIED LOADS MAY BE MULTIPLIED BY 0.75 FOR
 WIND LOADING PER AISI A 5.1.3.
 2004 FBC 1605.3.1.1 ALSO REQUIRES THE LOAD REDUCTIONS:
 605.3.1.1 LOAD REDUCTION.
 1. IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT OF
 TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE EFFECT
 OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN SHALL
 NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD LOAD AND
 ANY OF THE VARIABLE LOADS.
 2. INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1. DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23.
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3. SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 1B) BEFORE THE 2004 FBC THE CODE ALLOWED A 1 1/3RD
 INCREASE IN FASTENERS. CURRENTLY ALL PRODUCT APPROVALS
 BEFORE THE 2004 FBC WENT INTO EFFECT THEY HAVE TO BE
 RE-EVALUATED TO THE 2004 FBC OR HAVE A FLORIDA PE
 RECALCULATE THE FASTENER STRENGTH.
  
 1C) IN REVIEWING COMPARIBLE FASTENERS CLARK AND WESTERN
 HAVE VALUES OF 177 LBS FOR SHEAR AND 84 LBS FOR TENSION
 # 10 SCREW 33 MILS/ FY (KSI) 33
 DIETRICH VALUES OF 151 LBS FOR SHEAR AND 75 LBS FOR
 TENSION # 10 SCREW 33 MILD/ FY (KSI) 33
  
 1D) SSMA SCREW TABLE NOTES# 4, SCREW STRENGTH NEEDS TO
 BE VERIFIED BY THE SCREW MANUFACTER. WE HAVE FOUND SOME
 OF THE TIMES THE FASTENERS ARE IMPORTS AND TESTING HAS
 NOT BEEN COMPLETED
 BECAUSE OF INCONSISTEANCEY OF THE YIELD STRENGHT OF THE
 METALS OR ALLOYS.PLEASE PROVIDE THE ACTUAL SCREW
 MANUFACTURERS VALUES FOR SHEAR AND TENSION.
  
 1E) BLANEY ENGINEERING HAS BEEN CONTACTED BY THIS
 OFFICE BY SAMANTHA HILL AND IS AWARE THAT THE VALUES OF
 THE FASTENERS WILL NEED TO BE THE MANUFACTURERS VALUES,
 THAT YOU DO NOT INCREASE BUT DECREASE VALUES BECAUSSE
 OF COMBINED LOADING OF VERTICAL LOADS, GRAVIRTY LOADS
 AND HORIZONTAL LOADING THAT MAY OCCUR AT THE SAME TIME.
  
 WALKER ENGINEERINGPAGE 6 OF 31
  
 2) PLEASE PROVIDE WHERE THE VALUES FOUND ON PAGE 6
 SCREW ALLOWABLE PULLOUT WAS DERIVED FROM. THERE IS
 ASSUMPTION OR UNKNOWNS THAT DO MAKE A DIFFERENCE ON THE
 VALUES PRESENTED OR THAT WERE NOT STATED.
  
 2A) THE BASE METAL THICKNESS (GAUGE) THE FIRST UNKNOWN
 IS WHAT TYPE OF METAL ARE WE WORKING WITH FOR THE BASE
 METAL, STEEL, GALVENIZED STEEL, STAINLESS, ETC AND ON
 THE VALUES OF FY/ FU.
  
 2B) AS STATED ABOVE IN THE FIRST SECTION THE ALLOWABLE
 WORKING STRENGTH OF THE MATEIALS TO BE FATTACHED
 TOGETHER AND THE SCREW TO SEE WHAT IS THE WEAKEST VALUE
 THAT CAN BE USED, SINCE THIS WILL BE THE FAILURE POINT.
  
 3) UNDER THE WALKER ENGINEERING REPORT PAGE 2 THE
 DOCUMENT REFERENCES THE 2007 FBC, THIS IS INCORRECT,
 SHOULD READ THE 2004 FBC WITH 2007 SUPPLEMENTS.
  
 4) WALKER ENGINEERING REPORT PAGE2 ASCE 7-05 IS
 REFRENCED THE 2004 FBC CHAPTER 35 ONLY REFRENCES THE
 ASCE 7-02 VERSION PLEASE CORRECT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-10 Cont ID  
Sent By jwitmer Date 2008-09-10 Time 10:03 Rev Time 3.33
Received By jwitmer Date 2008-09-10 Time 10:03 Sent To  
Notes
2008-09-10 10:05:12BUILDING PLAN REVIEW
 PERMIT: 08020128
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPT. 10/08
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
  
 ACTION: REVIEWED
  
 1)PROVISO: SUBMITTED WERE TWO TYPES OF FLOOR EXSPANSION
 JOINT MATERIALS, IN ONE CASE THE SINCE THE HFXR-1-1
 SYSTEM DOES INDICATE THAT THE FIRE BARRIER IS OPTIONAL,
 SHOP DRAWINGS ARE TO BE REVIEWED BY THE DESIGN TEAM
 BEFORE SUBMITTED TO THE BUILDING DEPARTMENT, SINCE THE
 CUT SHEETS PROVIDED DO NOT INDICATE THE REQUIRED FIRE
 BARRIER SYSTEM TO TIE WITH THIS PRODUCT.
 THE SECOND PRODUCT SUBMITTED WAS MM PYRO-FLEX/ PF
 SERIES AGAIN THERE IS NO INFORMATION AS TO THE REQUIRED
 THICKNESS OF THIS PRODUCT OR THE HOURLY RATING OF THE
 PRODUCT, THE DESIGN TEAM BEFORE SUBMITTED TO THE
 BUILDING DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO
 NOT INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE
 WITH THIS PRODUCT.
  
 2) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS
 BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES
 THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS
 OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE
 THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-11 Cont ID  
Sent By jwitmer Date 2008-08-11 Time 13:41 Rev Time 15.00
Received By jwitmer Date 2008-08-07 Time 13:41 Sent To  
Notes
2008-08-07 13:46:10BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 3RD REVIEW 08-07-08
 ACTION: DENIED
  
 1-4) COMPLIED.
  
 5) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8-10) COMPLIED.
  
 11)INFORMATIONAL ONLY, PLEASE REVIEW SHEET A021 EXIT
 ANALYSIS, SALES AREA PER SQ FT/ OCC. THIS IS THE 2ND
 FLOOR WHICH IS NOT CONSIDERED THE GRADE FLOOR. THE
 OCCUPANT LOAD FOR THIS FLOORS SALES AREA WOULD BE
 FIGURED AT 60 FT / OCCUPANT NOT THE 30 AS INDICATED IN
 THE TABLE SEE TABLE 1004.1.2.PLAN NOTES HAVE BEEN ADDED
 TO THE EXIT STAIRWAY SCHEDULE.
  
 11A) COMPLIED.
  
 11B) 08-11-08 COMPLIED.
  
 11C-11K) COMPLIED.
  
 12A)PROVISO: SUBMITTED WERE TWO TYPES OF FLOOR
 EXSPANSION JOINT MATERIALS, IN ONE CASE THE SINCE THE
 HFXR-1-1 SYSTEM DOES INDICATE THAT THE FIRE BARRIER IS
 OPTIONAL, SHOP DRAWINGS ARE TO BE REVIEWED BY THE
 DESIGN TEAM BEFORE SUBMITTED TO THE BUILDING
 DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO NOT
 INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE WITH
 THIS PRODUCT.
 THE SECOND PRODUCT SUBMITTED WAS MM PYRO-FLEX/ PF
 SERIES AGAIN THERE IS NO INFORMATION AS TO THE REQUIRED
 THICKNESS OF THIS PRODUCT OR THE HOURLY RATING OF THE
 PRODUCT, THE DESIGN TEAM BEFORE SUBMITTED TO THE
 BUILDING DEPARTMENT, SINCE THE CUT SHEETS PROVIDED DO
 NOT INDICATE THE REQUIRED FIRE BARRIER SYSTEM TO TIE
 WITH THIS PRODUCT.
  
 13) 08-11-08 COMPLIED.
 14-19) COMPLIED.
  
 20) COMPLIED.
  
 21A) 08-11-08 COMPLIED.
  
 21B-C) 11-08-08 COMPLIED.T
  
 22-30) COMPLIED.
  
 31) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS
 BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES
 THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS
 OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE
 THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-24 Cont ID  
Sent By jwitmer Date 2008-06-24 Time 14:03 Rev Time 8.88
Received By jwitmer Date 2008-06-24 Time 14:03 Sent To  
Notes
2008-06-24 15:00:55BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 2NDREVIEW 6-24-08
 ACTION: DENIED
  
 1A)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL, FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE CORRECT
 SHEET G001 BUILDINGCODE INFORMATION.
 BUILDING ALLOWABLE FLOOR AREA- IS INDICATED AS
 UNLIMITED, NOTE S-2 PORTION OF THE BUILDING DOES HAVE
 AREA LIITATIONS TABLE 503.
  
 PLEASE NOTE THAT IF A PERMIT APPLICATION WILL NEED TO
 BE APPLIED FOR BEFORE DEC. 31, 2008 TO LOCK THIS
 PROJECT IN UNDER THE 2004 FBC. ON JAN.1, 2009 THE 2007
 FBC WILL GO INTO AFFECT.
  
 2) 2ND REQUEST, AT THIS TIME WE HAVE NOT SEEN ANY
 APPLICATION FOR A RESIDENT INSPECTOR. FBC* 109.3.7
 RESIDENT INSPECTOR. SUBMIT INSPECTOR RESUME' AND
 LICENSE DOCUMENTS TO KEN CONRAD , DIRECTOR OF THE
 RESIDENT INSPECTOR PROGRAM. 805-6711 OR 805-3749.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 XXX -BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE STRENGTH (F'C)
 IN EXCESS OF 3000 PSI
 - PILE DRIVING
 XXX - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 3) FBC* 109.3.7 SINCE A RESIDENT INSPECTOR WILL
 REQUIRED, THREE OF ALL DOCUMENTS (PLANS, REPORTS,
 SUBMITTALS AND PRODUCT APPROVALS) WILL BE REQUIRED FOR
 ISSUANCE OF THE PERMIT.
  
 4) NOTE THERE HAVE BEEN (2) SUBMITIONS OF SOILS REPORTS
 TO THIS OFFICE, MAY 29TH 3 SETS OF COPIED SIGNATURES OF
 THE ENGINNEER WERE SUBMITTED, THE SECOND SET DATED JUNE
 22, 2008 WERE SUBMITTED TO THIS OFFICE AGAIN
 PHOTO-COPIED SIGNATURES WITH A RAISED SEAL WERE
 SUBMITTED TO THIS OFFICE.
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 SOILS REPORTS PLEASE SUBMIT THREE REPORTS WITH ORIGINAL
 SIGNATURES, NOT COPIES OR STAMPED SIGNATURES.1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 ALLOF THE SUBMITTED SOILS REPORTS ARE GOING TO BE
 RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA ENGINEERS'
 BOARD.
  
 5)BUILDING PROVISO:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00.IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8A)SEECOMMENT 1-E .
  
 8B-C) COMPLIED.
  
 9-10) COMPLIED.
  
 11) PLEASE REVIEWSHEET A021 EXIT ANALYSIS, SALES AREA
 PERSQ FT/ OCC. THIS IS THE 2ND FLOOR WHICH IS NOT
 CONSIDERED THE GRADE FLOOR. THE OCCUPANT LOAD FOR THIS
 FLOORS SALES AREA WOULD BE FIGURED AT60 FT / OCCUPANT
 NOT THE 30 AS INDICATED IN THE TABLE SEE TABLE
 1004.1.2.
  
 11A) COMPLIED.
  
 11B) SEMI-COMPLIED.AS DISCUSSED IN OUR MEETING WITH
 THE TARGET DESIGN TEAM WE CONCUR THAT STAIRA IS NOT
 PART OF THE REQUIRED EGRESS STAIRS BUT IF THIS IS TO BE
 THE CASE PLEASE SEE A021 THAT DOES HAVE TRAVEL
 DISTANCES MARKED WITH AN ARROW DIRECTLY DOWN THESE
 STAIRS. 707.2, EXCEPTION 2.
  
 11C-11K) COMPLIED.
  
 12A)PROVISO: PLEASE PROVIDE CUT SHEET OF ASTM E1966
 ASSEMBLY. NUMBER.A021 REFERS TO DETAIL#2 SHEETA331
 THIS SECTION OR DETAIL REFERENCES DETAIL 20 ON SHEET
 A231. IT APPEARS TO BE AN EXPANSION JOINT IN THE FLOOR
 BUT THERE IS NO INFORMATION THAT I CAN FIND ON THE
 FIREPROOFING REQUIREMENTS TABLE 601 FOR FLOOR SYSTEMS
 AND OCCUPANCY TYPE SEPARATION TABLE 302.3.2.PLEASE
 PROVIDE FLOOR CEILING TYPE PENETRATIONS FOR PIPES AND
 CONDUITS AS WELL AS FOR ANY HORIZONTAL PENETRATION OF
 RATED FLOOR/ CEILING ASSEMBLY.
 SEE 711.3.& 712.3.1.
  
 12B)COMPLIED.
  
 13) 2ND REQUEST, THE RESPONSE INDICATES COMPLIANCE ON
 CIVIL PLANS , PLEASE PROVIDE THE PLANS FOR REVIEW.
 SHEETA110 INDICATES THE DISABLED PARKING SPACES AND
 ACCESS AISLES BUT NOT THE ELEVATION CHANGES OF THE
 PARKING LOT VERSES DISABLED SPACES AND ACCESS AISLES.
 THE OTHER ISSUE IS NO INFORMATION FOR DETECTABLE
 WARNING AT HAZARDOUS VEHICULAR AREAS 11-4.29.5.
  
 14) SHEET A110 :
 A-C)COMPLIED.
 D) NEW COMMENT: THIS SHEET INDICATES MULTIPLE AREAS
 WHERE CURB CUTS ARE INDICATED, PLEASE COMPLY WITH
 11-4.7.5 FLARED SIDES.
 E) NEW COMMENT: GRID LINE 8 AT B/C THIS HANDICAPPED
 PARKING SPACE IS MISSING THE ACCESS AISLE11-4.6.3.
  
 15-19) COMPLIED.
  
 20)2ND REQUEST, SHEET A351 & A352 BOTH INDICATE AN
 ELECTRICAL DISTRIBUTION CENTER THAT DOES NOT HAVE A
 CODE COMPLIANT STAIR. THE CODE DOES ALLOW FOR FIXED
 LADDERS AS PART OF A MEANS OF EGRESS IN THE FOLLOWING
 LOCATIONS:FOR BOILERS (1014.3), REFRIGERATION ROOM
 (1014.4), STAGE EXITS 410.5.4, 1014.6.6.1 GALLERY,
 GRIDIRONS AND CATWALKS THAT ARE ASSOCIATED WITH STAGES
 AND HELISTOPS (1018.1.2.). PLEASE PROVIDE A CODE
 COMPLIANT STAIRWAY.THE PLANS WILL MEET THE EXCEPTION
 UNDER 1009.3 INDUSTRIAL EQUIPMENT ACCESS STAIRS. PLEASE
 PROVIDE THE WIDTH OF THE STAIRS, TREAD AND RISERS.
  
 21) 2ND REQUESTPLEASE PROVIDE ADDITIONAL INFORMATION
 ON THE ELECTRICAL DISTRIBUTION CENTER,
 PRE-MANUFACTURED? TYPE OF MATERIAL, FIRE RATINGS ETC?
 NFPA 13.8.14.10. THE STAIR WALL THAT LEADS TO THE EDC
 ARE INDICATED AS 2HR WALLS. THE WALLS DO NOT CONTINUE
 TO ENCLOSE THE STAIR LANDING WHICH WOULD BE WHAT
 SUROUNDS THE EDC. HOW DOES THIS MAKE A STAIRWELL
 ENCLOSURE WITH A 2 HR RATING?
 THE COMMENT# 24 WILL ILLUSTRATE THE 2 HR WALL RATING
 REQUIRED AROUND THE EMERGENCY EQUIREMENT ROOM ONLY.
  
 22-23) COMPLIED.
  
 24) SHEET A351,A361 & ELECTRICAL CUT SHEETS FROM
 MITSUBISHI ELECTRIC, THEMAIN ELECTRIC CENTER ROOM 129
 & 137, PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 ELECTRICAL DISTRIBUTION CENTER THAT IS INDICATED TO BE
 PRE-MANUFACTURED. TYPE OF MATERIAL, FIRE RATINGS ETC?
 NFPA 13.8.14.10. THE CUT SHEETS DO NOT PROVIDE HOW THE
 HOUR RATING IS ACHIEVED OR WHAT MATERIALS EITHER OF THE
 EDCS ARE
 CONSTRUCTED OF? PLEASE PROVIDE RATING OF THE DOORS FOR
 BOTH 129 AND 137. NOTE IN UNIT 137 THE EMERGENCY
 EQUIPMENT ROOM WILL ALSO REQUIRE A 2HR RATING FROM THE
 REST OF THE ENCLOSURE. THERE CAN BE
 NO REDUCTION FOR FIRE SPRINKLERS, PLEASE SEE NFPA 110
 7.2.1.1, ALSO SEE ELECTRICAL COMMENTS. PLEASE PROVIDE A
 COPY OF THE UL RATING U415 SYSTEM F/ 2006 UL DIRECTORY,
 WE DO NOT HAVE UP TO DATE
 UL LISTING BOOKS TO VERIFY DETAIL 5/ A351.
  
 25-27) COMPLIED.
  
 28) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 3COPIES IF THRESHOLD OR RESIDENT INSPECTOR OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
  
 28A) WINDOWS: CURTAIN-WALL - COMPLIED.
  
 28B) WINDOWS: STOREFRONT- 2ND REQUEST,
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0308.02 ANCHOR CALCULATIONS
 THIS REVISION ON 04/13/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28C1) AUTOMATIC BYPASS DOOR NOA03-0605.03
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 03-0605.03 ANCHOR CALCULATIONS
 THIS REVISION ON 10/31/03 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28C2) AUTOMATIC SLIDING DOORS NOA 04-1026.02
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-1026.02ANCHOR CALCULATIONS
 THIS REVISION ON 10/11/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28D) EXTERIOR GLAZED SWING DOORS NOA 04-0209.03 THIS
 NOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC WENT
 INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1 1/3
 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0209.03 ANCHOR CALCULATIONS
 THIS REVISION ON 04/13/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28E1) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRSNOA
 04-0203.03
 THISNOA WAS ISSUED AND TESTEDBEFORE THE 2004 FBC
 WENT INTO EFFECT. BEFORE THIS DATE STEEL INCREASES OF 1
 1/3 WERE COMMON PLACE AND TAKEN WITH FASTENERS, AP.E.
 SHOULD REVIEW THE TEST REPORT INFORMATION TO SEE IF THE
 INCREASES WERE TAKEN.THE NEWER MIAMI-DADE NOAS THAT
 WERE RENEWED AFTER THE 2004 FBC WENT INTO EFFECT WILL
 STATE UNDER THE HEADING (3) CALCULATIONS, ANCHOR
 VERIFICATION VERIFIED TO THE 2004 FBC- NO STEEL
 INCREASES TAKEN. NOA 04-0203.03 ANCHOR CALCULATIONS
 THIS REVISION ON 08/09/04 BEFORE THE ISSUANCE OF THE
 2004 FBC.
 1605.3.1.1 LOAD REDUCTION.
 1.IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT
 OF TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE
 EFFECT OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN
 SHALL NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD
 LOAD AND ANY OF THE VARIABLE LOADS.
 2.INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3.SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28E2) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRS -
 COMPLIED.SEE CALCULATION STATEMENT # 1, ANCHOR
 VERIFICATION OF THE 2004 FBC
  
 28F)1) EXTERIOR COIL DOORS/ SECTIONAL DOORSCORNELL IRON
 WORKS SUBMITTED FL5416 THE ATTACHED MIAMI-DADE REPORT
 IS NOT THE CORRECT BACK-UP REPORT LISTED WITH THE
 STATE, ES16-23-01 IS THE CORRECT REPORT.
  
 28F)2) EXTERIOR COIL/ ROLL UP DOOR COOKSON COMPANY
 FL2211-R1 THE ATTACHED IS A MIAMI-DADE REPORT IS NOT
 THE CORRECT BACK-UP REPORT LISTED WITH THE STATE,
 WLCD-002-B-2004 IS THE CORRECT REPORT,
  
 28F)3) EXTERIOR SECTIONAL DOOR: CLOPAY MISSING THE
 FLORIDA COVERSHEET AND CORRESPONDING REPORTS THERE ARE
 (3) REPORTS WITH THE DOOR MODEL 3200 OR 3220. NOTE
 PRESSURES ARE LOWER UNDER THESE REPORTS.
  
 28G) FASCIA SYSTEMS
  
 28H) EFIS WALL SYSTEMS- DRYVIT SYSTEMS FL2030-R2
 SUBMITTED 06-0608.05PLEASE SUPPLY CORRESPONDING
 REPORT 06-1004.06DRYVIT OUTSULATION PLUS, PLEASE
 CORRECT.
  
 28I) ROOFING SYSTEMS W/ INSULATION- COMPLIED.
  
 28J) ROOF HATCH- COMPLIED.
  
 28K) LOUVER WALL- RUSKIN FL3283-R1 WAS SUBMITTED WITH
 THE WRONG MIAMI-DADE NOA FOR BACK UP
  
 28L) ALCAN ALUCOBOND COMPOSITE WALL PANEL NOA
 06-1019.02 IS A NON-FIRE RATED COMPOSITE PANEL, WHERE
 WILL THIS PRODUCT BE USED, TYPE I-B NONCOMBUSTIBLES AND
 SECTION 603?
 NOTE # 4 STUDS GRATER THAN 4'-0"IN HEIGHT MUST
 BE DESIGNED BY A FL PE FOR A MAXIMUM OF 90+/-. FLORIDA
 DOES HAVE ALCAN COMPOSITE PANELS LISTED ON WEBSITE.
  
 29)COMPLIED.
  
 30)COMPLIED.
  
 31) BUILDING PROVISO: PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR FIRE RESISTANT RATING OF STRUCTURAL MEMBERS
 BEFORE FRAMING INSPECTION. THE CODE ANALYSIS INDICATES
 THIS TO BE A TYPE I-B BUILDING REQUIRING FIRE RATINGS
 OF THE STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE
 THE MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING. TABLE 601 & 721.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By jwitmer Date 2008-03-21 Time 08:47 Rev Time 8.88
Received By jwitmer Date 2008-03-21 Time 08:47 Sent To  
Notes
2008-04-01 09:24:16BUILDING PLAN REVIEW
 PERMIT: 08020128 (PLAN REVIEW)
 ADD: 1760 PALM BEACH LAKES
 CONT: RYAN COMPANIES
 TEL: (621)677-7235
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECTURAL FIRM: RSP ARCHITECTURAL GROUP
 STEVEN J. FAUTSCH
 AR# 93674
  
 ENGINEERING FIRM TRC WORLD WIDE ENGINEERING
 MARCUS O. UNTERWEGER
 PE#63860
  
 BUILDING TYPE: I-B/ FULLY SPRINKLERED
 REVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE CORRECT
 SHEET G001 BUILDING CODE INFORMATION. PLEASE NOTE THAT
 IF A PERMIT APPLICATION WILL NEED TO BE APPLIED FOR
 BEFORE OCT 1, 2008 TO LOCK THIS PROJECT IN UNDER THE
 2004 FBC. OCT 1, 2008 THE 2007 FBC
 WILL GO INTO AFFECT.
  
 2) FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 XXX -BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE STRENGTH (F'C) IN EXCESS
 OF 3000 PSI
 - PILE DRIVING
 XXX - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION
  
 3) FBC* 109.3.7 SINCE A RESIDENT INSPECTOR WILL
 REQUIRED, THREE OF ALL DOCUMENTS (PLANS, REPORTS,
 SUBMITTALS AND PRODUCT APPROVALS) WILL BE REQUIRED FOR
 ISSUANCE OF THE PERMIT.
  
 4) SOILS REPORTS 2 REPORTS WERE SUBMITTED, PLEASE
 SUBMIT THREE REPORTS WITH ORIGINAL SIGNATURES, NOT
 COPIES OR STAMPED SIGNATURES. 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) SHEET G001 THE BUILDING CODE INFORMATION :
 8A) THE PLANS INDICATE THIS TO HAVE A S2 AND M
 OCCUPANCY PLEASE SEE CODE SECTIONS THAT WOULD CLASSIFY
 THIS AS A MIXED USE BUILDING, NOT THE NON-SEPARATED USE
 AS INDICATED IN YOUR CODE ANALYSIS.
  
 406.2.7MIXED OCCUPANCIES. PARKING GARAGES SHALL BE
 SEPARATED FROM OTHER OCCUPANCIES IN ACCORDANCE WITH
 SECTION 302.3.2 .
  
 406.3.4 PLEASE SEE ALLOWABLE MIXED USES ALLOWED IN THE
 SAME BUILDING AS A OPEN PARKING GARAGE.302.3 MIXED USE
 AND 508.7 A, B, M & R OCCUPANCIES.
  
 302.3.2 SEPARATED USES.
 EACH PORTION OF THE BUILDING SHALL BE INDIVIDUALLY
 CLASSIFIED AS TO USE AND SHALL BE COMPLETELY SEPARATED
 FROM ADJACENT AREAS BY FIRE BARRIER WALLS OR HORIZONTAL
 ASSEMBLIES OR BOTH HAVING A FIRE-RESISTANCE RATING
 DETERMINED IN ACCORDANCE WITH TABLE 302.3.2 FOR USES
 BEING SEPARATED. EACH FIRE AREA SHALL COMPLY WITH THIS
 CODE BASED ON THE USE OF THAT SPACE. EACH FIRE AREA
 SHALL COMPLY WITH THE HEIGHT LIMITATIONS BASED ON THE
 USE OF THAT SPACE AND THE TYPE OF CONSTRUCTION
 CLASSIFICATION. IN EACH STORY, THE BUILDING AREA SHALL
 BE SUCH THAT THE SUM OF THE RATIOS OF THE FLOOR AREA OF
 EACH USE DIVIDED BY THE ALLOWABLE AREA FOR EACH USE
 SHALL NOT EXCEED ONE.
  
 TABLE 302.3.2 WILL REQUIRE A 2HR RATING BETWEEN THE S2
 AND MERCANTILE OCCUPANCIES.
 ALSO SEE SECTION 508.7.1 FIRE SEPARATION.
  
 508.7.1 FIRE SEPARATION
 FIRE SEPARATION ASSEMBLIES BETWEEN THE PARKING
 OCCUPANCY AND THE UPPER OCCUPANCY SHALL CORRESPOND TO
 THE REQUIRED FIRE-RESISTANCE RATING PRESCRIBED IN TABLE
 302.3.2 FOR THE USES INVOLVED. THE TYPE OF CONSTRUCTION
 SHALL APPLY TO EACH OCCUPANCY INDIVIDUALLY, EXCEPT THAT
 STRUCTURAL MEMBERS, INCLUDING MAIN BRACING WITHIN THE
 OPEN PARKING STRUCTURE, WHICH IS NECESSARY TO SUPPORT
 THE UPPER OCCUPANCY, SHALL BE PROTECTED WITH THE MORE
 RESTRICTIVE FIRE-RESISTANCE-RATED ASSEMBLIES OF THE
 GROUPS INVOLVED AS SHOWN IN TABLE 601 . MEANS OF EGRESS
 FOR THE UPPER OCCUPANCY SHALL CONFORM TO CHAPTER 10 AND
 SHALL BE SEPARATED FROM THE PARKING OCCUPANCY BY FIRE
 BARRIERS HAVING AT LEAST A 2-HOUR FIRE-RESISTANCE
 RATING AS REQUIRED BY SECTION 706 , WITH SELF-CLOSING
 DOORS COMPLYING WITH SECTION 715 . MEANS OF EGRESS FROM
 THE OPEN PARKING GARAGE SHALL COMPLY WITH SECTION 406.3
 (OPEN PARKING GARAGES) .
  
 NOTE PLEASE SEE 2004 FBC CODE COMMENTARY FOR SECTION
 508.7.1. THIS SECTION CONTAINS ADDITIONAL CONDITIONS
 FOR THE USE OF 508.7 AS AN ALTERNATIVE TO THE GENERAL
 MIXED-USE PROVISIONS IN SECTION 302.3. IT CONTAINS AN
 ADDITIONAL FIVE CRITERIA.
  
 8B) SHEET G001 BUILDING CODE INFO ALSO INDICATES THIS
 TO BE A OPEN PARKING GARAGE PLEASE PROVIDE OPENING
 CALCULATIONS MEETING THE REQUIREMENTS OF 406.3.3.1.
 ALSO SEE EXCEPTION.
 IN ADDITION TO THIS REQUIREMENT PLEASE SEE ALLOWABLE
 OPENINGS IN TABLE 704.8. PLANS INDICATE WALLS WITH LESS
 THAN 10?-0? FROM THE PROPERTY LINE, PLEASE PROVIDE
 OPENING CALCULATIONS FOR EXTERIOR WALLS.
  
 8C) PLANS INDICATE WALLS WITHIN 10?-0? OF THE PROPERTY
 LINE THE CODE ANALYSIS DOES
 NOT PROVIDE THE ALLOWABLE OPENINGS MENTIONED ABOVE(
 TABLE 704.8) NOR THE RATING OF THE BUILDING ELEMENTS
 THAT ARE LISTED IN TABLE 601, PLEASE PROVIDE THE HOURLY
 RATING REQUIRED, THE BUILDING ELEMENTS FIRE RATING CAN
 BE TAKEN FROM TABLE 720.1 AND FOR COLUMNS AND BEAMS
 TABLE 721.3.4 & TABLE 721.3.5.
  
 9) SHEET G001 INDICATES IN A NOTE SEE SHEET A001 FOR
 THE FLORIDA PRODUCT APPROVALS.
 THE INSPECTORS CAN NOT COMPLETE THEIR INSPECTIONS
 WITHOUT THE ACTUAL PRODUCT APPROVALS. WE AS PLAN
 REVIEWERS ALSO CAN NOT EVEN START OUR PORTION OF THE
 REVIEW UNTIL THE FLORIDA COVERSHEETS AND THE ASSOCIATED
 REPORT AND TECHNICAL SHEETS ARE PROVIDED.
 GLAZED OPENINGS: IN MANY CASES THE FLORIDA COVERSHEET
 MAY LIST MULTIPLE SERIES OF WINDOWS UNDER A SINGLE
 REPORT AND OR IN A SINGLE REPORT THEIR MAY HAVE
 MULTIPLE OPTIONS
 TO GLAZING IN THICKNESS AND TYPE OF LAMINATIONS TO
 CREATE LAMINATED GLAZING UNITS WITH LARGE MISSILE
 IMPACT TESTING. UNTIL THE CONTRACTOR OR DESIGNER
 INDICATES WHICH OF THESE
 OPTIONS ARE TO BE INSTALLED WE CAN NOT DETERMINE CODE
 COMPLIANCE FOR THE PRODUCT.
 PLEASE SUPPLY THREE SETS OF PRODUCT APPROVALS WITH IN
 BINDERS INDENTIFYING EACH OF THE
 PRODUCTS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 10A) SHEET G001 NOTES FOR PRODUCT APPROVALS NOTE THERE
 MAY NO FLORIDA AND MIAMI-DADE APPROVALS FOR ROOF
 HATCHES BUT THERE IS A LOCAL PRODUCT APPROVAL UNDER
 AHJ, AUTHORITY HAVING JURISDICTION, THE CITY OF WEST
 PALM BEACH DOES HAVE A LOCAL APPROVAL FOR THE NYSTORM
 RHG3630T ROOF SCUTTLE, A COPY WILL BE ATTACHED.
  
 10B) PLEASE SEE SHEET A020 EXIT WIDTH ANALYSIS, PLEASE
 CORRECT THE CODE TO THE 2004 FBC W/ 2007 SUPPLEMENTS.
  
  
 11) NOTE, IT APPEARS THAT THE EXIT WIDTH ANALYSIS AND
 THE EXIT WIDTH DOOR & STAIR KEY FOUND ON A021 INDICATE
 A OVERAGE OF 96 OCCUPANTS OUR CALCULATIONS INDICATE A
 SHORTAGE OF -34 OCCUPANTS, IN EITHER CASE THE PLANS
 WILL NEED TO MEET THE MINIMUM CODE REQUIREMENTS FOR
 WIDTH REQUIREMENTS.
 I WILL EXPLAIN THE AREAS WHERE I BELIEVE WE MAY HAVE A
 DIFFERENCE IN OUR FIGURES, AND THERE MAY BE LESS SEVERE
 ISSUES THAT WILL NEED TO BE ADDRESSED.
  
 11A) A-305 STAIR- A THE STAIR WIDTH IS INDICATED AS
 4?-6? BUT THE INTERMEDIATE OR MID- LANDING IS ONLY
 4?-0? IN DEPTH. PLEASE SEE 1009.4THE MINIMUM DIMENSION
 MEASURED IN THE DIRECTION OF TRAVEL IS TO BE EQUAL TO
 THE WIDTH OF THE STAIRWAY. THIS IS AN ISSUE THAT WE SEE
 ON ALL OF THE STAIRS.
  
 11B) STAIRWAY A & ESCALATORS DO NOT MEET THE SHAFT
 ENCLOSURES AND THE EXCEPTIONS FOUND IN 707.2 EXCEPTION
 2, THE STAIR A WOULD NOT BE PART OF THE EGRESS
 CALCULATION & PROTECTED ACCORDING TO ITEMS 2.1 AND 2.2.
 PLEASE PROVIDE ADDITIONAL INFORMATION FOR CODE
 COMPLIANCE.
  
 11C) IF THE 2ND FLOOR IS TO BE LEFT OPEN TO THE STAIR-A
 PLEASE REVIEW 404 ATRIUM REQUIREMENTS
 AND 404.5 ENCLOSURE OF ATRIUMS AS WELL AS POSSIBLE
 404.4 SMOKE CONTROL.
  
 11D) THIS IS A COMMENT THAT MAY OR MAY NOT APPLY TO
 THIS STAIRWELL DEPENDING ON THE REVISIONS TO THE PLAN,
 THIS COMMENT DOES PERTAIN TO OTHER STAIRWELLS SO IN
 CONSIDERATION TO THE CONCEPT CHANGES I WOULD BRING THIS
 ISSUE TO VIEW. PLEASE SEE 1019.1.4 WHERE NON-RATED
 WALLS OR UNPROTECTED OPENINGS ENCLOSE THE EXTERIOR OF
 THE STAIRWAY AND THE WALLS OR OPENINGS ARE EXPOSED BY
 OTHER PARTS OF THE BUILDING AT AN ANGLE LESS THAN 180
 DEGREES, THE BUILDING EXTERIOR WALLS WITHIN 10 FT
 HORIZONTALLY OF A NONRATED WALL OR OPENING SHALL BE
 CONSTRUCTED AS REQUIRED FOR A MINIMUM 1-HOUR FIRE
 RESISTANCE WITH ? HOUR OPENING PROTECTIVES. SEE CODE
 COMMENTARY.
  
 11E) STAIRWELL B THERE ARE UNKNOWNS BUT ASSUMPTIONS AS
 TO DOORS IN THE DOOR SCHEDULE,
 SEE SHEET A611 DOOR NUMBERS 071.1- 074.2 THESE DOOR
 WIDTHS ARE NOT GIVEN. THE 4 DOORS AT THE TOP OF THE
 STAIRS DO NOT PROVIDE DOOR INFORMATION, AND THE DOORS
 AT THE BOTTOM OF THE
 STAIRS ARE GIVEN AS ROUGH OPENINGS NOT CLEAR OPENING.
 PLEASE PROVIDE ADDITIONAL INFORMATION SO A REVIEW OF
 THIS EXIT CAN BE ACCOMPLISHED. 106.1.2*.
  
 11F) THERE MAY BE A BIT OF CONVERGENCE FROM THE 4 DOORS
 AT THE TOP STAIRS AND STAIRS, THIS IS A UNKNOWN UNTIL
 THE DOOR WIDTHS CAN BE DETERMINED
  
 11G) THE MID-LANDING, PLEASE SEE 1009.4THE MINIMUM
 DIMENSION MEASURED IN THE DIRECTION OF TRAVEL IS TO BE
 EQUAL TO THE WIDTH OF THE STAIRWAY. THIS IS AN ISSUE
 THAT WE SEE ON ALL OF THE STAIRS.
  
 11H) FOR STAIRS B,C & D ALL OF THESE STAIRS WE AGREE
 WITH THE DESIGNER AT 600 OCCUPANT LOAD FOR EACH
 STAIRWELL. ISSUES WITH THESE STAIRS WILL BE THE
 MID-LANDING 1009.4 AND 1019.1.4 WHERE NON-RATED WALLS
 OR UNPROTECTED OPENINGS ENCLOSE THE EXTERIOR OF THE
 STAIRWAY AND THE WALLS OR OPENINGS ARE EXPOSED BY OTHER
 PARTS OF THE BUILDING AT AN ANGLE LESS THAN 180
 DEGREES, THE BUILDING EXTERIOR WALLS WITHIN 10 FT
 HORIZONTALLY OF A NONRATED WALL OR OPENING SHALL BE
 CONSTRUCTED AS REQUIRED FOR A MINIMUM 1-HOUR FIRE
 RESISTANCE WITH ? HOUR OPENING PROTECTION. SEE CODE
 COMMENTARY.
  
 11I) STAIR E MID-LANDING, , PLEASE SEE 1009.4THE
 MINIMUM DIMENSION MEASURED IN THE DIRECTION OF TRAVEL
 IS TO BE EQUAL TO THE WIDTH OF THE STAIRWAY. THIS IS AN
 ISSUE THAT WE SEE ON ALL OF THE STAIRS.
  
 11J) STAIR E SEE THE BOTTOM SET OF DOORS THE WIDTH OF
 THE DOOR IS NOT ON THE DOOR SCHEDULE FOR DOOR NUMBER
 074.1 & 07.42. ADDITIONAL INFORMATION
 REQUIRED.106.1.2*.
  
 11K) STAIR F, THE ISSUE WITH THIS STAIR IS THE WIDTH OF
 THE STAIR VERSES HAND RAILS. SEE 1009.11.2 HANDRAILS
 SHALL BE PROVIDED WITHIN 30 INCHES OF ALL PORTIONS OF
 THE STAIR WIDTH REQUIRED FOR EGRESS CAPACITY IN
 ACCORDANCE WITH TABLE 1005.1 .
 SHEET A021 INDICATES THE USE OF ONLY (1) HANDRAIL WHICH
 IN ACTUALITY ONLY A 10?-0? WIDE STAIR AND OCCUPANT LOAD
 OF 400 NOT THE 540 AS INDICATED IN THE PLAN MULTIPLE
 HANDRAILS WOULD BE NEEDED TO ACCOMMODATE AND ACHIEVE
 THE 540 OCCUPANT LOAD FOR THIS STAIR. THIS IS THE
 STAIRWAY THAT CURRENTLY LOOSES 140 OF THE OCCUPANTS AS
 DESIGNED BY NOT HAVING MORE INTERMEDIATE HANDRAILS.
  
 12A) A021 REFERS TO DETAIL#2 SHEET A331 THIS SECTION OR
 DETAIL REFERENCES DETAIL 20 ON SHEET A231. IT APPEARS
 TO BE AN EXPANSION JOINT IN THE FLOOR BUT THERE IS NO
 INFORMATION THAT I CAN FIND ON THE FIREPROOFING
 REQUIREMENTS TABLE 601 FOR FLOOR SYSTEMS AND OCCUPANCY
 TYPE SEPARATION TABLE 302.3.2.PLEASE PROVIDE FLOOR
 CEILING TYPE PENETRATIONS FOR PIPES AND CONDUITS AS
 WELL AS FOR ANY HORIZONTAL PENETRATION OF RATED FLOOR/
 CEILING ASSEMBLY.
 SEE 711.3.& 712.3.1.
  
 12B) SHEET A331 INDICATES DETAIL 2 THE RIGHT UPPER
 PORTION INDICATES A CIRCULATION AREA THAT LEADS IN TO
 STAIRWELL D, THE WALL TYPE IS P5 THIS WALL TYPE
 INDICATES A FINISH ON ONE SIDE. SHEET A601 PARTITION
 TYPES INDICATES THE USE OF PLYWOOD ON OR WITHIN MANY
 PARTITIONS. PLEASE SEE 603.1(1.1) FIRE RETARDANT
 TREATED WOOD SHALL BE PERMITTED IN:
 1.1 NONBEARING PARTITIONS WHERE THE REQUIRED FIRE
 RESISTANCE RATING IS LESS THAN TWO HOURS OR LESS.
  
 603.21 MATERIALS ALLOWED IN CONCEALED SPACES OF
 BUILDINGS OF TYPE I AND II CONSTRUCTION IN ACCORDANCE
 WITH SECTION 717.5. PLEASE UPDATE TO FIRE RETARDANT
 TREATED PLYWOOD.
  
 13) SHEET A110 INDICATES THE DISABLED PARKING SPACES
 AND ACCESS AISLES BUT NOT THE ELEVATION CHANGES OF THE
 PARKING LOT VERSES DISABLED SPACES AND ACCESS AISLES.
 THE OTHER ISSUE IS NO INFORMATION FOR DETECTABLE
 WARNING AT HAZARDOUS VEHICULAR AREAS 11-4.29.5.
  
 14) SHEET A110 PLEASE PROVIDE INFORMATION ON VAN
 ACCESSIBILITY, 11-4.6.5 VERTICAL CLEARANCE.
 A) 114? TO VEHICLE ACCESS ROUTE FROM SITE ENTRANCE TO
 EXIT & PASSENGER LOADING ZONES
 ALSO SEE 11-4.6.6.
 B) 98? MINIMUM AT PARKING ZONE.
 C) SIGNAGE 11-4.6.4
  
 15) PLEASE PROVIDE COMPLIANCE WITH 11-4.1.3(8)(A) AND
 SECTION 11-4.1.3(8)(B) AND SHALL BE SATISFIED
 INDEPENDENTLY..
  
 16) SHEET A301 DETAIL 1 INDICATES THE USE OF A FOOD
 SERVICE AREA THE PLANS INDICATE A AREA FOR 50 FOR
 SEATING, PLEASE COMPLY WITH 11-5.1 INDICATING THE AREA
 OF 5 % DISABLED PERSONS.
  
 17) PLEASE PROVIDE SECTIONS FOR COUNTERS AND BARS TO
 INDICATE COMPLIANCE WITH 11-5.2,
 11-5.5 & 11-5.6 A303 DETAIL 2 INDICATES A 3?-0? COUNTER
 HEIGHT..
  
 18) A311 ROOM TRAINING/ LOUNGE IS 2448 SQ FT APPROX /
 15 = 163 OCCUPANT LOAD, THIS IS AN ASSEMBLY AREA
 REQUIRING 1 HR RATED WALLS AND OPENING PROTECTIVES. SEE
 TABLE 1004.1.2,THIS WILL BE CLASSIFIED AS A A2
 OCCUPANCY OCCUPANT LOAD > THAN 50. SEE TABLE 1016.1
 ASSEMBLY LOADS> THAN 30 WITH FIRE SPRINKLERS WILL STILL
 REQUIRE 1 HR RATING. PLEASE CORRECT WALL TYPES AND
 OPENING PROTECTIVES. TABLE 715.3. SEE CORRIDOR 118 DOES
 NOT INDICATE A FIRE RESISTANCE RATING.
  
 19) SHEET A311 FAMILY RESTROOM 107, REST ROOMS 108, 109
 AND 131 DO NOT INDICATE AN UNOBSTRUCTED TURNING SPACE
 AS REQUIRED IN 11-4.22.3. THE ACCESSIBLE STALLS IN
 RESTROOM
 108 & 109 DO NOT PROVIDE THE WIDTH DIMENSION SEE FIGURE
 30(A) STANDARD STALL A MINIMUM OF 60? CLEAR.
  
 20) SHEET A351 & A352 BOTH INDICATE AN ELECTRICAL
 DISTRIBUTION CENTER THAT DOES NOT HAVE A CODE COMPLIANT
 STAIR. THE CODE DOES ALLOW FOR FIXED LADDERS AS PART OF
 A MEANS OF EGRESS IN THE FOLLOWING LOCATIONS: FOR
 BOILERS (1014.3), REFRIGERATION ROOM (1014.4), STAGE
 EXITS 410.5.4, 1014.6.6.1 GALLERY, GRIDIRONS AND
 CATWALKS THAT ARE ASSOCIATED WITH STAGES
 AND HELISTOPS (1018.1.2.). PLEASE PROVIDE A CODE
 COMPLIANT STAIRWAY. SEE 1014.1 & TABLE 1014.1.
  
 21) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 ELECTRICAL DISTRIBUTION CENTER, PRE-MANUFACTURED? TYPE
 OF MATERIAL, FIRE RATINGS ETC? NFPA 13.8.14.10.
  
 22)THE WALLS OR SHAFT WHERE THE CURRENT SHIPS LADDER IS
 LOCATED HAS A 2 HR FIRE RATING BUT THERE ARE NO WALL
 RATINGS FOR THE WALLS SURROUNDING THE EDC. 106.1.2.
 ADDITIONAL INFORMATION REQUIRED. THIS WOULD APPEAR TO
 BE PART OF THE SHAFT WALL CONSTRUCTION BUT THERE ARE NO
 WALL IDENTIFICATION TAGS.
  
 23) THE SAME SHEETS IDENTIFY ANOTHER SHIPS LADDER WHICH
 RISES TO THE ROOF LEVEL WITH A
 ROOF HATCH. NOTE THIS WILL BE A PRODUCT THAT WILL
 REQUIRE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA..
 NOTE CURRENTLY NEITHER THE STATE NOR MIAMI-DADE
 CURRENTLY HAVE A LISTING. THE CITY OF WPB DOES HAVE A
 LOCAL APPROVAL FOR A NYSTROM RHG3630T ROOF HATCH. A
 COPY WILL BE ATTACHED.
  
 24) SHEET A361 MAIN ELECTRIC CENTER PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE ELECTRICAL DISTRIBUTION
 CENTER, PRE-MANUFACTURED? TYPE OF MATERIAL, FIRE
 RATINGS ETC? NFPA 13.8.14.10.
  
 25) SHEET A361 ALSO INDICATES THERE TO BE A GENERATOR,
 PLEASE PROVIDE THE SIZE OF GENERATOR AND PROVIDE
 ANCHORAGE DETAILS 1609. 1.3 ANCHORAGE AGAINST MOMENT OF
 OVERTURNING, SLIDING AND UPLIFT.
  
 26) PLEASE PROVIDE THE AMOUNT OF PROPANE AND TYPE OF
 TANKS TO BE USED. PLANS INDICATE SEE MECHANICAL PLANS
 FOR ATTACHMENT, M-111 INDICATES THE GENERATOR AND TANKS
 IN A DIFFERENT LOCATION. 106.1.2*. ADDITIONAL
 INFORMATION REQUIRED.
  
 27) S001 DESIGN CODES, PLEASE UPDATE THE 2004 FBC AND
 SUPPLEMENTS TO THE 2007 SUPPLEMENTS. NOTE IF THIS MAJOR
 WORKING DRAWING REVIEW IS NOT SUBMITTED AS A PERMIT
 BEFORE OCT.1, 2008 IT WILL NEED TO BE RE-REVIEWED UNDER
 THE 2007 FBC.
  
 28)) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
  
 28A) WINDOWS: CURTAIN-WALL
 ******************************************************
 * ****************
 NOTE: THE FOLLOWING SYSTEMS LISTED BELOW, HAVE NOT
 PROVIDED THE FLORIDA COVERSHEET THAT
 PROVIDES ADDITIONAL INFORMATION NOT LISTED IN THE TEST
 REPORT.
  
 THE SECOND ISSUE WITH THE NOA?S ARE THEY WERE TESTED
 BEFORE THE 2004 FBC WENT INTO EFFECT. BEFORE THIS DATE
 STEEL INCREASES OF 1 1/3 WERE COMMON PLACE AND TAKEN
 WITH FASTENERS, A P.E. SHOULD REVIEW THE TEST REPORT
 INFORMATION TO SEE IF THE INCREASES WERE TAKEN. THE
 NEWER MIAMI-DADE NOA?S THAT WERE RENEWED AFTER THE 2004
 FBC WENT INTO EFFECT WILL STATE UNDER THE HEADING (3)
 CALCULATIONS, ANCHOR VERIFICATION VERIFIED TO THE 2004
 FBC- NO STEEL INCREASES TAKEN.
 1605.3.1.1 LOAD REDUCTION.
 1. IT IS PERMITTED TO MULTIPLY THE COMBINED EFFECT OF
 TWO OR MORE VARIABLE LOADS BY 0.75 AND ADD THE EFFECT
 OF DEAD LOAD. THE COMBINED LOAD USED IN DESIGN SHALL
 NOT BE LESS THAN THE SUM OF THE EFFECT OF DEAD LOAD AND
 ANY OF THE VARIABLE LOADS.
 2. INCREASES IN ALLOWABLE STRESS SPECIFIED IN THE
 MATERIALS, SECTIONS OF THIS CODE OR A REFERENCED
 STANDARD SHALL NOT BE PERMITTED TO BE USED WITH LOAD
 COMBINATIONS OF SECTIONS 1605.3.1 . DURATION OF LOAD
 INCREASE SHALL BE PERMITTED IN ACCORDANCE WITH CHAPTER
 23 .
 EXCEPTION: INCREASES IN ALLOWABLE STRESS SHALL BE
 PERMITTED IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402
 PROVIDED THE LOAD REDUCTION OF SECTION 1605.3.1.1 ITEM
 1 SHALL NOT BE APPLIED.
 3. SIMULTANEOUS USE OF BOTH ONE-THIRD INCREASE IN
 ALLOWABLE STRESS AND THE 25-PERCENT REDUCTION IN
 COMBINED LOADS SHALL NOT BE PERMITTED.
  
 28B) WINDOWS: STOREFRONT
 28C) AUTOMATIC BYPASS DOOR PEDESTRIANS AND CARTS 28D)
 EXTERIOR GLAZED SWING DOORS
 28E) EXTERIOR HOLLOW METAL DOORS SINGLE AND PAIRS 28F)
 EXTERIOR COIL DOORS/ SECTIONAL DOORS
 28G) FASCIA SYSTEMS
 28H) EFIS WALL SYSTEMS
 28I) ROOFING SYSTEMS W/ INSULATION- ONLY A DRIP EDGE
 REPORT SUBMITTED, NO REPORT FOR FLAT
 DECK
 28J) ROOF HATCH- SEE ATTACHMENT
  
  
 *******THE CITY REQUEST THE FLORIDA COVER SHEETS *****
  
 29) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 30) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 31) THE CODE ANALYSIS INDICATES THIS TO BE A TYPE I-B
 BUILDING REQUIRING FIRE RATINGS OF THE
 STRUCTURAL STEEL AND BAR JOIST, PLEASE PROVIDE THE
 MANUFACTURERS SPEC AND THE THICKNESS REQUIRED TO
 ACHIEVE THE REQUIRED FIRE RATING.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2009-09-09 Cont ID  
Sent By dpalmer Date 2009-09-09 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2009-09-09 Time 12:05 Sent To  
Notes
2009-09-09 12:05:59E110

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 12:59 Sent To  
Notes
2009-07-28 13:00:16SELECTIVE COORDINATION STUDY.

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 12:59 Sent To  
Notes
2009-07-28 12:59:32REV'S OK./

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-07-08 Cont ID  
Sent By dpalmer Date 2009-07-08 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 16:19 Sent To PC
Notes
2009-07-08 13:47:52 
  
 ** DENIED PLANS **
  
 1) NOTE: AS REQUESTED ON PREVIOUS REVIEW PLEASE SUBMIT
 A COMPLETE SELECTIVE COORDINATION STUDY INCLUDING ALL
 RELEVANT TIME CURVES.
 THE SINGLE SHEET DOCUMENT SUBMITTED IS NOT THE COMPLETE
 INFORMATION NEEDED FOR REVIEW.
 PLEASE SEE NFPA-70 700.27, 701.18, 240.12.
 ** THIS WAS DERIVED BASED ON SEVERAL REVISIONS AGO WHEN
 ALL BATTERY BACK UP LIGHTING REQUIRED FOR EGRESS UNDER
 EMERGENCY CONDITIONS WAS REVISED TO ONLY USE THE NEW
 LIFE SAFETY GENERATOR AS BACK UP FOR EMERGENCY
 LIGHTING.
  
 *** THIS WILL AFFECT ANY APPLICATION FOR TCO OR CO OF
 BUILDING.
  
 ** AT THIS TIME SHEET E-801 SUBMITTED IS STAMPED OK.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-05-13 Cont ID  
Sent By dpalmer Date 2009-05-13 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2009-05-08 Time 15:37 Sent To  
Notes
2009-05-13 13:59:51**REDLINED PLANS,
  
 NOTES:
  
 *** PROVISO FROM 9/29/08 STILL NEEDS TO BE ADDRESSED.
  
  
 1) NOTE: THE SELECTIVE COORDINATION STUDY STILL NEEDS
 TO BE DONE AND SUBMITTED WITH COMPLETE TIME CURVES FOR
 ALL 700 AND 701 SYSTEMS.
 700.27, 701.8, 240.12 NFPA-110 6.5.1
  
 2) NOTE: ** CALL WAS MADE TO ENGINEER FOR INFORMATION
 ON CHANGES TO ASME-17 FOR STATE ELEVATOR STANDARD.
 THERE HAVE BEEN SOME CHANGES TO CODE REQUIREMENTS FOR
 LIGHTING. THIS IS NOT UNDER THE REVIEW OF THIS
 REVIEWER. THIS IS BEING NOTED AT THIS TIME TO ADDRESS
 ANY ITEMS BEFORE THEY COME UP IN THE INSPECTION DONE BY
 THE STATE ELEVATOR INSPECTOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2009-05-11 11:02:035/11 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-03-10 Cont ID  
Sent By dpalmer Date 2009-03-10 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2009-03-10 Time 15:41 Sent To  
Notes
2009-03-10 15:41:56** DENIED REVISIONS **
  
 1) NOTE: NOT ALL CHANGES AND REVISIONS ON SHEETS HAVE
 BEEN IDENTIFIED WITH CLOUDS AND TRIANGLES.
 FOR EXAMPLE: PLEASE SEE E1110 WHICH CONTAINS A
 SUBSTANTIAL AMOUNT OF REVISIONS MOST ARE NOT
 IDENTIFIED.
 FOR EXAMPLE: PLEASE SEE E001 WHERE CLOUDS ARE SHOWN
 HOWEVER NO IDENTIFICATION IS SHOWN.
  
 ** THESE ARE TWO EXAMPLES ONLY. THERE ARE OTHERS.
 PLEASE BE SURE ALL REVISIONS ARE IDENTIFIED ON PLANS.
  
 FBC 106.5, 106.1.1, 106.1.2 FOR CLARITY, ADDITIONAL
 INFORMATION OF RECORD PLANS.
 FBC CHAPTER 13, CHAPTER 10, NEC 2005.
  
 2) NOTE: PLANS NOW HAVE MOST ALL PREVIOUS BATTERY BACK
 UP FIXTURES REMOVED. BASED ON THE REVISED PLANS THIS IS
 NOT PERMITTED AS SHOWN. A STRAIGHT NATURAL GAS
 GENERATOR IS NOT PERMITTED BY THIS AHJ.
 THIS WAS GONE OVER BEFORE PERMIT OF BUILDING WAS ISSUED
 YET PLANS ARE NOW ONCE AGAIN BEING REVISED TO GO BACK
 TO SOMETHING THAT HAD ALREADY BEEN COMMENTED ON.
 PLEASE SEE 700.12.B.3. ONSITE FUEL SHALL BE REQUIRED.
 PLEASE SEE NFPA-101 AS THE BACK UP POWER SOURCE FOR
 EMERGENCY LIGHTING FIXTURES ARE AT THE DETERMINATION OF
 THE AHJ. SECTION 7.8.2.1.
 THE CODE IS SPECIFIC TO THE REQUIREMENT OF ON-SITE FUEL
 REQUIRED. PLEASE SEE FBC CHAPTER 10, 1006.2.3.
  
 3) NOTE: PLEASE PROVIDE COMPLETE STOCK OF MATERIALS AND
 RETAIL GOODS IN AREAS IN WHICH DESIRED USED OF *FINE
 MERCHANDISE* IS PLACED IN THE INPUT DATA REPORT OF THE
 ENERGY CALCULATIONS.
 THE AMOUNT OF FINE MERCHANDISE WOULD BE LIMITED TO
 SQUARE FEET OF DISPLAY AREA ONLY. NOT AREAS OF GENERAL
 LIGHTING. PLEASE ALSO KNOW THAT THIS ALLOWANCE MAY BE
 USED FOR ITEMS SUCH AS JEWELRY AS NOTED IN THE CODE
 HOWEVER BASED ON THE CALCULATIONS ALL DISPLAY AREAS ARE
 NOTED AS FINE MERCHANDISE WHICH DOES NOT POSSIBLE OR
 PERMISSIBLE.
 FBC 13-415.2, 13-415.2.ABC.1.1, .1.2, 13-415.2.B.2 ETC
  
 4) NOTE: ALL EGRESS PATHS SHALL CONTAIN THE BATTERY
 BACK UP FIXTURES SUCH AS STAIRS. SOME STAIR AREAS STILL
 CONTAIN FIXTURES AS NOTED HOWEVER STAIRS SUCH AS THE
 MAIN EGRESS STAIRS AT THE REAR OF THE STORE HAVE NOW
 BEEN REVISED TO REMOVE SUCH FIXTURES.
 THIS WILL NOT BE PERMITTED. THIS WAS GONE OVER
 EXTENSIVELY BEFORE PERMIT ISSUANCE YET THE PLANS HAVE
 NOW BEEN REVISED TO GO BACK TO PREVIOUS COMMENTS.
 NFPA-101 7.8.1.3, 7.9.2.1, 7.9.2.2, FBC 1006, NEC
 700.12B3 ETC
  
 5) NOTE: PLEASE BE SURE ALL ITEMS IN THE INPUT DATA
 REPORT COORDINATES WITH *ALL* LIGHTING ON PLANS. ISSUED
 PERMIT WAS BASED ON SOME ERRORS HOWEVER BASED ON THE
 FBC 13-103.3 STATES WITHOUT GROSS ERRORS.
 AS THERE HAS BEEN NUMEROUS FIXTURES ADDED, TYPES OF
 FIXTURES REVISED, TYPES OF FIXTURES TO BE REVISED AND
 ACTUAL REMOVAL OF SEVERAL OTHER FIXTURES THE PLANS AND
 CALCULATIONS NEED TO COORDINATE COMPLETELY.
 ** ONE EXAMPLE WOULD BE FIXTURES ON PREVIOUS
 CALCULATIONS WHICH WERE 85VA ARE NOW 58 VA WHICH IS OK,
 HOWEVER THIS DOES NOT COORDINATE WITH THE FIXTURE
 LEGEND.
 ** FOR EXAMPLE: FIXTURES IN AREAS AND ROOMS ON PLANS
 NEED TO MATCH THE IDR. ONE LOCATION ALONE WOULD BE ROOM
 105.
  
 6) NOTE: TO DATE OF THIS REVIEW NO LOW VOLTAGE PERMIT
 APPLICATION HAS BEEN SUBMITTED. PLEASE KNOW THAT THE
 LOW VOLTAGE SCOPE OF WORK ON PLANS NEEDS TO BE UNDER A
 SEPARATE PERMIT AS NOTED ON ORIGINAL REVIEWS.
 PERMIT FEE BASED ON THE LOW VOLTAGE VALUATION WOULD BE
 REQUIRED AT THE TIME OF PERMIT APPLICATION.
  
 7) NOTE: PLEASE SEE PREVIOUS PROVISO ISSUANCE OF
 9/29/08. NO SELECTIVE COORDINATION STUDY, TIME CURVES
 ETC HAVE BEEN SUBMITTED TO DATE. PLEASE SEE 700.27,
 701.8, 240.12, NFPA-110 6.5.1 ETC
  
 8) NOTE: PLEASE BE SURE ALL PLANS AS NOTED ABOVE HAVE
 ALL REVISIONS LABELED WITH CLOUDS AND TRIANGLES. THERE
 ARE SEVERAL LOCATIONS WHERE THE PLANS CONTAIN CLOUDS
 YET THERE IS NO IDENTIFICATION OF THE REVISIONS TO
 COORDINATE WITH THE TITLE BLOCKS. SEE SHEET E341 FOR
 EXAMPLE;
 FBC 106.1.1,106.1.2, 106.5.
 NEC 2005, 240, 310, 220 ETC CHAPTERS GIVEN IN GENERAL
 FOR COORDINATION.
  
 9) NOTE: RISER DIAGRAM HAS BEEN COMPLETELY REVISED TO
 NOW INCLUDE A NEW PANEL HPE-1 400AMP YET NO PANEL
 SCHEDULE FOR LOADS ETC WAS SUBMITTED.
 PLEASE SEE 700.9 FOR WIRING OF LIFE SAFETY SYSTEMS WITH
 OTHER SYSTEMS. WHAT TYPE OF PANEL IS HPE?
 WITH THIS REVISION IF YOU LOSE THE 150KW GENERATOR AND
 THE NEW 40KW UNIT HANDLES THE LIFE SAFETY LOADS, WHAT
 TAKES CARE OF THE LEGALLY REQUIRED ITEMS? (701 LOADS).
 THIS COMMENT ALONG WITH SEVERAL OTHERS ABOVE NEED TO BE
 GONE OVER AS SOON AS POSSIBLE AS THE DESIGN CHANGES
 WILL HAVE A MAJOR IMPACT OF THE BUILDING CONSTRUCTION
 TIME FRAME.
  
  
 **** IMPORTANT> ANY SHEETS WHICH DID NOT NEED TO HAVE
 CHANGES MADE NEED TO BE PLACED BACK INTO THE SETS WHEN
 RESUBMITTING THE REVISIONS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-09-29 Cont ID  
Sent By dpalmer Date 2008-09-29 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2008-09-29 Time 13:33 Sent To  
Notes
2008-09-29 13:35:10ELECTRICAL PLANS STAMPED IN ALL THREE SETS.
 LOW VOLTAGE SYSTEMS WILL BE UNDER SEPARATE PERMIT(S)
 HOWEVER MAY REFERENCE MAIN PERMIT NUMBER FOR TURN
 AROUND PERMIT.
2008-09-29 13:34:17 
 ** PROVISO/REDLINED **
  
 1) NOTE: EMERGENCY SYSTEMS AS SHOWN ON RISER FOR ATS
 NOTED FOR ELEVATOR IS NOT A SYSTEM UNDER NEC 700.
 PLEASE KNOW THIS MAY BE A SYSTEM AS NOTED FOR 701. ALL
 LIFE SAFETY ITEMS ARE UNDER POWER BACK UP OTHER THAN
 THE GENERATOR FOR LIFE SAFETY.
 UPON CONVERSATION WITH THE DESIGNERS OF RECORD THE
 BATTERY BACK UP LIGHTING ADDED IN MANY AREAS WILL NO
 LONGER BE BATTERY BACK UP AND AN ADDITIONAL GENERATOR
 MAY BE ADDED AT LATER DATE FOR OCCUPANCY UNDER
 GENERATOR POWER.
  
 2) NOTE: PLEASE SEE ROOM #168 ON E141 WHICH INDICATES A
 STANDARD SWITCH DEVICE. NEEDS OCCUPANCY SENSOR TYPE
 DEVICE. 13-415.1.ABC.1.2.
  
 3) NOTE: SELECTIVE COORDINATION STUDAY WILL BE REQUIRED
 FOR ALL EMERGENCY/LEGALLY REQUIRED SYSTEMS.
 700.27,701.8, 240.12 AND NFPA-110 SECTION 6.
  
 ** THE ABOVE NOTES ARE BASED ON INFORMATION THE RISER
 AND SYSTEM DESIGNATIONS WILL BE REVISED AND SUBMITTED
 WITHIN 30DAYS OF ISSUANCE OF PERMIT.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 17:46 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2008-09-24 17:48:08*** PASSED REVIEW STOP FOR PERMIT ISSUANCE ONCE ALL
 TRADES ARE OK.
  
 ** PROVISO NOTES TO FOLLOW ON 9/29.
 ** PROCESSING AND STAMPING OF PLANS ALSO TO FOLLOW ON
 9/29.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-17 Cont ID  
Sent By dpalmer Date 2008-09-17 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2008-09-17 Time 15:50 Sent To  
Notes
2008-09-17 15:51:01 
 ** DENIED REVIEW **
  
 *** PLANS ARE IN FAILED STATUS**
 *** NEW SHEETS WILL BE REQUIRED. AT THIS TIME A FINAL
 LIST OF NEW SHEETS CAN NOT BE DETERMINED AT THIS TIME
 BASED ON COMMENT NUMBER ONE BELOW.
  
 1) NOTE: LIGHTING FOR ALL AREAS OUT AND AWAY FROM THE
 BUILDING INCLUDING OUT OF THE GARAGE IS CONSIDERED LIFE
 SAFETY REQUIRING EGRESS LIGHTING. IF THE GENERATOR AS
 NOTED WILL NO LONGER BE FEEDING LIGHTING FOR EGRESS
 BACK UP IN AREAS SUCH AS THE GARAGE EGRESS PATHS WILL
 REQUIRE BATTERY BACK UP OF SOME SORT. THE GENERATOR
 WOULD NO LONGER BE A *LIFE SAFETY/EMERGENCY* GENERATOR
 BY DEFINITION.
 PLEASE SEE NFPA-101 7.8, 7.9.
 CALLED MR. ERDMAN FROM NELSON-RUDIE AND WENT OVER MANY
 SCENARIOS.
 THE RISER STILL INDICATES THERE BEING A LIFE SAFETY/
 EMERGENCY ATS AND SYSTEM. HOW CAN THE GENERATOR BE
 CONSIDERED A LIFE SAFETY SYSTEM?
 PLEASE SEE DEFINITIONS OF NFPA-110, NFPA-70,
 700.1,701.1, AND WIRING OF SYSTEMS IN 700.9, 701.10
 ETC.
 NOTES ON PLANS WOULD NEED TO BE CHANGED, RISER,
 LIGHTING ETC. A PHONE CONFERENCE AT LENGTH MAY BE
 NEEDED ONCE ARCHITECT AND ENGINEER CONTACT EACH OTHER
 TO GO OVER ITEMS BROUGHT UP.
 *** PLEASE SEE DEFINITIONS OF SYSTEM AS NOTED ABOVE.
  
 2) NOTE: NO GROSS ERRORS ON INPUT DATA REPORT AS
 SUBMITTED AS NOTED IN 13-103.3
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-18 Cont ID  
Sent By dpalmer Date 2008-08-18 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2008-08-14 Time 14:55 Sent To  
Notes
2008-08-14 17:05:24 
  
  
  
  
 ** DENIED REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
  
 1) NOTE: PLANS STILL SUBMITTED ONLY FOR PLAN REVIEW AND
 NOT SUBMITTED UNDER PERMIT APPLICATION AT THIS TIME.
  
 2) NOTE: PLEASE BE SURE TO GO THROUGH THE SUBMITTED
 ENERGY CALCULATIONS AND COORDINATE ALL INFORMATION WITH
 PLANS.
 ON THE PREVIOUS REVIEW ONE OF THE EXAMPLES GIVEN WAS
 THE FACT MANY OF THE EXTERIOR LIGHTS SHOWN ON PLANS WAS
 NOT IN THE INPUT DATA REPORT. THE RESPONSE FORM THE
 DESIGN TEAM IS THAT THE EXTERIOR LIGHTS ARE LOCATED IN
 THE EXTERIOR SECTION OF THE INPUT DATA REPORT. THIS
 OFFICE/REVIEWER IS AWARE OF WHERE THE EXTERIOR LIGHTS
 ARE SHOWN IN AN INPUT DATA REPORT. THE COMMENT WAS IN
 FACT THE LIGHTING SHOWN ON THE PLANS FOR ALL EXTERIOR
 LIGHTS DID NOT MATCH WITH THE LIGHTING SHOWN IN THE
 INPUT DATA REPORT.
 PLEASE SEE THE FIXTURE SCHEDULE AS THERE ARE FIXTURES
 LISTED AND ON PLANS WHICH ARE NOT IN THE INPUT DATA
 REPORT FOR EXTERIOR LIGHTS.
 ONE EXAMPLE IS THE 94 WATT FIXTURE AS NO FIXTURES IN
 THE IDR ARE 94WATTS.
 ANOTHER IS THE COUNT OF THE 50WATT FIXTURES AS THE
 PLANS SHOW MORE THAN THE 6 WHICH IS INDICATED IN THE
 IDR.
 ** THIS IS ONLY A COUPLE AS NOTED FOR DESIGN
 BENEFIT.
  
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3 13-400.A.3
  
 3) NOTE: PLEASE SEE NFPA-101 7.8.1.3 AS NOTED ON
 PREVIOUS REVIEWS. ALL STAIRS ARE REQUIRED TO CONTAIN AT
 LEAST 10FT CANDLES UNDER NORMAL CONDITIONS AND IS
 PERMITTED TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS. PLEASE SEE SHEET ULEN WHICH IS A NEW SHEET
 PROVIDED. PLEASE SEE THE LEVELS SHOWN UNDER NORMAL
 CONDITIONS ARE IN FACT ABOUT 10 TIMES LESS THAN THE
 MINIMUM REQUIRED BY THE LIFE SAFETY CODE.
 ALL LEVELS MUST MEET MINIMUM.
 PLEASE SEE THE EDC STAIRS. THE PLANS INDICATE SOME SORT
 OF EMERGENCY LEVEL HOWEVER THE SECTION OF THE PLANS FOR
 THE FRONT EDC STAIRS IS NOT READABLE AND ONLY SHOWS
 EMERGENCY LEVELS.
 ** KEEP NOTE** THE LIGHTING LEVELS OF OTHER AREAS SHALL
 NOT BE FIGURED INTO THE EQUATION OF AVERAGE.
  
 ** THE PREVIOUS REVIEW REQUESTED A LETTER FROM TARGET
 CORPORATE OFFICES THAT THE STORE WILL NOT BE OCCUPIED
 UNDER EMERGENCY POWER. THE RESPONSE MENTIONS TO SEE
 LETTER FROM TARGET CORPORATION.
 THE LETTER SUBMITTED IS NOT FROM TARGET CORPORATE
 OFFICER.
 THE LETTER STATES THAT TARGET TEAM SHALL EVACUATE ALL
 OCCUPANTS AND THE BUILDING WILL NOT BE *PUBLICLY
 OCCUPIED*.
  
 ** THE LIFE SAFETY CODE DOES NOT ONLY ADDRESS THE
 PUBLIC IS ALSO ADDRESSES THE SAFETY OF ALL EMPLOYEES.
 THE DOCUMENTS SHALL BE FROM TARGET CORPORATE BEING ONE
 OF THE CORPORATION ATTORNEYS/OFFICERS AND IT SHALL
 STATE ALL OCCUPANTS INCLUDING EMPLOYEES SHALL EVACUATE
 OR PLACE BATTERY BACK UP FIXTURES IN EGRESS AREAS
 MEETING THE MINIMUM LEVELS UNDER EMERGENCY EGRESS.
  
 LS 101 7.8, 7.9
  
 4) NOTE: PLEASE PROVIDE INFORMATION WHERE THE RATING
 BETWEEN THE EPSS EQUIPMENT AND OTHER NORMAL EQUIPMENT
 IS SHOWN. THE RESPONSE MENTIONS THE 1HR SEPARATION IS
 PROVIDED HOWEVER BASED ON PLANS AND COORDINATION OF
 SUPPORTING DOCUMENTS THIS COULD NOT BE LOCATED.
 NFPA-110 7.2
  
 5) NOTE: PLEASE SEE COMMENT #18 FROM PREVIOUS REVIEW.
 THE RESPONSE PACKAGE CONTAINS SPECS/CUT SHEETS FOR TYPE
 OF DEVICE WHICH SNAPS ONTOTHE BREAKER. THE RESPONSE
 MENTIONS DISCONNECTS WERE ADDED. IF DISCONNECTS WILL BE
 USED AND NO PROPOSAL OF SOME SORT OF DEVICE BEING ADDED
 TO BREAKER IS GOING TO BE PROPOSED PLEASE REMOVE FROM
 PACKAGE AND ANY OTHER PLANS/DOCUMENTS.
  
 422.30.31.110.3.90.7. ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-23 Cont ID  
Sent By dpalmer Date 2008-06-23 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 17:09 Sent To  
Notes
2008-06-23 17:08:31** DENIED2ND PLAN REVIEW**
  
 ** PLAN REVIEW ONLY.
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. SOME OF THESE
 ARE THE SAME NOTES, COMMENTS AND/OR CODE SECTIONS.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS DUE TO ITEMS
 BEING CHANGED OR PLACED ON THE PLANS FOR THE FIRST
 TIME.
  
 ** PLEASE SEE THERE ARE ALSO NEW COMMENTS.
  
 ** AS STATED ON PREVIOUS REVIEW THERE WERE SOME ITEMS
 NOT YET SUBMITTED IN WHICH A REVIEW OF THOSE ITEMS
 COULD NOT BE DONE.
  
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN
 REVIEW ONLY * FOR A SECOND REVIEW AND HAVE NOT BEEN
 SUBMITTED UNDER PERMIT APPLICATION.
 PLEASE KNOW THAT ONCE ALL ITEMS FOR CODE REVIEWS ARE
 DONE PLANS WILL STILL REMAIN IN FAILED STATS UNTIL
 PERMIT APPLICATION HAS BEEN MADE. VERIFICATION OF
 SEVERAL ITEMS SUCH AS VALID LICENSING ETC IS DONE AT
 TIME OF APPLICATION BEFORE ISSUANCE OF PERMIT(S). THIS
 COMMENT WILL REPEAT AS PERMIT APPLICATION HAS NOT BEEN
 MADE.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 2) NOTE: PLEASE SEE NOTICE AT THE END OF THIS REVIEW
 WHICH IS NOTED AS ** IMPORTANT** ON CORRECT PROCEDURE
 ON RE-SUBMITTING PLANS AND THE REMOVING OF OLD/VOIDED
 SHEETS. IF THERE QUESTIONS PLEASE CONTACT THIS
 REVIEWER.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO EPS
 LEVEL-1 EQUIPMENT WHICH IS NOT PERMITTED TO BE LOCATED
 IN THE SAME ELECTRICAL ROOM AS THE NORMAL ELECTRICAL
 EQUIPMENT. THE RESPONSE MENTIONS TO SEE NEW REVISED
 E355 HOWEVER THE PLANS NOW ONLY SHOW SORT OF DOORS AND
 DASHED LINES. THIS DOES NOT PROVIDE ANY RATINGS OF
 WALLS. THIS DOES NOT PROVIDE ANY LISTED ASSEMBLIES FOR
 WALL. THIS DOES NOT PROVIDE ANY INFORMATION ON DOORS TO
 BE USED. NO WALLS OR DOORS WERE LOCATED ON OTHER TRADE
 PLANS SUCH AS ARCHITECTURAL OR MECHANICAL SHEETS.
 PLEASE SEE THE FOLLOWING TEXT REMAINS FROM PREVIOUS
 REVIEW WITH RESPECT TO NFPA-110 CHAPTER 7.
 PLEASE SEE NFPA-110 7.2, 7.1.3 PLEASE SEE 7.2.2.1 BELOW
 ALSO.
 7.2.1THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE RATING
 OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED OUTSIDE
 THE BUILDING CAPABLE OF RESISTING THE ENTRANCE OF SNOW
 OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY LOCAL
 BUILDING CODES.
 7.2.1.2NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON LOAD SHEDDING
 FOR OTHER SYSTEMS ON EPS LEVEL-1 GENERATOR PER NFPA-110
 7.1.5. WHAT PROVIDES SHEDDING OF NON-EMERGENCY OR ANY
 LEGALLY REQUIRED LOADS?
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 FOUR POLE TRANSFER SWITCHES. THESE ARE NOW SHOWN ON
 RISER AS FOUR POLE YET WHERE IS THE SEPARATELY DERIVED
 GENERATOR GROUNDING PER 250.20, 250.50?
  
 6) NOTE: PLEASE SEE THE FOLLOWING COMMENTS WITH RESPECT
 TO LIGHTING CONTROLS FOR FLORIDA BUILDING CODE CHAPTER
 13 REQUIREMENTS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS IN WHICH
 REQUIRED LIGHTING CONTROLS ARE NOT.
 PLEASE SEE 13-415.1.ABC.1, .1.1, .1.2 , .1.3 AND .1.4.
  
 A) ALL SEPARATE SPACES CONTAINING FLOOR TO CEILING
 HEIGHT PARTITIONS ARE REQUIRED TO CONTAIN ONE OR MORE
 OF THE FOLLOWING FOR SEPARATE SPACE CONTROL. INDIVIDUAL
 OCCUPANCY SENSORS OR AN OVER RIDE DEVICE OF SOME SORT
 TO OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLEASE SEE ROOMS 121,122. RESPONSE MENTIONS TO SEE
 REVISED E-131 HOWEVER IT IS UNCLEAR WHAT WAS REVISED.
 PLEASE SEE SPACES 105, 105A, 103A, 103, 104. AS
 MENTIONS ON PREVIOUS REVIEW THESE ARE SOME EXAMPLES
 ONLY.
  
 B) PLEASE SEE 13-415.1.ABC.1.3 FOR SEPARATE CONTROLS
 REQUIRED FOR DISPLAY/ ACCENT LIGHTING. NO AUTOMATED
 CONTROLS COULD BE LOCATED FOR THESE SPECIALTY LIGHTS.
  
 C) PLEASE SEE 13-415.1.ABC.1.4. WHERE ARE THE LIGHTING
 CONTROLS LOCATED FOR ALL OUTSIDE LIGHTS MEETING THIS
 SECTION?
 PLEASE SEE TWO METHODS AS NOTED PREVIOUSLY. IF A TIME
 CLOCK IS CHOSEN. IT MUST BE ASTRONOMICAL AND MUST HAVE
 A MINIMUM OF 10HR BATTERY BACK UP FOR PROGRAMMING.
  
 D) PLEASE SEE SOME OTHER AREAS IN WHICH STANDARD
 SWITCHES ARE BEING SHOWN. FOR EXAMPLE: PLEASE SEE
 STAIRS TO EDC ROOM #2. PLEASE KNOW ANY AUTOMATED
 CONTROLS WHICH ARE REQUIRED AND ARE LOCATED IN EGRESS
 PATHS SHALL BE FAIL SAFE *ON*>
 PLEASE SEE FBC 1016.1, AND NFPA-101 LIFE SAFETY CODE
 7.8.1.2.2.
  
 E) PLEASE SEE SYMBOL LEGEND WAS NOT UPDATED FOR DEVICES
 ON PLANS.
  
 F) PLEASE SEE THE LIGHTING CONTROLS IN MANY AREAS WHICH
 ARE REQUIRED TO BE AUTOMATED OF SOME KIND ARE SHOWING
 UP AS *MANUAL ON/OFF * ON THE INPUT DATA REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS.
 PLEASE BE SURE TO THE FOLLOWING COMMENTS.
  
 ** AS NOTED ON PREVIOUS REVIEW SOME OF THE ABOVE
 EXAMPLES ARE GIVEN AS A BENEFIT AND MAY NOT BE IN
 ANYWAY ALL POSSIBLE LOCATIONS.
  
 7) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY
 CALCULATIONS COORDINATE WITH THE PLANS. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
  
 FOR EXAMPLE:
 PLEASE EXPLAIN HOW THE IDR SHOWS *MANUAL ON/OFF* FOR
 LIGHTING WHICH IS REQUIRED TO BE SOME SORT OF AUTOMATED
 SYSTEM OR DEVICE.
  
 FOR EXAMPLE:
 PLEASE SEE THE SPACE FILLED OUT ON THE CERTIFICATION
 SHEET STATES THE PERSON WHO PREPARED THE DOCUMENT AS
 THE FIRM. THE SHEET CALLS FOR THE INDIVIDUAL TO CERTIFY
 THE SUBMITTED CALCULATIONS HOWEVER THE PRINTED NAME AND
 SIGNATURE IS NOT LOCATED ON THE SUBMITTED ENERGY
 CALCULATIONS. THESE WERE NOT SIGNED, DATED OR SEALED AS
 REQUIRED.
 PLEASE SEE FBC 13-103.1 AS THESE SHALL BE DONE BY THE
 ENGINEER WHO PREPARED CALCULATIONS.
 PLEASE BE SURE TO ALSO SEE FAC 61G15-23.002, FS 471.025
 AS THIS REQUIRES ALL DOCUMENTS PREPARED BY AN ENGINEER
 TO BE SIGNED, DATED AND SEALED ACCORDINGLY.
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEW TRADES.
  
 FOR EXAMPLE:
 PLEASE COORDINATE THE NUMBER AND KW RATINGS OF ALL
 ELECTRIC WATER HEATERS ON PLANS/PANEL SCHEDULES WITH
 THAT OF THE SHOWN ON THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL ITEMS ON EXTERIOR LIGHTING
 WHICH IS SHOWN ON PLANS WHICH DO NOT SHOW UP ON THE IDR
 AND OTHER WHERE THE NUMBER AND WATTAGE OF FIXTURES DO
 NOT CORRELATE.
 PLEASE SEE MISSING FIXTURES X-3, X-5, X-6, H1, H1A
 ETC.
 PLEASE SEE THERE ARE MANY ITEMS ON ELECTRICAL PLANS
 WHICH ARE NOT IN THE IDR.
 PLEASE ALSO SEE THE FOLLOWING COMMENT WITH RESPECT TO
 THE SITE LIGHTING PLANS AND COORDINATION NEEDED.
  
 FOR EXAMPLE:
 PLEASE GO OVER ALL INTERIOR LIGHTING. MOST ARE IN GOOD
 SHAPE HOWEVER AS THE FIXTURE LEGEND IS NOT COMPLETE
 WITH SOME LIGHTING FOR SPECIALTY LIGHTS AND FIXTURES
 SUCH AS S-1, MANY COULD NOT BE VERIFIED.
  
 ** THESE ARE A FEW EXAMPLES ONLY AND MAY IN NO WAY BE
 AN EXHAUSTED LIST. THESE EXAMPLES WERE GIVEN AS A
 BENEFIT TO CLEARLY COORDINATE **ALL ** LIGHTING ON
 PLANS WITH THE IDR.
  
 8) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL
 SITE LIGHTING PLANS WITH THE SL PLANS WHICH ARE IN THE
 CIVIL SETS. AS THE LIGHTING IS A REQUIRED DESIGN
 PARAMETER UNDER FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 FOR THE ENGINEER THESE ARE REQUIRED TO BE
 COMPLETED AT THIS TIME.
 PLEASE SEE THE NUMBER OF FIXTURES AND LOCATIONS COULD
 NOT BE CONFIRMED AS THE SITE SHEETS WERE NOT THE SAME.
 PLEASE SEE THE SL PLANS AS THESE CONTAIN FIXTURES AND
 OTHER LOCATIONS WHICH WERE NOT CLEARLY VISIBLE OR
 READABLE. PLEASE SEE THE FOLLOWING COMMENT FOR MINIMUM
 SCALE AND DETAILS NEEDED.
 PLEASE SEE THE OUTSIDE LIGHTS ON THE ELECTRICAL PLANS
 FOR WALL PACKS, POLES ETC NEED TO COORDINATE. PLEASE
 SEE COMMENTS WITH RESPECT TO LIGHTING FOR LIFE SAFETY
 CODE AS WELL.
 FBC 106.1.2 FOR COORDINATION.
  
 9) NOTE: PLEASE SUBMIT PLANS WITH A MINIMUM OF 1/8 INCH
 SCALE. THE 1/16 TH INCH SCALE IS OK AS LONG AS THERE
 ARE OTHER SHEETS WHICH PROVIDE THE LARGER DETAIL. THIS
 IS CLEARLY AN ISSUE AS THE COMMENT #8 ABOVE FINDS
 INCONSISTENCIES IN PLANS WHICH ARE NOT EASILY READ.
 PLEASE SEE SHEETS E110 AND E11 AS SOME OF THESE SMALLER
 AREAS ARE NOT SHOWN ON ANY OTHER LOCATION ON PLANS.
 MOST CAN BE READ ON THESE TWO SHEETS BUT NOT ALL AND
 THE MINIMUM IS REQUIRED. FBC 106.1.3 ADMIN SECTION.
  
 10) NOTE: THE PLANS AND RESPONSE LETTERS MENTIONS THIS
 BUILDING WILL NOT BE OCCUPIED IN EMERGENCY. THIS SHOULD
 BE STATED THIS WILL BE UN-OCCUPIED UNDER EMERGENCY
 POWER. THIS BUILDING WILL BE REQUIRED TO EVACUATE IN
 THE ONE AND HALF HOUR TIME FRAME. PLEASE OBTAIN A
 LETTER FROM CORPORATE WHICH STATES AN UNDERSTANDING
 THAT THIS STORE SHALL REMAIN CLOSED IN THE EVENT OF A
 POWER FAILURE. ( OR WORDS TO THAT AFFECT).
 A NOTICE AND HOLD WILL BE PLACED ON LAND FILE AND
 LETTER WILL REMAIN PERMANENTLY ON FILE FOR THIS
 LOCATION.
  
 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 SOME WERE SUBMITTED FOR SOME AREAS HOWEVER THERE ARE
 OTHER AREAS SUCH AS THE REAR STAIRS WHICH DO NOT SHOW
 *ANY* LIGHTING LEVELS FOR EITHER NORMAL OR EMERGENCY.
 PLEASE SEE THE SUBMITTED SHEETS LLE AND ULE CLEARLY
 STATE THE SHEETS ARE NOT TO BE USED FOR CONSTRUCTION
 AND ARE NOT SIGNED, DATED OR SEALED BY THE RESPONSIBLE
 DESIGNER OF RECORD. THESE SHEETS ALSO CONTAIN A NOTE
 WHICH MENTIONS THESE LEVELS ARE THE LEVELS UNDER
 BATTERY. HOW IS THIS POSSIBLE WHEN DOZENS OF THESE
 FIXTURES CONTAIN NO BATTERY BACK UP AT ALL?
 PLEASE SEE THE RESPONSE ALSO MENTIONS THE NORMAL LEVELS
 OF LIGHTING ARE NOT PROVIDED BECAUSE THE INTERPRETATION
 IS THAT THE DESIGN MEETS CODE. THIS IS NOT ACCEPTABLE
 IN LIEU OF SUBMITTING, SHOWING AND TAKING
 RESPONSIBILITY OF THE *MINIMUM* LIGHTING LEVELS AS
 REQUIRED UNDER THE LIFE SAFETY CODE.
 IT IS THE RESPONSIBILITY OF THE DESIGN PROFESSIONAL TO
 ACHIEVE MINIMUM LEVELS AND SHOW ON PLANS FOR DESIGN.
 PLEASE SEE FAC 61G15-33.004.
 **
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR *ALL* EGRESS
 AREAS UNDER BOTH NORMAL AND EMERGENCY CONDITIONS. THE
 AREAS SUCH AS STAIRS SHALL SHOW LIGHTING LEVELS OF 10FT
 CANDLES AT *ALL * WALKING SURFACES ON STAIRS.
 THESE LEVELS ARE PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY. PLEASE SEE PREVIOUS COMMENTS AS ALL STAIRS
 ARE REQUIRED TO CONTAIN BATTERY BACK UP FIXTURES FOR
 THE MINIMUM OF 1FT CANDLE.
 ** THIS IS ALSO TO INCLUDE THE REAR STAIRS WHICH
 CURRENTLY DO NOT SHOW ANY LEVELS AND FOR ALL OTHER
 STAIRS WHICH ONLY SHOW UNDER EMERGENCY.
 WHAT ABOUT STAIRS FROM EDC ROOM? NO LEVELS UNDER EITHER
 CONDITION?
 PLEASE BE SURE TO INDICATE THE *BATTERY BACK UP* OR
 *EMERGENCY BALLAST* ON FIXTURE LEGEND FOR FIXTURES AS
 REQUIRED.
 NFPA-101 2003 7.8, 7.9. 7.8.1.3, 7.9.2.2.
 ** PREVIOUS REVIEW**
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 NOTES REQUIRED TO BE ADDED TO PLANS PER
 13-413.A.ABC.2.1 AND .2.2. THE RESPONSE MENTIONS NOTES
 ADDED TO E000 WHICH WERE LOCATED ON PLANS HOWEVER THE
 WORDING AS SHOWN IN THE FLORIDA BUILDING CODE WAS NOT
 ON PLANS. THIS WAS CONFIRMED WITH DCA (DEPARTMENT OF
 COMMUNITY AFFAIRS) PREVIOUSLY THAT THE WORDING LOCATED
 IN THE CODE IS THE WORDING WHICH IS TO BE LOCATED ON
 PLANS.
 PLEASE ADJUST.
  
 13) NOTE: PLEASE SEE THE SIZE OF THE FEEDERS FROM THE
 SERVICE EQUIPMENT MAIN TO THE MAIN DISTRIBUTION
 SWITCHBOARD DO NOT MEET THE MINIMUM SIZE PER 310.16,
 240.4B. PLEASE SEE THE CONDUCTOR SHALL BE AT OR ABOVE
 THE OVER CURRENT PROTECTION WHICH IS PROTECTING THE
 CONDUCTORS.
 (MAY NOT USE THE 90 DEGREE COLUMN UNLESS ALL EQUIPMENT,
 LUGS ETC MEET 90 DEGREE TEMP RATINGS)
 PLEASE SEE 110.14.
 NEW COMMENT>
  
 14) NOTE: PLEASE SEE 250.24, 250.6 AS THE GROUNDING
 ELECTRODE SYSTEM SHALL BE ATTACHED TO THE FIRST MEANS
 OF DISCONNECT WHICH IS THE SERVICE EQUIPMENT MAIN
 LOCATED OUTSIDE.
 PLEASE ADJUST RISER GROUNDING ELECTRODE SYSTEM AND
 DETAIL.
 PLEASE BE SURE TO SEE NOTE ABOVE WITH RESPECT TO THE
 GENERATOR AND SEPARATELY DERIVED SYSTEMS.
 NEW COMMENT>
  
 15) NOTE: PLEASE SEE 250.24, 250.110, 250.122 ETC AS
 THE EQUIPMENT GROUNDING CONDUCTOR IS MISSING ON THE
 CONDUIT FROM THE MAIN TO THE MAIN SWITCHBOARD. (MDS).
 PLEASE SEE FEEDER SCHEDULE 18A.
 NEW COMMENT>
  
 16) NOTE: PLEASE SEE THE NEW DISCONNECTS WHICH WERE
 ADDED FROM PREVIOUS REVIEW NOTES WITH RESPECT TO THE
 DISCONNECTING MEANS REQUIRED PER 225.31-225.39,
 700.12B6, 702.11 ARE NOT RATED FOR THE CIRCUIT IN WHICH
 THEY ARE A PART OF. PLEASE SEE THE BREAKER AND OVER
 CURRENT PROTECTION ON THE GENERATOR IS HIGHER THAN THE
 RATING OF THESE NEW DISCONNECTS.THE RISER SHOWS BOTH
 AS 60A RATED WHEN THESE ARE WITHIN 100AMP CIRCUITS TO
 EMERGENCY LOADS.
 PLEASE SEE THAT ALL EQUIPMENT SHALL BE LISTED AND RATED
 FOR THE LOAD SERVED.225.39, 110.3, 90.7.
  
 17) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO THE ELEVATOR PIT LIGHTING LEVELS TO MEET
 620.23, ASTMA17.1-2004 YET NO LEVELS WERE SHOWN. THE
 RESPONSE MENTIONS THE FIXTURE WAS CHANGED ON LEGEND.
 HOW DOES THIS ADDRESS THE COMMENT?
 WHERE ARE THE LIGHTING LEVELS SHOWN?
  
 18) NOTE: PLEASE SEE THE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO THE HANDLE PROPOSED *LOCK OFF DEVICE*. THE
 SUBMITTED MANUFACTURES SPEC/CUT SHEET IS NOT AN
 ACCEPTABLE DEVICE IN LIEUOF THE DISCONNECT REQUIRED
 AND DOES NOT MEET THE PERMANENT MEANS.
 THIS ARE NOT LISTED FOR PERMANENT INSTALLATIONS!!
 110.3.
 ** PLEASE KNOW THE NEW NEC 2008 WILL CLARIFY THE CODE
 AND THE INTENT.THIS WILL CLEARLY STATE THAT IT WAS
 NEVER THE INTENT TO ALLOW *HANDLE LOCK OFF DEVICES* IN
 LIEU OF THE REQUIRED DISCONNECTING MEANS.
 IN ANY CASE MOST *LOCK OFF*, *LOCK OUT/TAG OUT* DEVICES
 ARE FOR TEMPORARY INSTALLATIONS ONLY. MOST ARE NOT
 LISTED FOR PERMANENT MEANS.
 ** PLEASE ADJUST PLANS ACCORDINGLY FOR DISCONNECTS
 ETC.
 110.3, 90.7
 FBC
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2008-06-20 17:09:411ROLL AND BOOKS IN ELEC FOR REVIEW.
 REVIEW TO COMMENCE ON 6/23

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 19:05 Sent To  
Notes
2008-03-08 14:40:072008-03-08 14:40:07
  
 ** DENIED REVIEW**
  
 ** PLAN REVIEW
 SUPER TARGET
 1760 PALM BEACH LAKES BLVD.
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW AND SOME ITEMS NOT YET ON PLANS A
 REVIEW OF ONLY THE DOCUMENTS SUBMITTED CAN BE DONE AT
 THIS TIME. THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN
 REVIEW ONLY * AND HAVE NOT BEEN SUBMITTED UNDER PERMIT
 APPLICATION. PLEASE KNOW THAT ONCE ALL ITEMS FOR CODE
 REVIEWS ARE DONE PLANS WILL STILL REMAIN IN FAILED
 STATS UNTIL PERMIT APPLICATION HAS BEEN MADE.
 VERIFICATION OF SEVERAL ITEMS SUCH AS VALID LICENSING
 ETC IS DONE AT TIME OF APPLICATION BEFORE ISSUANCE OF
 PERMIT(S).
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 2) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WIRING SHALL
 BE UNDER SEPARATE PERMITS FROM THE MAIN ELECTRICAL
 PERMIT. THE LV FOR PHONE, CATV AND OTHER SYSTEMS NOT
 INCLUDING LV FOR SECURITY MAY BE ALL UNDER ONE LV
 PERMIT. THE SECURITY SYSTEM IS A SEPARATE LV PERMIT
 FROM OTHERS LISTED ABOVE. IN EITHER CASE AS ALL LOW
 VOLTAGE SYSTEMS ARE SHOWN ON BASE BUILDING PLANS, THE
 APPLICANT MAY REFERENCE THESE PLANS FOR A *TURN-AROUND*
 PERMIT.
 ** THIS IS GIVEN FOR INFORMATIONAL PURPOSE AND IF THERE
 ARE ANY QUESTIONS ON THIS ITEM PLEASE CONTACT THIS
 REVIEWER.
  
 3) NOTE: PLEASE SEE NOTICE AT THE END OF THIS REVIEW
 WHICH IS NOTED AS ** IMPORTANT** ON CORRECT PROCEDURE
 ON RE-SUBMITTING PLANS AND THE REMOVING OF OLD/VOIDED
 SHEETS. IF THERE QUESTIONS PLEASE CONTACT THIS
 REVIEWER.
  
 4) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS AS WELL AS
 COVER SHEET ON ARCHITECTURAL COVER SHEETS CONTAIN THE
 FOLLOWING CODES. SOME OF THESE MAY ALREADY BE LISTED
 HOWEVER NOT ALL AT BOTH PLACES. THESE MAY BE ON THE
 FIRST E-SHEET AND NOT ON ALL SHEETS.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA_70
 2003 NFPA-101
 2002 NFPA-72
 2002 NFPA-110
 2003 NFPA-20 (NOT YET DETERMINED)
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH ALSO
 MAY REQUIRE SPECIFIC CODES TO BE LISTED ON PLANS.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, ALL ATS EQUIPMENT, AND FUEL
 TANK.
 PLEASE KNOW THAT A REVIEW OF THE FUEL TANK WILL BE DONE
 BY THE MECHANICAL, FIRE MARSHAL ETC.
 PLEASE SEE COMMENTS BELOW WITH RESPECT TO THE ATS
 UNITS.
 ** PLEASE SUBMIT ANY FIRE PUMP AND FIRE PUMP
 CONTROLLERS SPECS/CUT SHEETS AS WELL IF THIS BUILDING
 WILL CONTAIN ANY SUCH UNITS. PLANS DID NOT SEEM TO
 CONTAIN ANY FIRE PUMP ETC AND A REVIEW OF MANY ITEMS
 COULD NOT BE DONE IF THIS BUILDING IS GOING TO CONTAIN
 A FIRE PUMP.
 IF APPLICABLE PLEASE SEE NFPA-20, CHAPTERS 9 AND 10.
  
 6) NOTE: PLEASE SEE THE EMERGENCY LIFE SAFETY EQUIPMENT
 IS NOT PERMITTED IN THE SAME ROOM(S) AS THE NORMAL
 ELECTRICAL EQUIPMENT. PLEASE SEE NFPA-110 7.2, 7.1.3
 PLEASE SEE 7.2.2.1 BELOW ALSO.
 7.2.1THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE RATING
 OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED OUTSIDE
 THE BUILDING CAPABLE OF RESISTING THE ENTRANCE OF SNOW
 OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY LOCAL
 BUILDING CODES.
 7.2.1.2NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
  
 7) NOTE: PLEASE SEE 230.95, 240.13 AS THESE SECTIONS OF
 THE CODE AMONG OTHERS REQUIRED GROUND FAULT PROTECTION
 (GFP) ON THE SERVICE. THE PLANS CLEARLY SHOW THE GFP
 PROTECTION REQUIRED HOWEVER PLEASE SEE 700.6D, 700.26
 AND NFPA-110 6.2.15. AS THE CODE REQUIRES GFP ON NORMAL
 SIDE AND REQUIRES GF SENSING ON THE EMERGENCY SIDE THE
 ISOLATION OF THE SYSTEMS AND NEUTRALS IS IMPERATIVE.
 PROVISIONS SHALL BE INCLUDED FOR ENSURING CONTINUITY,
 TRANSFER, AND ISOLATION OF THE PRIMARY AND THE EPS
 NEUTRAL CONDUCTORS WHEREVER THEY ARE SEPARATELY
 GROUNDED TO ACHIEVE GROUND-FAULT SENSING.
 PLEASE SEE THE FOLLOWING INFORMATION GIVEN IS SECTIONS
 REMOVED FROM WHITE PAPERS AS WELL FROM TWO MANUFACTURES
 OF TRANSFER SWITCHES AND GENERATORS. THIS MAY HELP IN
 PROVIDING THE NEEDED EQUIPMENT AND ADJUSTMENT SO THE
 PLANS AND RISER.
  
 ** ** ASCO WHITE PAPER EXCERPT***
 **WHERE GROUND FAULTPROTECTION IS TRIGGERED BY THE
 CODE AND AN ALTERNATE POWER SUPPLY IS INCLUDED,
 SWITCHING OF THE NEUTRAL BECOMES NECESSARY. THE CIRCUIT
 SHOWN ABOVE ILLUSTRATESSUCH A CIRCUMSTANCE. THE
 SERVICE IS LARGER THAN 1,000 AMPS. CONSEQUENTLY, GROUND
 FAULT PROTECTION IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF ITIS INSTALLED THERE AND
 THE GENERATOR NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL, A GROUND FAULT
 WHEN THE GENERATOR ISFEEDING THE LOAD WILL CAUSE THE
 MAIN SERVICE DISCONNECT TO OPEN. THIS WILL NOT
 DISCONNECT THE ARCING FAULT FROM THE GENERATOR.
 COORDINATION IS THUSLOST."
  
 *****CATERPILLAR WHITE PAPER EXCERPT***
 SHOULD THE DESIGNER WANT TO GROUND THE GENERATOR AND
 STILL ADHERE TO CODE AND AVOID THE PROBLEMS
 OF SPLIT RETURN PATHS AND IMPROPER GFP SENSING
 THE USE OF A FOUR POLE TRANSFER SWITCH IS CALLED FOR.
 FOUR POLE TRANSFER SWITCHES
 FOUR POLE SWITCHES ARE EMPLOYED TO INSURE
 THAT THE GENERATOR CAN BE GROUNDED WITHOUT COMPROMISING
 THE NEC. THAT IS, THE GEN SET
 CAN BE WIRED AS A SEPARATELY DERIVED SYSTEM BY
 GROUNDING THE NEUTRAL AT THE GEN SET AS LONG AS THE
 NEUTRAL IS NO LONGER SOLID THROUGH THE TRANSFER SWITCH.
 THIS OF COURSE INFERS THAT NEUTRAL BE SWITCHED AT THE
 SAME TIME AS THE PHASES.
 THIS SCHEME WILL ALSO INSURE GFP OPERATION AS INTENDED.
 FIG. 12 SHOWS A FOUR POLE TRANSFER SWITCH WIRED WITH A
 GEN SET HAVING ITS NEUTRAL GROUNDED AT THE HOUSING. IN
 THIS WIRING THE NEUTRAL RETURN PATH IS DELIBERATELY
 OPEN FOR GROUND RETURN CURRENTS BY THE TRANSFER SWITCH
 CONTACTS. THIS WILL ALSO AVOID NUISANCE TRIPPING IN THE
 CASE OF AN UNBALANCED LOAD. IN EFFECT, THE GEN SET IS
 NOW COMPLETELY ISOLATED FROM THE UTILITY SERVICE AND
 PRESENTS AN EFFECTIVE AND SAFE ALTERNATIVE TO SOLID
 NEUTRAL LINES. A DESIGNER HAS THE TOOLS TO NOW
 CONFIGURE A STANDBY SYSTEM AS EITHER SEPARATELY DERIVED
 OR NOT. IF THE SYSTEM NEEDS ARE FOR NOT GROUNDING THE
 GEN SET AT ITS SITE THEN A THREE POLE TRANSFER SWITCH
 WITH A SOLID NEUTRAL SHOULD BE EMPLOYED. IF THE GEN SET
 NEEDS TO BE GROUNDED AT ITS SITE, THEN A FOUR POLE
 TRANSFER SWITCH MUST BE DESIGNED INTO THE SYSTEM. THIS
 WILL INSURE THAT THE NEUTRAL IS SWITCHED ISOLATING THE
 NORMAL OR UTILITY SUPPLY. LASTLY, SHOULD THE DESIGNER
 DECIDE TO SWITCH THE NEUTRAL, CONSIDERATION TO CONTACT
 RATINGS AND PERFORMANCE SHOULD BE TAKEN INTO ACCOUNT.
 FOURTH POLE AND UL REQUIREMENTS
 AS OF APRIL 1989, UL 1008 REQUIRED THAT THE FOURTH POLE
 OF A TRANSFER SWITCH BE TESTED AND PROVEN TO HAVE
 RATINGS EQUAL TO ITS PHASE CONTACTS IF NOT OF THE SAME
 CONSTRUCTION. AND THAT BUS SPACING IS CLOSER TO LINE
 THAN ITS LINE TO LINE SPACING OR IT HAS A DIFFERENT
 MEANS OF SUPPORT FOR ITS NEUTRAL BUS. THAT MEANS THAT
 THE NEUTRAL CONTACT MUST BE CAPABLE OF WITHSTAND AND
 CLOSE INTO FAULT RATINGS AT LEAST EQUAL TO THE PHASE
 CONTACTS. THE FACT IS, NOT ALL TRANSFER SWITCHES
 EMPLOYING A FOURTH POLE ARE CONSTRUCTED IN LIKE
 FASHION.
  
 AS NOTED ABOVE THE USE OF 4-POLE TRANSFER SWITCHES IS
 NEEDED. PLEASE SHOW ON PLANS THE SEPARATELY DERIVED
 GROUNDING ELECTRODE SYSTEM AT THE GENERATOR.
  
 8) NOTE: PLEASE SEE PANEL LP4 ON THE SECONDARY SIDE OF
 THE TRANSFORMER REQUIRES A MAIN CIRCUIT BREAKER PER
 240.21, 408.36.
  
 9) NOTE: PLEASE COMPLETE ALL INFORMATION ON PLANS AND
 SUPPORTING DOCUMENTS FOR COMPLIANCE WITH THE FBC AND
 CHAPTER 13.
 PLEASE KNOW THE MINIMUM REQUIRES FEDERALLY ADOPTED INTO
 LAW IN JULY 04 WAS THAT ALL STATES ARE REQUIRED TO MEET
 THE MINIMUM OF 1999 ASHRAE 90.1 OR BETTER BY THE NEXT
 CODE CYCLE. PLEASE SEE THE FBC AND CHAPTER 13 FOR ALL
 ITEMS.
 THIS NOTE WILL BE DONE INS SUB-SECTIONS AND THE INPUT
 DATA REPORT WILL BE NOTED AS IDR.
  
 A) PLEASE BE SURE TO SEE 13-415.1.ABC.1.1, .1.2, .1.3
 AND .1.4 FOR ALL LIGHTING CONTROLS REQUIRED. PLEASE SEE
 THERE ARE SEVERAL LOCATIONS WHICH ARE MISSING REQUIRED
 CONTROLS.
 FOR EXAMPLE:
 MISSING SEPARATE SPACES OVER RIDES AND LIGHTING
 CONTROLS.ALL OVER RIDES ARE REQUIRED FOR SYSTEM
 CONTROLS.
 SOME EXAMPLES OFROOMS MISSING REQUIRED CONTROLS:
 143,008,105,105A,108,109,122,168,139 ETC THIS IS NOT
 ALL LOCATIONS AND ONLY GIVING A FEW AS EXAMPLES.
 MISSING LIGHTING ZONES AS REQUIRED.
 MISSING BACK UP TIME FOR OUTSIDE LIGHTING PROGRAMMING
 WHICH CODE SECTION ABOVE REQUIRES A 10HR MINIMUM.
 PLEASE SEE MISSING CONTROLS AND DETAILS FOR OUTSIDE
 LIGHTING.
  
 B) PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLEASE
 PLACE REQUIRED NOTES ON PLANS ACCORDINGLY.
  
 C) PLEASE SEE 13-413.1.ABC.1.1 AND .1.2 AND SUBMIT
 VOLTAGE DROP CALCULATIONS FOR ALL WORST CASE. PLEASE
 SEE THERE ARE BRANCH CIRCUITS AND FEEDERS WHICH ARE IN
 QUESTION DUE TO THE LONGER LENGTHS AS SHOWN ON PLANS.
  
 D) PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES
 WITH THE LIGHTING ON THE IDR SUBMITTED WITH THE ENERGY
 CALCULATIONS. PLEASE KNOW AT THIS TIME THERE ARE
 SEVERAL HUNDRED FIXTURES/LUMINAIRES MISSING FORM THE
 IDR.
 PLEASE SEE FOR EXAMPLE: THE IDR FOR EXTERIOR LIGHTING
 SHOWS NOT ONE FIXTURE. HOW IS THIS POSSIBLE WHEN THERE
 ARE HUNDRED(S) OF LUMINAIRES ONPLANS???
 PLEASE SEE FOR EXAMPLE: THE LIGHTING SHOWN ON THE
 FIXTURE LEGEND DOES NOT CORRELATE WITH THE IDR FOR
 DOZENS OF FIXTURES FOR THE CORRECT WATTAGES. PLEASE SEE
 13-415.2.ABC.1, .1.1, .1.2 AND .1.3 FOR VA RATINGS TO
 BE USED IN CALCULATIONS.
 THIS SHALL INCLUDE ALL ACCENT LIGHTING SUCH AS TRACK
 LIGHTING WHICH IS NOTED SPECIFICALLY IN THE CODES ABOVE
 ALONG WITH THE VA TO BE FIGURED FOR COLD CATHODE
 LIGHTING NOTED ON SPECIALTY LIGHTING PLANS.
  
 E) PLEASE BE SURE TO SHOW AND INDICATE ALL LIGHTING
 FIXTURE DESIGNATIONS ON PLANS. PLEASE SEE SOME
 LOCATIONS DO CONTAIN A NOTE FOR TYPES OF FIXTURES
 HOWEVER MANY AREAS DO NOT CONTAIN DESIGNATIONS WHICH
 COORDINATE WITH THE FIXTURE LEGEND.
 EXAMPLE: ARE 102
  
 F) PLEASE COORDINATE ELECTRICAL WATER HEATERS ON
 PLANS/EQUIPMENT SCHEDULE WITH THAT OF THE UNITS SHOWN
 ON THE IDR. THE IDR APPEARS TO SHOW MORE THAN THE UNITS
 ON EQUIPMENT SCHEDULE.
  
 ** PLEASE SEE THAT THE NOTES ABOVE WITH RESPECT TO FBC
 CHAPTER 13 ARE SOME OF THE ITEMS GIVEN AS EXAMPLES AND
 ARE IN NO WAY ALL ITEMS. PLEASE SEE COMMENTS FROM OTHER
 TRADES FOR THE SAME CHAPTER.
  
 10) NOTE: PLEASE SUBMIT SITE LIGHTING PLANS. UNABLE TO
 REVIEW AT THIS TIME.
 NEC 2005, FBC CHAPTER 13
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 FOR ADDITIONAL
 INFORMATION.
  
 11) NOTE: PLEASE SUBMIT EMERGENCY EGRESS PHOTO-METRICS
 FOR ALL EGRESS PATHS INCLUDING ALL STAIR AREAS. PLEASE
 SEE 7.8.1.3, 7.9.2.2 AS THE LIGHTING LEVELS FOR STAIRS
 UNDER NORMAL CONDITIONS ARE REQUIRED AT 10FT CANDLES
 MINIMUM.
 PLEASE SEE THAT ALL REQUIRED EGRESS PATHS, MAIN
 ELECTRICAL ROOMS, ELEVATOR EQUIPMENT/MACHINE ROOMS ETC
 SHALL CONTAIN BATTERY BACK UP TYPE FIXTURES TO PROVIDE
 THE 1FT CANDLE MINIMUM FOR THE *EGRESS PATHS*. PLEASE
 SEE 7.8.1.2.2 AND 7.8.2.
 COULD NOT LOCATE FIXTURES ON FIXTURE LEGEND WITH THE
 REQUIRED BATTERY BACK UP.
 PHOTO-METRICS ARE REQUIRED AND AS NONE HAVE BEEN
 SUBMITTED AT THIS TIME NO REVIEW CAN BE DONE. FLORIDA
 ADMINISTRATIVE CODE 61G15-33.004
 FBC 106.1.2
  
 12) NOTE: PLEASE PROVIDE GROUND RISE ON ONE-LINE SHEET
 OR OTHER SHEET PER 250.58. ALSO AS NOTED ABOVE WITH
 RESPECT TO THE GENERATOR AND SEPARATELY DERIVED SYSTEMS
 PER 250.20, 250.30. THE NOTE ON RISER SHEET FOR
 TRANSFORMER GROUND IS OK.
  
 13) NOTE: PLEASE INDICATE COLOR CODING FOR THE 277/480V
 SYSTEM AS FOLLOWS.
 BROWN, PURPLE AND YELLOW.
 THIS LOCAL JURISDICTION EXISTINGWIRING SYSTEMS ARE AS
 NOTED ABOVE INCLUDING OTHER LOCAL JURISDICTIONS AS THE
 NEC DOES NOT PROVIDE COLOR CODING NEEDED FOR THESE
 VOLTAGES. THE ORANGE MARKING AS NOTED IN THE NEC IS FOR
 THE HIGH-LEG OF AN OPEN DELTA SYSTEM.
 90.4
  
 14) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE PROPOSED UPS SYSTEM. PLEASE BE SURE
 DOCUMENTS CONTAIN A LISTING FROM A NRTL. (NATIONALLY
 RECOGNIZED TESTING LABORATORY).
 110.3, 90.7.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 15) NOTE: PLEASE SEE NOTE ONE E001 MENTIONS TO SEE E361
 FOR DETAILS ON THE GENERATOR HOWEVER NO DETAILED
 SPECIFIC INFORMATION COULD BE LOCATED.
 PLEASE SEE OCTAGONAL NOTE #15 FOR EXAMPLE.
 PLEASE SEE OTHER SHEETS ON PLANS SUBMITTED CONTAIN
 OTHER NOTES IN BOXES AND OCTAGONAL NOTES HOWEVER THE
 NOTES DO NOT MATCH OR THE NOTE IS NOT ON ANY LEGEND OR
 DETAIL ON SHEET TO LOCATE INFORMATION.
 PLEASE SEE ONE EXAMPLE BESIDES ONE NOTED ABOVE: SHEET
 E210 NOTES 4 AND 6 WHICH ARE IN LISTED NOTED. ONLY ONE
 NOTE/ SQUARE BOX #6 WAS LOCATED ON SHEET, WHERE IS NOTE
 #4?
 OCTAGONAL NOTES ON E355, E14, E17, ???
 ** PLEASE GO THROUGH ALL SHEETS AND UPDATE NOTES, ETC
 THIS NOTES ONLY SOME ITEMS. SOME OTHERS NOTED ABOVE WAS
 THE MISSING FIXTURE DESIGNATIONS OR NOTES/BOXES ETC FOR
 THE FIXTURES.
  
 16) NOTE: PLEASE SEE THE ALARM DEVICE LOCATIONS AS
 NOTED ON PLANS SHEET E-210 MAKE NOTE TO SEE
 ARCHITECTURAL SHEETS FOR LOCATIONS AND DEVICE HEIGHTS.
 THIS REVIEWER COULD NOT READILY LOCATE THESE ON
 ARCHITECTURAL SHEETS. PLEASE PROVIDE DETAILED
 INFORMATION ON THE ELECTRICAL PLANS OR ADD DEVICES TO
 E-SHEETS.
 PLEASE PROVIDE A RESPONSE WHERE THESE ITEMS ARE
 LOCATED.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
 SEE THE NEXT NOTE:
  
 17) NOTE: PLEASE INCLUDE ALL MINIMUM LEVELS FOR FLORIDA
 ADA COMPLIANCE.
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) MORE
 SPECIFICALLY. THE LEVELS FOR ALL DEVICES TO MEET
 MINIMUM ADA LEVELS NEED TO BE NOTED ON PLANS AS WELL AS
 ADJUSTING THE DEVICES NOTED ON PLANS.
 FOR EXAMPLE: STROBES SHOWN AT LEVELS WAY BELOW THE
 MINIMUM LEVELS REQUIRED FOR ADA. (15CD ETC, WHEN
 REQUIRES TO BE 75CD MINIMUM).
  
 18) NOTE: PLEASE SEE FBC 3006.2, .4 ETC AND POSSIBLE
 COMMENTS FROM OTHER TRADES. PLEASE KNOW THE ELEVATOR
 MACHINE ROOMS ARE REQUIRED MEETING INDIVIDUAL AIR
 CONDITIONING AS WELL AS VENTILATION REQUIREMENTS.
 PLEASE SEE NEC 620.21-620.25. AT THIS TIME THERE ARE
 ITEMS IN THESE ROOMS AND OTHER EQUIPMENT WHICH IS
 REQUIRED TO BE ON DEDICATED CIRCUITS YET THEY FEED
 OTHER AREAS. SEE THE FOLLOWING COMMENT WHICH DIRECTLY
 AFFECT THIS NOTE.
 PLEASE SEE FOR EXAMPLE: THE LIGHTING IN THE MACHINE
 ROOM IS REQUIRED TO BE ON A DEDICATE CIRCUIT YET PLANS
 SHOWS THIS SAME CIRCUIT FEEDING OTHER AREAS/ROOMS WHICH
 IS NOT PERMITTED.
  
 19) NOTE: PLEASE SEE THE PLANS SHOWS CIRCUITS FOR MUCH
 OF THE EQUIPMENT FOR ESCALATOR AND ELEVATOR TO A Y1
 PANEL YET NO Y PANEL COULD BE LOCATED IN PANEL
 SCHEDULES OR LOCATED ON RISER. WHAT IS THIS PANEL? NEC
 240.4,310.16, 408, 620 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 20) NOTE: PLEASE SEE 620.213 AND ASME A17.1-2004,
 SAFETY CODE FOR ELEVATORS AND ESCALATORS, REQUIRES A
 MINIMUM OF 5 FT-CANDLES (54 LUX) AT THE PIT FLOOR AND
 REQUIRES LUMINAIRES TO BE EXTERNALLY GUARDED TO PREVENT
 ACCIDENTAL BREAKAGE.
 PLEASE INCLUDE IN THE PHOTO-METRIC CALCULATIONS AS
 NEEDED ABOVE FOR EGRESS PATHS. MAY SUBMIT ONE AS
 TYPICAL FOR BOTH.
  
 21) NOTE: PLEASE SUBMIT MORE DETAIL FOR THE RTCU
 CONTROL PANELS WHICH THE GFI RECEPTACLES FOR ROOFTOP
 EQUIPMENT IS BEING SHOWN. THESE ARE 277/480V UNITS, AND
 NOT CLEAR WHAT THESE PANELS ARE AT THIS TIME. PLEASE
 CLARIFY.
  
 22) NOTE: PLEASE SEE ROOM LOCATED ON SHEET E131 WHICH
 IS TO THE LEFT AND DOWN FROM AREA/ROOM 122. THIS ROOM
 DOES NOT APPEAR TO SHOW ANY DOORS.
 FBC 106.1.2
  
 23) NOTE: PLEASE KNOW THE RATINGS OF THE MAIN
 ELECTRICAL ROOM 145 AND ELECTRICAL DISTRIBUTION ROOM
 116 NEEDS TO BE VERIFIED. PLEASE KNOW AS FULL FIRE
 SPRINKLER PLANS WERE NOT SUBMITTED THE ROOM RATING
 NEEDS TO BE VERIFIED.
 THIS INFORMATION WILL BE GONE OVER WITH THE BUILDING
 REVIEWER WHEN BUILDING REVIEW IS DONE. COULD NOT
 READLIY LOCATE ON THE ARCHITECTURAL SHEETS THE RATING
 OF THESE ROOMS.
 MAY BE 3HRS OR AT THE LEAST 1HR. 450.42
 WILL ALSO NEED MORE INFORMATION ON THE VENTILATION
 TAKING PLACE IN THESE ROOMS ONCE THE MECHANICAL REVIEW
 TAKES PLACE.
 PLEASE PROVIDE TEMPERATURE RISE AND EQUIPMENT HEATING
 WILL NEED TO BE GONE OVER.
  
 24) NOTE: PLEASE SEE THE PANEL SCHEDULES NOTE A *HANDLE
 LOCK-OFF DEVICE* ON SOME ITEMS. PLEASE BE SURE TO
 VERIFY THE DEVICES BEING NOTED AS MANY OF THESE ITEMS
 ARE ONLY LISTED FOR TEMPORARY USE AND IF A DEVICE IS TO
 BE PERMANENTLY INSTALLED IN LIEU OF A REQUIRED
 DISCONNECT THE LOCK OFF DEVICE SHALL BE AN INTEGRAL
 PART OF THE BREAKER ASSEMBLY.
 PLEASE PROVIDE NOTE ACCORDINGLY AND PLEASE KNOW THIS
 WILL BE VERIFIED IN FIELD BY THE ELECTRICAL INSPECTOR
 AND FINAL DETERMINATION BY THE AHJ.
 110.3, 90.4, 90.7.
  
 25) NOTE: PLEASE SEE 210.8B2 INTHE 2005 NEC AS GFI
 PROTECTION IS REQUIRED FOR ALL 120V 15/20 AMP CIRCUITS
 IN KITCHENS.
 PLANS DO NOT SHOW PROTECTION, EQUIPMENT SCHEDULE DOES
 NOT SHOW PROTECTION AND COULD NOT LOCATE THE BREAKERS
 IN PANELS FOR REQUIRED PROTECTION.
 PLEASE PROVIDE AND ADJUST PLANS.
  
 26) NOTE: PLEASE CLARIFY ACCESS TO THE EDR 116, WHICH
 APPEARS TO BE SHOWN THROUGH A ROOM 115. WHAT IS THIS
 ROOM 115?
 PLEASE SEE A351 WHICH INDICATES THE ROOM SHOWN AS 116
 ON ELECTRICAL PLANS AS 129 ON A-SHEETS. PLEASE
 COORDINATE.
 **MAY NOT ACCESS THROUGH A STORAGE, OFFICE ROOM AS THIS
 CLEARLY WOULD INTERFERE WITH THE MEANS OF EGRESS
 PATHS.
 THIS MAY ALSO BE NOTED BY THE FIRE MARSHAL AND BUILDING
 REVIEWER(S).
 PLEASE CLARIFY.
 LS 101, NEC ACCESS TO ELECTRICAL ROOM 110.26, 240.24
  
 27) NOTE: PLEASE SEE KNOW THE CODE WILL REQUIRE A
 NEUTRAL CONDUCTOR TO THE FIRST MEANS OF DISCONNECT FOR
 EACH OF THE ATS DEVICES. RISER SHOWS (7) WITH 3W, WHICH
 LENDS TO NO NEUTRAL CONDUCTORS. PLEASE KNOW THAT
 WHETHER OR NOT THE UNIT IS SEPARATELY DERIVED THIS IS
 REQUIRED.
 250.6, 250.24, 250.20 ETC
  
 28) NOTE: PLEASE INDICATE THE SIZES OF BRANCH CIRCUIT
 CONDUCTORS ON THE PANEL SCHEDULES. AS THE VD
 CALCULATIONS HAVE NOT BEEN SUBMITTED AND THESE ARE NOT
 SHOWN AT THIS TIME ON PANEL SCHEDULES, UNABLE TO VERIFY
 ALL.
 240.4, 310.16.
 FBC 106.1.2, 106.3.5.1.2FOR ADDITIONAL INFORMATION.
  
 29) NOTE: PLEASE PROVIDE NOTES ON PLANS FOR REQUIRED
 SIGNAGE FOR ARC FLASH PROTECTION. 110.16
  
 30) NOTE: PLEASE INCLUDE DISCONNECTING MEANS FOR ALL
 FEEDERS FROM GENERATOR TO BUILDING. PLEASE SEE,
 225.31-225.39, 700.12B6, 701.11B6, AND 702.11B6. PLEASE
 KNOW BASED ON NOT HAVING THE INFORMATION ON THE
 BREAKERS FOR THE GENERATOR, THE CODE REQUIRES THE MEANS
 OF DISCONNECT TO BE *WITHIN SIGHT* AND *READILY
 ACCESSIBLE*. PLEASE SEE NEC ART 100 FOR DEFINITIONS.
 PLEASE ALSO KNOW AS THERE MAY BE ZONING AND OTHER
 REQUIREMENTS WHICH MAY REQUIRED FENCING/WALLS/AND
 LANDSCAPING THE BREAKERS MAY NOT BE READILY ACCESSIBLE.
 PLEASE ALSO KNOW THAT BASED ON THE GENERATOR AND THE
 LOCATION OF THIS UNIT THESE MAY BE INSIDE A LOCKED
 ENCLOSURE. THIS BEING SAID SEPARATE DISCONNECTSWHICH
 ARE NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION
 WILL BE REQUIRED AT THE BUILDING OR IN CLOSE PROXIMITY
 TO BE DETERMINED BY THIS OFFICEAND THE FIRE MARSHAL.
  
 31)NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED, A
 RESPONSE LETTER WILL BE HELPFUL IN THE FOLLOWING
 REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-07 19:04:112008-03-07 19:04:11
  
 REVIEW CONTINUED 3/7, IN PROGRESS TO CONTINUE 3/8,
 NOTES TO FOLLOW ONCE COMPLETED.
2008-02-16 19:56:142008-02-16 19:56:14
  
 REVIEW STOPPED,ELECTRICAL REVIEW WILL CONTINUE AFTER
 2/29. PLANS WILL GO INTO *F* STATUS AT THAT TIME AND
 NOTES WILL BE POSTED ONCE REVIEW IS COMPLETED.
2008-02-16 19:04:462008-02-16 19:04:46
  
 ONE ROLL IN ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 7 Status N Date 2009-03-06 Cont ID  
Sent By mgonzale Date 2009-03-06 Time 15:41 Rev Time 1.00
Received By mgonzale Date 2009-03-06 Time 15:41 Sent To  
Notes
2009-03-06 15:42:03NO CHANGES TO CIVIL OR SITE RELATED

Review Stop ENG ENGINEERING CSD
Rev No 6 Status N Date 2008-09-11 Cont ID  
Sent By rchokshi Date 2008-09-11 Time 08:23 Rev Time 0.00
Received By rchokshi Date 2008-09-11 Time 08:23 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2008-08-18 Cont ID  
Sent By rchokshi Date 2008-08-18 Time 10:21 Rev Time 0.00
Received By rchokshi Date 2008-08-18 Time 10:21 Sent To  
Notes
2008-08-18 10:25:44ACCORDING TO E-MAIL FROM MANNY G. OF 1000 45TH ST ENG,
 STORM WATER QUALITY CALS ARE APPROVED BY MOCK-ROOS.
 THEREFORE, WEACCEPT THEIR APPROVAL LETTER.
  
 RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 4 Status F Date 2008-07-25 Cont ID  
Sent By rchokshi Date 2008-07-25 Time 16:31 Rev Time 0.00
Received By rchokshi Date 2008-07-25 Time 16:19 Sent To  
Notes
2008-07-25 16:30:42FAILED FOR FOLLOWING REASONS:
  
 1. YOU NEED TO GET AN APPROVAL FROM 1000 45TH ST
 ENGINEERING FOR STORM WATER QUALITY CALS BEFORE WE
 ISSUE A PERMIT. THEREFORE, WE SUGGESTYOU KEEP IN
 TOUCH WITH 1000 45TH ST ENGINEERING FOR THEIR APPROVAL.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-07-24 Cont ID  
Sent By rchokshi Date 2008-07-24 Time 13:49 Rev Time 0.00
Received By rchokshi Date 2008-07-24 Time 13:20 Sent To  
Notes
2008-07-24 13:49:48FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT , ENVIRONMENTAL REPORT&STORM WATER CALS TO
 100045TH STREET ENGINEERING SERVICESFOR THEIR
 APPROVAL,BEFORE WE ISSUE A PERMIT.
  
 2. PLEASE SHOW ON DRAINAGE DRAWINGTHE SUMMARYOF THE
 TOTAL SITE AREA, PERVIOUS AND IMPERVIOUS AREAS. ALSO
 GREEN, LAKE,PARKING AREA,YOU ARE DEVELOPING FOR THIS
 PROJECT . PLEASEMAKE SURE THESE AREAS SHOWN ON
 DRAINAGE DRAWINGS MUST MATCH WITH AND USED IN STORM
 WATER QUALITY CALCULATIONS.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By rchokshi Date 2008-06-11 Time 14:07 Rev Time 0.00
Received By rchokshi Date 2008-06-11 Time 13:43 Sent To  
Notes
2008-06-11 14:07:07FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 2.PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT , ENVIRONMENTAL REPORT&STORM WATER QUALITY
 CALCULATIONS. STORM WATER CALS MUST BE APPROVED FROM
 100045TH STREET ENGINEERING SERVICES BEFORE WE
 APPROVE.
 PLEASE SHOW ON WATER QUALITY CALCULATION THAT YOU
 HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25, 100 YEAR
 FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU DETERMINE
 THE FIRST FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD
 BE ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE
 ROAD.
  
 3. PLEASE SHOW ON DRAINAGE DRAWINGTHE SUMMARYOF THE
 TOTAL SITE AREA, PERVIOUS AND IMPERVIOUS AREAS. ALSO
 GREEN, LAKE,PARKING AREA,YOU ARE DEVELOPING FOR THIS
 PROJECT . PLEASEMAKE SURE THESE AREAS SHOWN ON
 DRAINAGE DRAWINGS MUST MATCH WITH AND USED IN STORM
 WATER QUALITY CALCULATIONS.
  
 4. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET ENGINEERING BEFORE WE APPROVE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-14 Cont ID  
Sent By rchokshi Date 2008-03-14 Time 09:19 Rev Time 0.00
Received By rchokshi Date 2008-03-14 Time 09:05 Sent To  
Notes
2008-03-14 09:19:24FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2.PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 4. PLEASE PROVIDE WATER QUALITY CALCULATIONS.PLEASE
 SHOW ON CALCULATION THAT YOU HAVE CONSIDERED FLOOD ZONE
 AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA AND CROWN OF
 THE ROAD WHEN YOU DETERMINE THE FIRST FLOOR ELEVATION.
 FIRST FLOOR ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER
 THAN HIGHEST CROWN OF THE ROAD.
  
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SUMMARYOF THE
 SITE AREA, PERVIOUS AND IMPERVIOUS AREAS. ALSOGREEN,
 LAKE,PARKING AREA,YOU ARE DEVELOPING FOR THIS PROJECT
 . PLEASEMAKE SURE THESE AREAS SHOWN ON DRAINAGE
 DRAWINGS MUST MATCH WITH AND USED IN STORM WATER
 QUALITY CALCULATIONS. PLEASE PROVIDE A COPY OF THESE
 CALCULATIONS.
  
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
  
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT , ENVIRONMENTAL REPORT&STORM WATER QUALITY
 CALCULATIONS. STORM WATER CALS MUST BE APPROVED FROM
 100045TH STREET ENGINEERING SERVICES BEFORE WE
 APPROVED.
  
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET ENGINEERING BEFORE WE APPROVE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2009-10-07 Cont ID  
Sent By mawillia Date 2009-10-07 Time 14:56 Rev Time 0.00
Received By mawillia Date 2009-10-07 Time 14:33 Sent To  
Notes
2009-10-07 14:48:07*****REVISION APPROVED*****
  
  
 OF THE SIX REVISED PLAN SHEETS, A020 AND A611 WERE
 STAMPED, INITIALED, AND DATED;
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-09-15 Cont ID  
Sent By mawillia Date 2009-09-15 Time 11:36 Rev Time 0.00
Received By mawillia Date 2009-09-15 Time 11:26 Sent To B1
Notes
2009-09-15 11:31:11*****REVISION #103, DATED 9/04/09, APPROVED*****
  
 REVISED PLAN SHEETS A020 AND E110 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-07-30 Cont ID  
Sent By mawillia Date 2009-07-30 Time 13:40 Rev Time 0.00
Received By mawillia Date 2009-07-30 Time 12:58 Sent To  
Notes
2009-07-30 13:02:12*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A130, A201, A611, A801, AND F111,
 AND WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-05-14 Cont ID  
Sent By mawillia Date 2009-05-14 Time 11:58 Rev Time 0.00
Received By mawillia Date 2009-05-14 Time 10:19 Sent To  
Notes
2009-05-14 10:22:29*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS E901, E912, E922, E931, AND E932
 WERE STAMPED, INITIALED, AND DATED TO GO ALONG WITH THE
 PREVIOUSLY APPROVED SHEETS OF 3/16/09.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2009-03-17 Cont ID  
Sent By mawillia Date 2009-03-17 Time 14:14 Rev Time 0.00
Received By mawillia Date 2009-03-16 Time 15:39 Sent To  
Notes
2009-03-16 21:53:16*****PARTIAL APPROVAL*****
  
  
 REVISED PLAN SHEETS A020, A021, A130, A131, A201, A611,
 A801, A851, F111, AND F300 WERE STAMPED, INITIALED, AND
 DATED; HOWEVER SHEETS E901, E912, E922, AND E931 ARE TO
 BE FIRE-STAMPED WHEN THE ELECTRICAL PLAN EXAMINER'S
 COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2009-03-16 Cont ID  
Sent By mawillia Date 2009-03-16 Time 14:26 Rev Time 0.00
Received By mawillia Date 2009-03-16 Time 13:59 Sent To  
Notes
2009-03-16 14:25:50*****NOT REQUIRED*****
  
  
 1. THE SUBMITTED SHOP ARCHITECTURAL SHOP DRAWINGS
 AND/OR PRODUCT APPROVALS NOT REQUIRED TO BE FIRE
 STAMPED.
  
 2. THE SUBMITTED FIRE ALARM AND ASSOCIATED DRAWINGS,
 PRODUCT APPROVAL, AND SPEC SHEETS ARE TO BE SUBMITTED
 UNDER A SEPARATE FIRE ALARM PERMIT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-10-02 Cont ID  
Sent By mawillia Date 2008-09-30 Time 16:49 Rev Time 0.00
Received By lmartine Date 2008-09-30 Time 14:52 Sent To  
Notes
2008-10-02 14:51:52APPROVED FORE MIKE WILLIAMS
2008-09-30 16:48:58*****APPROVED*****
  
  
 PLAN SHEETS A020, A021, A130,A131,A201, A611, A801,
 F110, F111, F300, E901, E911, E912, E921, E922, AND
 E931 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-08-18 Cont ID  
Sent By mawillia Date 2008-08-18 Time 15:10 Rev Time 0.00
Received By mawillia Date 2008-08-18 Time 14:01 Sent To  
Notes
2008-08-18 15:07:14*****UNSAT*****
  
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEWS STILL NEEDS TO BE ADDRESSED:
  
 16.ON SHEET A020 AND A021, THE PATH OF EGRESS IS
 SHOWN TO PASS THROUGH OBSTRUCTIONS.THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) SHALL NOT BE THROUGH AN
 OBSTRUCTION OR POSSIBLE OBSTRUCTION.PLEASE REFERENCE
 NFPA 101, LIFE SAFETY CODE, 2003 EDITION - CH. 7.6.1
 FOR DETAILING THE MEASUREMENT OF TRAVEL DISTANCE TO
 EXITS ACCEPTABLE TO THE AHJ.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-01 Cont ID  
Sent By mawillia Date 2008-07-01 Time 09:08 Rev Time 0.00
Received By mawillia Date 2008-07-01 Time 07:07 Sent To  
Notes
2008-07-01 09:08:29*****UNSAT*****
  
  
 16.ON SHEET A020 AND A021, THE PATH OF EGRESS IS
 SHOWN TO PASS THROUGH OBSTRUCTIONS.THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) SHALL NOT BE THROUGH AN
 OBSTRUCTION OR POSSIBLE OBSTRUCTION
  
 18.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS OF ASME A17.1;AND
 SHALL BE ABLE TO ACCOMMODATE PARAMEDICAL EQUIPMENT. ADD
 COMMENT TO AN APPROPIATE PLAN SHEET
  
 24.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR
 THE INSTALLATION OF THE BUILDING'S SPRINKLER SYSTEM. IT
 IS INDICATED ON SHEET F300 REFERENCING THE 2004
 EDITION.THERE STILL IS A REFERENCE TO 2004 EDITION IN
 THE 61G15-32.004.(2) UNDER APPLICABLE NFPA STANDARD TO
 BE APPLIED
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 19:13 Rev Time 0.00
Received By mawillia Date 2008-04-24 Time 09:34 Sent To  
Notes
2008-04-24 12:16:35*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.WHEN THE OLD BUILDING IS TO BE DEMOLISHED, THE
 SPRINKLER SYSTEM SHALL NOT BE RENDERED INOPERABLE
 WITHOUT THE APPROVAL OF WEST PALM BEACH FIRE
 PREVENTION.
  
 03.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 PALM BEACH LAKES BOULEVARD, DISPLAY/SHOW THE ACTUAL
 ADDRESS NUMBERS ON THE STRUCTURE OF THE BUILDING.AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE A
 MINIMUM OF 6" IN HEIGHT AND 1" IN WIDTH/STROKE.IN THE
 EVENT THAT THE ADDRESS IS NOT READILY VISIBLE DUE TO
 THE BUILDING'S SETBACK FROM THE STREET, A MONUMENT
 SIGN/MARKEE WILL BE REQUIRED DEPICTING THE ADDRESS IN
 ADDITION TO THOSE ON THE STRUCTURE OF THE BUILDING.
  
 05.ILLUSTRATE ANY EXISTING OR NEW FIRE HYDRANTS.
  
 06.KNOX-BOX FOR THE BUILDING SHALL BE REQUIRED.SHOW
 WHERE THIS DEVICE WILL BE INSTALLED IN AN ACCESSIBLE
 LOCATION SO THAT FIRE RESCUE MAY GAIN EMERGENCY ACCESS
 TO THE STRUCTURE.
  
 07.ONLY ONE FIRE DEPARTMENT CONNECTION (FDC) IS
 SHOWN.CONSIDERING THE SIZE OF THIS CLASS A ( MORE
 THAN 30,000 SQUARE FEET) MERCANTILE OCCUPANCY WITHOUT
 THE MENTION OF A FIRE PUMP, WILL THE ONE FDC BE
 ADEQUATE?
  
 08.KNOX LOCKING CAPS SHALL BE REQUIRED ON THE FIRE
 DEPARTMENT CONNECTION(S) .FOR AN APPLICATION, CONTACT
 WEST PALM BEACH FIRE PREVENTION AT 561-804-4724.
  
 09.THE FIRE BARRIER SEPARATING PARKING STRUCTURES
 FROM THE MERCANTILE OCCUPANCY SHALL BE A FIRE BARRIER
 HAVING A FIRE RESISTIVE RATING OF NOT LESS THAN 2
 HOURS.
  
 10.OUTSIDE STAIRS, RAMPS, AND LANDINGS SHALL BE
 DESIGNED TO MINIMIZE WATER ACCUMULATION ON THEIR
 SURFACES.
  
 11.PRESCRIPTIVE STRENGHT REQUIREMENTS SHALL BE NOTED
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 12.HANDRAILS/GUARDRAILS SHALL BE REQUIRED ON BOTH
 SIDES OF THE STAIRS AND RAMPS.
  
 13.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.BUILDING PLANS SHALL BE DRAWN TO A MINUMUM OF 1/8
 INCH SCALE.SEVERAL SHEETS (SUCH AS A201, E911, FOR
 EXAMPLE) ARE SHOWN AT 1/16 INCH SCALE.
  
 15.ON SHEET A020 AND A021, IT IS ASSUMED THAT THE
 EXIT DIAGRAM IS THE SAME AS THE LIFE SAFETY PLAN. IF
 THIS ASSUMPTION IS INCORRECT, PROVIDE A LIFE SAFETY
 PLAN DEPICTING TRAVEL DISTANCES TO THE EXITS.
  
 16.ON SHEET A020 AND A021, THE PATH OF EGRESS IS
 SHOWN TO PASS THROUGH OBSTRUCTIONS.THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) SHALL NOT BE THROUGH AN
 OBSTRUCTION OR POSSIBLE OBSTRUCTION.
  
 17.SPECIFYTHE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A OR CLASS B.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 18.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS OF ASME A17.1;AND
 SHALL BE ABLE TO ACCOMMODATE PARAMEDICAL EQUIPMENT.
  
 19.ON SHEET A130, NO EXIT LIGHTS AND EMERGENCY
 LIGHTING IS SHOWN.
  
 20.ON SHEET A131, NO EMERGENCY LIGHTING IS SHOWN AND
 MORE EXIT LIGHTS MAY BE REQUIRED.VERIFY THAT SIGN
 PLACEMENT SHALLBE SUCH THAT NO POINT IN AN EXIT
 ACCESS CORRIDOR IS IN EXCESS OF 100 FEET FROM THE
 NEAREST SIGN.
  
 21.THERE IS AN EXIT LIGHT THAT DIRECTS PATRONS TO
 AREA/ROOM 174 BUT NO EXIT DOOR IS SHOWN.
  
 22. THERE IS NO SHEET A200 IN THE PLAN SET AS INDICATED
 IN THE SHEET INDEX (SHEET G001) .
  
 23. IN ADDITION TO THE ELECTRONIC SWITCHES, CHAIN AND
 LOCK WILL BE REQUIRED ON THE FIRE LINE BACKFLOW
 DEVICE.
  
 24.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR
 THE INSTALLATION OF THE BUILDING'S SPRINKLER SYSTEM. IT
 IS INDICATED ON SHEET F300 REFERENCING THE 2004
 EDITION.
  
 25.PROVIDE A LAYOUT OF THE BUILDING'S FIRE SPRINKLER
 SYSTEM TO BE INSTALLED.PLEASE BE ADVISED THAT
 SPECIFICATIONS AND OTHER RELATED MATERIALS ARE NOT
 NEEDED AT THIS TIME.
  
 26.FIRE SPRINKLER SYSTEM SHALL BE MONITORED.
  
 27.ALTHOUGH IN PLAN SET, NO SHEETS F111, F300 ARE NOT
 SHOWN IN THE SHEET INDEX (SHEET G001) .
  
 28.SHEETS R111, R141, R401, R411, R421, R501, R601,
 R621, AND R901 ARE NOT SHOWN IN THE SHEET INDEX (SHEET
 G001) .
  
 29.COULD NOT LOCATE THE FLOWS AND TAMPERS ON THE
 SPRINKLER AND/OR FIRE ALARM DRAWINGS.
  
 30.PLEASE EXPLAIN THE CORRELATION BETWEEN THE
 SPRINKLER SUPERVISORY INITIATING DEVICE PLAN ( E901 FOR
 EXAMPLE) AND A FIRE ALARM PLAN.
  
 31.INDICATE THE FLOOR LEVAL ON THE FIRE ALARM
 SHEETS.
  
 32.IT IS SHOWN ON SHEET E912,THE ELECTRICAL
 DISTRIBUTION CENTER/ROOM 116.HOW DOES ONE ACCESS THIS
 SPACE?IS THIS AREA FIRE PROTECTED (SPRINKLERED, FIRE
 RESISTIVE SEPARATED, ETC.)
  
 33.HOW IS THE EMERGENCY LIGHTING IN THE STAIRWELLS
 ATTAINED?
  
 34.PLEASE EXPLAIN WHAT IS AN INTRUSION SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 8 Status P Date 2009-07-30 Cont ID  
Sent By kstevens Date 2009-07-30 Time 12:02 Rev Time 0.00
Received By kstevens Date 2009-07-30 Time 12:02 Sent To  
Notes
2009-07-30 12:03:13GAS REVISION OK

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2009-07-02 Cont ID  
Sent By kstevens Date 2009-07-02 Time 08:56 Rev Time 0.00
Received By kstevens Date 2009-07-02 Time 08:56 Sent To  
Notes
2009-07-02 08:57:07REVISION OK -- SHT P502 -- LP GAS ISOMETRIC RISER
 DIAGRAM.

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2009-04-23 Cont ID  
Sent By kstevens Date 2009-04-23 Time 16:06 Rev Time 0.00
Received By kstevens Date 2009-04-22 Time 16:53 Sent To  
Notes
2009-04-23 16:15:47REVISION DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 A. SHT P111 SUBMIT THE FOLLOWING INFORMATION FOR THE
 LP/PROPANE GAS SYSTEM:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, INDICATE ON RISER DIAGRAM.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 B. NO 2ND STAGE REGULATOR IS SHOWN ON THE GAS PLAN.
 PLEASE INDICATE THE LOACTION ON THE RISER DIAGRAM AND
 THE GAS PLAN. A LISTED SHUT OFF VALVE IS REQUIRED
 IMMEDIATELY AHEAD OF THE REGULATOR. SECTION 409.4.
  
 C. SUBMIT THE MANUF. SPECIFICATIONS FOR THE 2ND STAGE
 REGULATOR. THE REGULATOR SHALL BE LISTED. SHOW THE
 MODEL NUMBER AND OUTLET CAPACITY FOR SINGLE OR MULTIPLE
 APPLIANCES. SECTION 106.1.2, (MORE INFORMATION
 REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2009-03-05 Cont ID  
Sent By kstevens Date 2009-03-05 Time 16:55 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 17:07 Sent To  
Notes
2009-03-06 07:57:43DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 NFPA-58
  
  
 1. SHT P111 THE PROPANE TANK IS REQUIRED TO BE A
 MINIMUM OF 10 FEET FROM THE BUILDING. NFPA-58 SECTION
 6.2.1 & ANNEX I SECTION I.1 AND FIGURE I.1(B). THE
 PROPANE TANK IS INDICATED UNDER THE BUILDING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 11:04 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 11:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-07-30 Cont ID  
Sent By kstevens Date 2008-07-30 Time 07:49 Rev Time 0.00
Received By kstevens Date 2008-07-29 Time 12:53 Sent To  
Notes
2008-07-30 07:49:47PLANS REVIEWED AND STAMPED BUT PERMIT WILL STAY IN
 FAILED STATUS UNTIL CONTRACTOR APPLIES FOR PERMIT

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By kstevens Date 2008-06-11 Time 09:37 Rev Time 0.00
Received By kstevens Date 2008-06-09 Time 15:46 Sent To  
Notes
2008-06-11 09:38:04 
  
 DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS
 REQUIRED FOR THE GAS PERMIT.
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
 **********NEW COMMENTS***********
  
 1B. SHOW THE SHUT OFF VALVE AND THE SECOND STAGE
 REGULATOR ON THE GAS RISER DIAGRAM. THE SHUT OFF VALVE
 SHALL BE INSTALLED UPSTREAM OF THE REGULATOR. SECTION
 409.4.
  
 2B. SUBMIT THE MANUFACTURE SPECIFICATION SHEETS FOR THE
 SECOND STAGE GAS REGULATOR. INDICATE MODEL NUMBER AND
 SHOW LISTING FOR REGULATOR ON SHEETS. SECTION 410.2.
  
 3B. VENTED REGULATORS SHALL COMPLY WITH SECTION 410.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-06-09 Cont ID  
Sent By kstevens Date 2008-04-09 Time 15:44 Rev Time 0.00
Received By kstevens Date 2008-04-09 Time 15:44 Sent To  
Notes
2008-06-09 15:46:41DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS
 REQUIRED FOR THE GAS PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--LENGHTS OF CUT SECTIONS NOT SHOWN.
  
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED WHEN
 COMMENT 24(A) SUBMITTED.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. THE LOCATION OF THE GAS METER, THE GENERATOR AND
 ASSOCIATED GAS PIPING SHALL BE INDICATED ON THE
 PLUMBING SHEETS TO VERIFY THE GAS ISOMETRIC PIPING.
 SECTION 106.1.2.
  
 25. PLANS ARE NOT 100% COMPLETE AT THIS TIME AND MORE
 COMMENTS MAY FOLLOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-16 Time 08:12 Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 08:11 Sent To  
Notes
2009-09-22 08:15:01C-9

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-09-08 Cont ID  
Sent By rbrown Date 2009-09-08 Time 18:41 Rev Time 0.00
Received By rbrown Date 2009-09-08 Time 18:41 Sent To  
Notes
2009-09-08 18:42:30C-28. REVISION FOR PARKING GARAGE EXIT SIGNAGE.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-08-20 Cont ID  
Sent By lmartine Date 2009-08-20 Time 11:01 Rev Time 0.00
Received By lmartine Date 2009-08-20 Time 11:01 Sent To  
Notes
2009-08-20 11:02:33PRECAST SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By jwitmer Date 2009-07-06 Time 08:10 Sent To  
Notes
2009-07-06 08:10:40INCOMING: C48

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 13:20 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 13:19 Sent To  
Notes
2009-06-11 13:20:56TO C-21 - ELEC & PLUMB REVISIONS

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 13:16 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 13:16 Sent To B
Notes
2009-06-11 13:17:16TO JW DESK - WALL DETAIL AND SHORING PLAN

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 16:30 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 16:30 Sent To B
Notes
2009-04-17 16:30:25TO "JWITMER"

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 15:27 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 15:27 Sent To B
Notes
2009-04-10 15:28:18TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-04-10 Cont ID  
Sent By adarroug Date 2009-04-10 Time 14:43 Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 14:43 Sent To  
Notes
2009-04-10 14:44:08TO "C34"

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 09:14 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 09:14 Sent To B
Notes
2009-04-03 09:15:25TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-13 Cont ID  
Sent By adarroug Date 2009-03-13 Time 10:56 Rev Time 0.00
Received By adarroug Date 2009-03-13 Time 10:56 Sent To B
Notes
2009-03-13 10:57:17TO "JWITMER" DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 15:26 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 15:26 Sent To B
Notes
2009-02-27 15:28:16TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 13:40 Rev Time 0.00
Received By adarroug Date 2009-02-17 Time 13:40 Sent To FIRE
Notes
2009-02-17 13:44:29TO "COMM" BD#13--PLANS CAME IN AS SUBMITTAL OF SHOP
 DRAWINGS FOR "BLDG" AND "F". AFTER TALKING WITH CAPTAIN
 WILLIAMS, WE DECIDED TO ROUTED IT THE BOARD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 15:22 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 15:22 Sent To  
Notes
2009-01-30 15:23:32TO "COMM" BD#52--PLANS ON RACK--5 BIG ROLLS, 10 SM
 ROLLS, 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 15:39 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 15:39 Sent To M
Notes
2008-11-21 15:40:07TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-04 Cont ID  
Sent By adarroug Date 2008-09-04 Time 09:12 Rev Time 0.00
Received By adarroug Date 2008-09-04 Time 09:12 Sent To  
Notes
2008-09-04 09:12:54TO "COMM" BD#22/PLANS ON RACK--4 ROLLS, 1 BOX W/BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 13:29 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 13:29 Sent To  
Notes
2008-07-15 13:33:32TO "COMM" BD#44/PLANS ON RACK/4 ROLLS, BINDERS, AND
 BOOKS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 08:24 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 08:24 Sent To  
Notes
2008-05-27 16:39:18TO "COMM" BD#48-PLANS ON RACK/5 ROLL, 1 BOX
2008-05-22 08:25:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-25 Cont ID  
Sent By lmartine Date 2008-04-25 Time 16:04 Rev Time 0.00
Received By lmartine Date 2008-02-07 Time 09:45 Sent To  
Notes
2008-02-07 09:46:19TO "COMM" BD#22/PLANS ON RACK--3 ROLLS AND PAPERWORK

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 15:21 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 14:31 Sent To P
Notes
2009-07-28 15:21:55REVISIONS AS FOLLOWS:
  
 ENERGY CALCULATIONS DATED 6/26/09
 M141 DELTA 62, M321 AND M601 DELTA 46, R111, R401,
 R411, R601, R611, R621 DELTA 59

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-24 Time 10:26 Rev Time 0.00
Received By rregueir Date 2009-04-24 Time 10:26 Sent To  
Notes
2009-04-30 10:26:31REVISED R PAGES

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-03-11 Cont ID  
Sent By rregueir Date 2009-03-11 Time 11:50 Rev Time 0.00
Received By rregueir Date 2009-03-10 Time 16:46 Sent To  
Notes
2009-03-11 11:55:31THE FOLLOWING PAGES WERE REVISED OR ADDED AS PART OF
 REVISION 32:
  
 M111
 M141
 M301
 M321
 M601
 R111
 R141
 R401
 R411
 R421
 R501
 R511
 R521
 R601
 R611
 R621
  
 THE FOLLOWING PROVISO IS ATTACHED TO PAGE R511:
  
 *****PROVISO*****
 PAGE R511 DETAIL #14: EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBC-M
 301.13. REVISE PLAN SHOWING SUPPORTS DESIGNED AND
 ATTACHED TO BUILDING STRUCTURE FOR WIND RESISTANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-09-10 Cont ID  
Sent By rregueir Date 2008-09-10 Time 10:39 Rev Time 0.00
Received By rregueir Date 2008-09-10 Time 09:23 Sent To  
Notes
2008-09-10 09:24:36THE WIND LOAD CALCULATIONS FOR THE HILL PHOENIX
 REFRIGERATION EQUIPMENT ROOM ARE OK. THE WIND LOAD
 CALCULATIONS FOR ALL OTHER OUTDOOR APPLIANCES ARE
 INSUFFICIENT. THE CALCULATIONS ONLY ACCOUNT FOR THE
 SIZE OF THE PANELS AND THE STRENGTH OF THE SCREWS
 HOLDING THE PANELS. THEY DO NOT COVER ANY OTHER ASPECTS
 OF THE CONSTRUCTION OF THE APPLIANCES. A COMPREHENSIVE
 ANALYSIS OF THE OVERALL CONSTRUCTION OF THE APPLIANCES
 IS REQUIRED TO DEMONSTRATE COMPLIANCE WITH FBCM 301.13.
 PLEASE CORRECT AND RESUBMIT. THIS IS THE ONLY
 OUTSTANDING MECHHANICAL REVIEW COMMENT AT THIS TIME. AS
 SUCH, IT WILL BE COVERED BY A PROVISO TO FACILITATE THE
 PROGRESS OF THE PROJECT WHILE A NEW ANALYSIS OR TESTING
 CAN BE DONE.
  
 REVIEW WILL REMAIN IN FAILED STATUS UNTIL THERE HAS
 BEEN AN ACTUAL APPLICATION FOR PERMIT. THESE PLANS ARE
 STILL SUBMITTED UNDER PLAN REVIEW ONLY STATUS. THE
 FOLLOWING PROVISO WILL BE ISSUED WITH THE PERMIT SET OF
 PLANS:
  
 ***************PROVISO**************
 ALL MECHANICAL APPLIANCES EXPOSED TO WIND SHALL
 DEMONSTRATE COMPLIANCE WITH FBCM 301.13 BY ANALYSIS OR
 TESTING. SUPPORTING DOCUMENTATION SHALL BE PROVIDED TO
 THE CODE OFFICIAL IN TIME FOR A PASSED REVIEW PRIOR TO
 INSTALLATION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-08-18 Cont ID  
Sent By rregueir Date 2008-08-18 Time 08:58 Rev Time 0.00
Received By rregueir Date 2008-08-18 Time 08:43 Sent To  
Notes
2008-08-18 08:57:41THE WIND LOAD CALCULATIONS FOR THE HILL PHOENIX
 REFRIGERATION EQUIPMENT ROOM ARE OK. THE WIND LOAD
 CALCULATIONS FOR ALL OTHER OUTDOOR APPLIANCES ARE
 INSUFFICIENT. THE CALCULATIONS ONLY ACCOUNT FOR THE
 SIZE OF THE PANELS AND THE STRENGTH OF THE SCREWS
 HOLDING THE PANELS. THEY DO NOT COVER ANY OTHER ASPECTS
 OF THE CONSTRUCTION OF THE APPLIANCES. A COMPREHENSIVE
 ANALYSIS OF THE OVERALL CONSTRUCTION OF THE APPLIANCES
 IS REQUIRED TO DEMONSTRATE COMPLIANCE WITH FBCM 301.13.
 PLEASE CORRECT AND RESUBMIT. THIS IS THE ONLY
 OUTSTANDING MECHHANICAL REVIEW COMMENT AT THIS TIME. AS
 SUCH, IT WILL BE COVERED BY A PROVISO TO FACILITATE THE
 PROGRESS OF THE PROJECT WHILE A NEW ANALYSIS OR TESTING
 CAN BE DONE.
  
 REVIEW WILL REMAIN IN FAILED STATUS UNTIL THERE HAS
 BEEN AN ACTUAL APPLICATION FOR PERMIT. THESE PLANS ARE
 STILL SUBMITTED UNDER PLAN REVIEW ONLY STATUS. THE
 FOLLOWING PROVISO WILL BE ISSUED WITH THE PERMIT SET OF
 PLANS:
  
 ***************PROVISO**************
 ALL MECHANICAL APPLIANCES EXPOSED TO WIND SHALL
 DEMONSTRATE COMPLIANCE WITH FBCM 301.13 BY ANALYSIS OR
 TESTING. SUPPORTING DOCUMENTATION SHALL BE PROVIDED TO
 THE CODE OFFICIAL IN TIME FOR A PASSED REVIEW PRIOR TO
 INSTALLATION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-08-05 Cont ID  
Sent By rregueir Date 2008-08-05 Time 10:30 Rev Time 0.00
Received By rregueir Date 2008-07-30 Time 15:26 Sent To  
Notes
2008-08-05 10:30:33REVIEW IN TEMPORARY FAIL STATUS PENDING RESOLUTION OF
 COMMENT #5 AND REVIEW OF WIND LOAD DATA FOR MECHANICAL
 APPLIANCES (BY STRUCTURAL REVIEWER). COMMENT #5
 REQUIRES A THROUGH-PENETRATION DETAIL FOR 8" ROUND DUCT
 PENETRATING RATED WALL WITHOUT FIRE DAMPER. SPOKE TO
 ERIC FROM NELSON-RUDIE VIA TELEPHONE. THE DESIGN TEAM
 HAS REQUESTED AN OPPORTUNITY TO PROVIDE THE MISSING
 DOCUMENTATION DURING THIS REVIEW CYCLE. THE WIND LOAD
 DATA FOR THE APPLIANCES WAS NOT PROVIDED WITH ORIGINAL
 SEAL/SIGNATURE OF THE STRUCTURAL ENGINEERS RESPONSIBLE
 FOR THE REPORTS. THIS WILL NEED TO BE CORRECTED. IF
 NECESSARY, ONCE ALL OUTSTANDING ISSUES ARE ADDRESSED,
 THIS MAY BE COVERED WITH A PROVISO TO ALLOW THE PROJECT
 TO MOVE FORWARD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-19 Cont ID  
Sent By rregueir Date 2008-06-19 Time 08:35 Rev Time 0.00
Received By rregueir Date 2008-06-17 Time 09:57 Sent To  
Notes
2008-06-19 08:35:20REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 AND 2: OK
  
 3. WIND LOAD CALCULATIONS ARE SUBJECT TO BUILDING PLAN
 REVIEW. IF ALL OTHER REVIEW ITEMS ARE ADDRESSED, A
 PROVISO WILL BE ISSUED TO COVER THE MISSING WIND
 RESISTANCE DOCUMENTATION FOR THE OUTDOOR APPLIANCES.
  
 4. OK
  
 5. PAGE M301 KEYNOTE #14 REFERENCES SECTION 07 8400. NO
 SUCH INFORMATION WAS PROVIDED. ADDITIONALLY, GENERAL
 NOTE E CALLS FOR FIRE DAMPERS AT ALL RATED ASSEMBLIES.
 THIS IS IN CONFLICT WITH KEYNOTE 14. PLEASE CLARIFY AND
 COORDINATE NOTES. DEMONSTRATE COMPLIANCE WITH FBCM
 607.1.1 AND 607.5. PROVIDE A DETAIL FOR THE
 THROUGH-PENETRATION FIRESTOP SYSTEM TO BE USED ON THE
 PLANS.
  
 6 AND 7: THESE COMMENTS WERE ADDRESSED BY REFERENCING A
 DOCUMENT WHICH WAS NOT SUBMITTED AS PERMIT
 DOCUMENTATION. PLEASE DEMONSTRATE CODE COMPLIANCE BY
 PROVIDING THE REQUESTED INFORMATION ON THE PLANS.
  
 8 THROUGH 12: OK
  
 13. MECHANICAL PORTIONS OF THE ENERGY CALCULATIONS HAVE
 BEEN CORRECTED. HOWEVER, THE CERTIFICATIONS PAGE OF THE
 CODE COMPLIANCE FORM HAS NOT BEEN SIGNED AND SEALED BY
 THE PREPARER IN ACCORDANCE WITH FBCB 13-103.1.1.1 AND
 13-103.2. PLEASE CORRECT AND RESUBMIT.
  
 NOTE: THIS PROJECT IS STILL SUBMITTED FOR PLAN REVIEW
 ONLY AND NOT FOR PERMIT. EVEN WHEN ALL OUTSTANDING
 COMMENTS HAVE BEEN ADDRESSED, PLANS WILL REMAIN IN
 FAILED STATUS UNTIL A PERMIT IS APPLIED FOR AND ISSUED.
 THESE PLANS ARE SUBJECT TO ANY CHANGES IN THE BUILDING
 CODES ADOPTED BY THE STATE UP TO THE DATE OF ACTUAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-16 Cont ID  
Sent By rregueir Date 2008-03-16 Time 12:58 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 12:05 Sent To  
Notes
2008-03-16 12:58:05REVIEW #: 1ST***PLAN CHECK ONLY***
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M321: RTU 5 DUCT SYSTEM ON FLOOR PLAN CALLS FOR A
 TOTAL OF 10,950 CFM OF SUPPLY WHILE THE RTU SCHEDULE ON
 M141 SHOWS RTU 5 PROVIDING 9125 CFM OF SUPPLY. WHICH
 ONE IS CORRECT? AIR DISTRIBUTION SYSTEMS SHALL BE
 DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 2. PG M321: AN 8 INCH ROUND, 175 CFM C-TYPE GRILL IS
 SHOWN ON FLOOR PLAN NEAR PHARMACY STORAGE ROOM 132. THE
 FLOOR PLAN DOES NOT INDICATE FROM WHERE THIS GRILL WILL
 BE SUPPLIED. THIS APPEARS TO BE A POSSIBLE DRAFTING
 ERROR. PLEASE CORRECT. FBCM 603.1.
  
 3. PG M141: DETAIL 2, NO INFORMATION COULD BE FOUND ON
 PLANS OR IN STRUCTURAL CALCULATIONS REGARDING
 ANTICIPATED WIND PRESSURES ON OUTDOOR AND ROOFTOP
 EQUIPMENT AND APPLIANCES. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FBCB PER FBCM 301.13. PROVIDE WIND
 LOAD CALCULATIONS WITH CORRESPONDING ATTACHMENT DETAILS
 FOR BUILDING PLAN REVIEW. IF MANUFACTURER HAS TESTED
 AND DOCUMENTED DETAILS FOR ATTACHMENT, THEY MAY BE USED
 TO DEMONSTRATE COMPLIANCE (PROVIDE DOCUMENTATION).
 ALSO, PLEASE PROVIDE EQUIPMENT AND APPLIANCE
 MANUFACTURER?S DATA SHOWING ALL OUTDOOR EQUIPMENT SUCH
 AS CONDENSING UNITS, ROOFTOP A/C UNITS, EXHAUST FANS
 AND THE ROOFTOP CONDENSER RACK TO BE DESIGNED AND
 CONSTRUCTED TO WITHSTAND ANTICIPATED WIND PRESSURES
 CALCULATED IN ACCORDANCE WITH FBCB SECTION 1609.
  
 4. PG M141 AND R141: ARE CONDENSING UNITS AND THE
 ROOFTOP CONDENSER RACK TO BE INSTALLED ON SOLID CURBS
 OR STANDS? DETAILS ON PLANS ARE UNCLEAR AS TO WHICH
 TYPE OF CURB IS TO BE USED AT WHICH LOCATION. WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT ON RAISED
 EQUIPMENT SUPPORTS, A MINIMUM CLEARANCE HEIGHT IS
 REQUIRED IN ACCORDANCE WITH FBCB TABLE 1509.7.
 NOTE PRE-ENGINEERED A/C STANDS ARE DEFINED BY FAC RULE
 9B-72 AS STRUCTURAL COMPONENTS. IF SUCH STANDS ARE
 USED, A PRODUCT APPROVAL IS REQUIRED AND SHALL BE
 SUBMITTED WITH PERMIT APPLICATION. PRODUCT APPROVALS
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE AHJ IN
 ACCORDANCE WITH FBCB 106.3.3.
  
 5. PG M301: THERE DOES NOT APPEAR TO BE A FIRE RATED
 SEPARATION BETWEEN THE PARKING GARAGE AREA (S-2
 OCCUPANCY) AND THE 1ST FLOOR LOBBY AREA OF THE STORE (M
 OCCUPANCY). WHILE THERE IS A "CODE ANALYSIS" ON PG G001
 INDICATING THAT A FIRE RATED SEPARATION IS NOT REQUIRED
 IN THIS AREA, THE ANALYSIS DOES NOT APPEAR TO BE
 ACCURATE. THE GOVERNING CODE SECTION REGARDING REQUIRED
 SEPARATION IS FBCB 406.2.7 WHICH STATES: ?PARKING
 GARAGES SHALL BE SEPARATED FROM OTHER OCCUPANCIES IN
 ACCORDANCE WITH SECTION 302.3.2.? FBCB TABLE 302.3.2
 FOR SEPARATED USES REQUIRES A MINIMUM 2-HOUR SEPARATION
 BETWEEN THESE OCCUPANCIES. AS IT IS UNKNOWN WHERE THIS
 OCCUPANCY SEPARATION WILL BE PROVIDED, IT IS NOT
 POSSIBLE TO DO A THOROUGH REVIEW OF THE MECHANICAL
 SYSTEMS SHOWN ON THIS PAGE AT THIS TIME. ENSURE THAT
 OPENING PROTECTIVES ARE SHOWN WHENEVER DUCTS PENETRATE
 RATED ASSEMBLIES IN ACCORDANCE WITH FBCM 607.5.
 COORDINATE WITH ARCHITECTURAL PLANS.
  
 6. PG M301: KEYNOTES 1 AND 2 CALL FOR DUCT AND PIPE
 PENETRATIONS THROUGH A FIRE RATED HORIZONTAL ASSEMBLY
 (SEE COMMENT ABOVE). SHOW HOW THESE OPENINGS ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.6 AND FBCB
 712.4.1.2.
  
 7. PG M301 AND M321: FLOOR PLAN AND KEYNOTES CALL FOR
 COMBINATION FIRE/SMOKE DAMPERS. HOW WILL THE SMOKE
 DAMPERS BE ACTUATED? DETAIL #14 ON PG E941 SHOWS A
 SMOKE DETECTOR W/DAMPER INTERFACE BUT IT IS UNCLEAR
 WHERE THESE DETECTORS WILL BE LOCATED AND WHETHER THEY
 ARE TO BE CONNECTED TO THE SMOKE DAMPERS. INDICATE
 CLEARLY ON PLANS HOW THE SMOKE DAMPERS ARE TO BE
 ACTUATED BY ONE OF THE METHODS LISTED IN ACCORDANCE
 WITH FBCM 607.3.2.1.
  
 8. PG M321: THE 16X16 DUCT FOR TF-4 IS SHOWN
 PENETRATING A 2-HOUR RATED WALL ASSEMBLY (TYPE P33X)
 INTO ROOM 155, AS SHOWN ON PG A351. THIS DUCT IS ALSO
 SHOWN RUNNING PARALLEL DIRECTLY ABOVE THE 2-HOUR RATED
 WALL BETWEEN ROOMS 115 AND 161. THESE WALLS APPEAR TO
 BE FROM FLOOR TO UNDERSIDE OF ROOF DECK. THE FIRE/SMOKE
 DAMPERS IN THE DUCTS FEEDING THE UPPER EDC AREA DO NOT
 APPEAR TO BE LOCATED WHERE FIRE-RESISTANCE RATED
 CONSTRUCTION IS BEING PROVIDED. THIS AREA REQUIRES
 ADDITIONAL CLARIFICATION AS TO THE DESIGN INTENT AND
 THE LOCATION OF ALL FIRE-RESISTANCE RATED ASSEMBLIES.
 PLEASE COORDINATE WITH ARCHITECTURAL PLANS, SHOWING
 OPENING PROTECTIVES AT ALL DUCT PENETRATIONS OF RATED
 ASSEMBLIES IN ACCORDANCE WITH FBCM 607.5.
  
 9. ALL MECHANICAL FLOOR PLANS: BY WHAT MEANS ARE THE
 EXHAUST FANS FOR RESTROOM AREAS BEING CONTROLLED? ARE
 THEY TO RUN CONTINUOUS, RUN BY LIGHT SWITCH OR RUN BY
 OCCUPANCY SENSORS? PLEASE INDICATE ON FAN PRV SCHEDULE
 HOW FANS ARE TO BE CONTROLLED. WHERE MECHANICAL EXHAUST
 IS REQUIRED BY FBCM TABLE 403.3, RECIRCULATION OF AIR
 FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR SUPPLIED
 TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN
 EXCESS OF THAT REQUIRED BY FBCM TABLE 403.3. SHOW PRV
 CONTROLS FOR RESTROOM AREAS TO BE IN COMPLIANCE WITH
 THIS SECTION. ALSO, SEE FBCM 401.3.
  
 10. PG M301 AND M601: AC-2 SHALL BE PROVIDED WITH FAN
 SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH FBCM
 606.2 AND 606.4.
  
 11. OUTSIDE AIR CALCULATIONS COULD NOT BE FOUND ON
 PLANS. PLEASE PROVIDE CALCULATINS SHOWING OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD, AMOUNT OF VENTILATION
 REQUIRED AND AMOUNT OF VENTILATION PROVIDED IN
 ACCORDANCE WITH FBCM TABLE 403.3. ALSO, PROVIDE AN AIR
 BALANCE SHEDULE SHOWING BUILDING SYSTEMS TO BE IN
 BALANCE IN ACCORDANCE WITH FBCM 403.1 AND FBCB
 13-409.1.ABC.2.
  
 12. SYSTEM SIZING CALCULATIONS: SOME ASPECTS OF THE
 COOLING LOAD CALCULATION DATA DO NOT CORRESPOND WITH
 THE INFORMATIN PROVIDED IN THE EQUIPMENT SCHEDULE ON PG
 M141. EXAMPLE: RTU-02 IN THE SCHEDULE SHOWS THE AIRFLOW
 AT 12,380 CFM WHILE THE AIRFLOW IN THE SYSTEM SIZING
 CALCULATION SHOWS 16,483. PLEASE SHOW INFORMATION IN
 CALCULATIONS TO BE ACCURATE WITH RESPECT TO THE
 INFORMATION SHOWN ON PLANS. ALSO, MOST SYSTEMS IN THE
 CALCULATIONS SHOW RETURN AIR FLOW RATES IN EXCESS OF
 THE SUPPLY AIR FLOW RATES. HOW IS THIS POSSIBLE? ARE
 THE RTU'S EXHAUSTING AIR? WILL THIS CONDITION PUT THE
 SPACES IN NEGATIVE PRESSURE? PLEASE CLARIFY. SEE FBC
 13-407.1.ABC.1.1. SEE ALSO COMMENT #11 ABOVE.
  
 13. ENERGY CALCULATIONS: SEVERAL OF THE A/C SYSTEMS
 SHOWN IN THE SYSTEM REPORT COMPLIANCE PORTION OF THE
 ENERGY CALCULATIONS DO NOT CORRESPOND WITH THE
 INFORMATION PROVIDED IN THE EQUIPMENT SCHEDULE ON
 PLANS.
 EXAMPLE 1: RTU-01 IS IDENTIFIED ON PLANS AS A LENNOX
 48,000 BTU/H SYSTEM BUT IN ENERGY CALCULATIONS IT IS
 SHOWN AS AN AAON SYSTEM SIZED BETWEEN 65,000 AND 135,
 000 BTU/H.
 EXAMPLE 2: RTU-02 IS IDENTIFIED ON PLANS AS A LCC360H4B
 339,506 BTU/H SYSTEM WITH AN EER OF 10.1 BUT IN ENERGY
 CALCULATIONS IT IS SHOWN AS A LCC156H2B SIZED BETWEEN
 135,000 AND 240,000 BTU/H WITH AN EER OF 12.2.
 THE VALUES ENTERED ON THE ENERGY CALCULATION MUST
 CORRESPOND WITH THE INFORMATION ON THE PLAN IN ORDER TO
 SHOW COMPLIANCE WITH FBCB CHAPTER 13. THESE ARE ONLY
 TWO EXAMPLES OF MANY DISCREPENCIES BETWEEN THE PLANS
 AND ENERGY CALCULATIONS. PLEASE VERIFY ALL INPUT DATA
 IN THE ENERGY CALCULATIONS WITH THE INFORMATION SHOWN
 ON THE PLANS TO ENSURE THE ACCURACY OF THE
 CALCULATIONS. THE PLANS AND SPECIFICATIONS, INCLUDING
 THE ENERGY CODE CALCULATIONS, SHALL SHOW, IN SUFFICIENT
 DETAIL, ALL PERTINENT DATA AND FEATURES OF THE BUILDING
 AND THE EQUIPMENT AND SYSTEMS AS HEREIN GOVERNED
 INCLUDING, BUT NOT LIMITED TO: DESIGN CRITERIA,
 EXTERIOR ENVELOPE COMPONENT MATERIALS, U-VALUES OF THE
 ENVELOPE SYSTEMS, R-VALUES OF INSULATING MATERIALS,
 SIZE AND TYPE OF APPARATUS AND EQUIPMENT, EQUIPMENT AND
 SYSTEMS CONTROLS AND OTHER PERTINENT DATA TO INDICATE
 CONFORMANCE WITH THE REQUIREMENTS OF THE CODE IN
 ACCORDANCE WITH FBCB 13-103.3. ENERGY CALCULATIONS WILL
 BE REVIEWED IN THEIR ENTIRETY UPON RESUBMITTAL.
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE
 REFRIGERATION AND WALK-IN COOLER SYSTEMS. THE
 DOCUMENTATION FOR THESE SYSTEMS IS SUFFICIENT WITH THE
 EXCEPTION OF ANY INFORMATION REQUESTED IN ABOVE
 COMMENTS. THE SEPARATE PERMIT MAY BE APPLIED FOR BY
 REFERENCE TO THE MASTER PERMIT NUMBER AND THESE PLANS.
  
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WIH
 INFORMATION ON HOW THE COMMENT IS ADDRESSED AND WHERE
 THE RELEVANT INFORMATION CAN BE LOCATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-07-30 Cont ID  
Sent By kstevens Date 2009-07-30 Time 12:03 Rev Time 0.00
Received By kstevens Date 2009-07-30 Time 12:03 Sent To FIRE
Notes
2009-07-30 12:11:02REVISIONS OK -- SHTS P110, P111, P141, P301, P302,
 P311, P401, P501 & P502.

Review Stop P PLUMBING
Rev No 9 Status P Date 2009-07-02 Cont ID  
Sent By kstevens Date 2009-07-02 Time 08:57 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 1658 Sent To  
Notes
2009-07-02 08:58:22REVISIONS OK -- SHTS P111, P141 & P302

Review Stop P PLUMBING
Rev No 8 Status F Date 2009-04-23 Cont ID  
Sent By kstevens Date 2009-04-23 Time 16:02 Rev Time 0.00
Received By kstevens Date 2009-04-23 Time 16:01 Sent To  
Notes
2009-04-23 16:18:12REVISIONS DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1 (ADMINISTRATIVE)
  
 1. SHT P141 NO REVISIONS NOTED. PLEASE CLOUD AND NUMBER
 ALL REVISIONS. BP-3.0 SHOWS NO NEW REVISIONS. SECTION
 106.1.3.
  
 2. SHT P302. SOME REVISIONS NOTED WITH NO CLOUDS OR
 REVISION NUMBERS. PLEASE INDICATE ALL REVISIONS WITH
 CLOUD AND A REVISION NUMBER. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-04-23 Cont ID  
Sent By kstevens Date 2009-04-23 Time 16:16 Rev Time 0.00
Received By kstevens Date 2009-04-22 Time 16:53 Sent To  
Notes
2009-04-23 16:17:28REVISIONS OK -- SHTS P110, P311, P351, P501, P601.

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-03-05 Cont ID  
Sent By kstevens Date 2009-03-05 Time 16:04 Rev Time 0.00
Received By kstevens Date 2009-03-05 Time 16:03 Sent To  
Notes
2009-03-05 16:54:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 NFPA-58
 FBC-2004 CHAPTER 1
  
 1. SHT P110 THE OFFSET DOWNSTREAM OF THE 10 INCH STORM
 DRAIN BY COL LINE 12 SHALL BE INDICATED AS 12 INCH PIPE
 @ 1/4" PER FT PER TABLE 1106.3. PLEASE INDICATE ON
 PLAN. REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 2. SHT P111 THE PROPANE TANK IS REQUIRED TO BE A
 MINIMUM OF 10 FEET FROM THE BUILDING. NFPA-58 SECTION
 6.2.1 & ANNEX I SECTION I.1 AND FIGURE I.1(B). THE
 PROPANE TANK IS INDICATED UNDER THE BUILDING.
  
 3. SHT P111 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 4. SHT P141 REVISION INDEX SHOWS REVISION BP-3.0. THIS
 REVISION WAS NOT FOUND OR APPROVED. NO REVISIONS WERE
 FOUND ON THIS SHEET. PLEASE CLARIFY. SECTION 106.1.3.
  
 5. SHT P302 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. (SEE
 BETWEEN COL. LINES 1 & 2). THERE WAS A CHANGE/REVISION
 THAT WAS NOT CLOUDED/NUMBERED TO THE RIGHT OF COL. LINE
 1 JUST ABOVE COL. LINE B. PLEASE CLOUD AND NUMBER ALL
 REVISIONS. ALSO REVISION BP-3.0 WAS NOT FOUND OR
 APPROVED. PLEASE CLARIFY. SECTION 106.1.3. PLEASE
 INDICATE WHERE REVISION BP-3.0 CAN BE FOUND.
  
 6. SHT P351 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND.
  
 7. SHT P501 ALL REVISIONS SHALL BE CLOUDED AND
 INDICATED WITH A REVISION NUMBER THAT IS SHOWN ON THE
 REVISION INDEX. SECTION 106.1.3. THERE ARE REVISIONS
 THAT ARE CLOUDED, BUT SHOW NO REVISION NUMBER. ALSO
 REVISION BP-3.0 WAS NOT FOUND OR APPROVED. PLEASE
 CLARIFY. SECTION 106.1.3. PLEASE INDICATE WHERE
 REVISION BP-3.0 CAN BE FOUND. ALSO MANY REVISION
 TRIANGLES WITH THE NUMBERS 1 & 2 ARE SHOWN ON THE FLOOR
 PLAN BUT NOT IN THE REVISION INDEX. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-03-05 Cont ID  
Sent By kstevens Date 2009-03-05 Time 16:00 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 17:07 Sent To  
Notes
2009-03-05 16:03:47REVISIONS OK
  
 SHT P300 REV. BP-3.0
 SHT P301 REV. 8 - REV. BP-3.0 NOT FOUND OR APPROVED
 SHT P401 REV. 32 - REV. BP-3.0 NOT FOUND OR APPROVED
 SHT P421 REV. 32 - REV. BP-3.0 NOT FOUND OR APPROVED
 SHT P431 REV. 32 - REV. BP-3.0 NOT FOUND OR APPROVED
 SHT P502 REV. 26 & REV. 32 - REV. BP-3.0 NOT FOUND OR
 APPROVED

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 11:04 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-07-30 Cont ID  
Sent By kstevens Date 2008-07-30 Time 07:48 Rev Time 0.00
Received By kstevens Date 2008-07-29 Time 12:53 Sent To  
Notes
2008-07-30 07:49:30PLANS REVIEWED AND STAMPED BUT PERMIT WILL STAY IN
 FAILED STATUS UNTIL CONTRACTOR APPLIES FOR PERMIT

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By kstevens Date 2008-06-11 Time 07:32 Rev Time 0.00
Received By kstevens Date 2008-06-09 Time 15:46 Sent To  
Notes
2008-06-11 08:57:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 MUNICIPAL CODE CITY WPB
  
 ****FROM PREVIOUS PLAN REVIEW:
  
 PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME:
  
 1. OK
 2. OK
  
 3. SHT G001 SHEET INDEX. 3 SHEETS ON THE INDEX WERE NOT
 FOUND & 2 "F" SHEETS & 10 "R" SHEETS SUBMITTED ARE NOT
 SHOWN ON THE INDEX. PLEASE CORRELATE. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THERE ARE SHEETS MISSING FROM
 AT LEAST ONE SET OF PLANS. PLEASE CHECK ALL SETS OF
 PLANS TO MAKE SURE THE SHEETS SUBMITTED CORRELATE WITH
 THE SHEET INDEX ON SHT G001.
  
 4. OK
 5. OK
 6. OK
  
 7. SHT A313 SHOW THE CLEAR FLOOR SPACE FOR ACCESSIBLE
 WATER CLOSETS AND LAVS PER SECTIONS 11-4.16.2 &
 11-4.19.3.
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS
 REQUIRED FOR ALL ACCESSIBLE WATER CLOSETS NO MATTER IF
 THEY ARE IN STALLS OR TOILET ROOMS. THE REQUIREMENT IS
 FOR TRANSFERING FROM THE WHEELCHAIR TO THE W/C. THE
 TURNING AREA IS NOT REQUIRED IN THE STALL AND IS A
 DIFFERENT REQUIREMENT FROM THE CLEAR FLOOR SPACE.
  
 8. OK
 9. OK
 10. OK (WILL PROVISO - REQUIRED AT TIME OF FINAL
 PLUMBING INSPECTION)
  
 11. OK
 12. OK
 13. OK
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. ALSO THEPHOTO PROCESSING MAY BE REQUIRED
 TO INSTALL A NEUTRALIZING TANK. PLEASE CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE AT (561)644-1821, OR
 BY FAX (561) 822-2287, OR E-MAIL [email protected]. A
 WRITTEN DETERMINATION FOR BOTH ISSUES SHALL BE
 SUBMITTED WITH PLANS INDICATING THE REQUIREMENT
 OUTCOME. ARTICLE III SECTION 90-124(7). ****RESPONSE
 NOTED, WAITING FOR REVISION FROM RODNEY COMPO.
  
 15. OK
 16. OK
 17. OK
 18. OK (SEE COMMENT #10).
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
  
 24. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS
 REQUIRED FOR THE GAS PERMIT.
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 25. OK
  
 **********NEW COMMENT***********
  
 1B. SHOW THE SHUT OFF VALVE AND THE SECOND STAGE
 REGULATOR ON THE GAS RISER DIAGRAM. THE SHUT OFF VALVE
 SHALL BE INSTALLED UPSTREAM OF THE REGULATOR. SECTION
 409.4.
  
 2B. SUBMIT THE MANUFACTURE SPECIFICATION SHEETS FOR THE
 SECOND STAGE GAS REGULATOR. INDICATE MODEL NUMBER AND
 SHOW LISTING FOR REGULATOR ON SHEETS. SECTION 410.2.
  
 3B. VENTED REGULATORS SHALL COMPLY WITH SECTION 410.3.
  
 4B. SHTS P100, P3OO & P502 THE FLOOR DRAIN SHOWN IN THE
 MECHANICAL ROOM SHALL CONNECT TO THE SANITARY SYSTEM,
 NOT THE STORM SYSTEM. ARTICLE III SECTION 203(A).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-09 Cont ID  
Sent By kstevens Date 2008-04-09 Time 18:30 Rev Time 0.00
Received By kstevens Date 2008-04-07 Time 15:54 Sent To  
Notes
2008-04-09 19:00:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 MUNICIPAL CODE CITY WPB
  
 PLANS IN FOR PLAN REVIEW ONLY AT THIS TIME:
  
 1. SHT G001 PLUMBING FIXTURE COUNT SHOWS SIX LAVS
 REQUIRED. PER TABLE 403.1 SEVEN LAVS ARE REQUIRED.
 PLEASE CORRECT REQUIRED LAV FIXTURE COUNT.
  
 2. SHT G001 FIXTURES PROVIDED SHOWS 3 DRINKING
 FOUNTAINS REQUIRED. 5 DRINKING FOUNTAINS ARE REQUIRED.
 DRINKING WATER AVAILABLE AT THE FOOD SERVICE ONLY
 COUNTS AS ONE FIXTURE EXCEPTION. SHOW 4 DRINKING
 FOUNTAINS. TABLE 403.1 & SECTION 410.1.
  
 3. SHT G001 SHEET INDEX. 3 SHEETS ON THE INDEX WERE NOT
 FOUND & 2 "F" SHEETS & 10 "R" SHEETS SUBMITTED ARE NOT
 SHOWN ON THE INDEX. PLEASE CORRELATE. SECTION 106.1.2.
  
 4. SHT A121 SHOW COMPLIANCE WITH SECTIONS 1210.1 &
 1210.2 OF THE BUILDING CODE FOR FINISHES.
  
 5. SHTS A141 & P111 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106& 1107 WITH
 ALL SUBSECTIONS AND TABLES. INDICATE THE TOTAL AREA TO
 BE DRAINED FOR EACH ROOF DRAIN. INCLUDE IN THE
 CALCULATIONS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ANY ROOF AREA THAT DRAINS ON TO THE ROOF
 AREA FROM ABOVE. SUBMIT THE ELEVATION OF THE ROOF AT
 THE HIGH POINTS AND LOW POINTS AS WELL AS THE ELEVATION
 OF THE TOP OF ALL PARAPETS TO VERIFY CALCULATIONS. AS
 SHOWN ON SHT P111 THE SQUARE FOOTAGE INDICATED IS THE
 SAME FOR EACH ROOF DRAIN, BUT THE AREAS ARE DIFFERENT
 PER THE SLOPE AND THE CRICKETS.
  
 6. SHT A313 DETAIL #1 SHOW THE ACCESSIBLE WATER CLOSETS
 IN TOILET ROOMS 108 & 109 TO BE 1'6" OFF THE SIDE WALL
 OF THE STALL PER FIGURE 11-30E.
  
 7. SHT A313 SHOW THE CLEAR FLOOR SPACE FOR ACCESSIBLE
 WATER CLOSETS AND LAVS PER SECTIONS 11-4.16.2 &
 11-4.19.3.
  
 8. SHT A313 DETAIL #20ACCESSIBLE WATER CLOSET IS
 INDICATED AS 1'5" CLEAR OFF THE WALL TO THE CENTERLINE
 OF THE W/C. THE W/C IS REQUIRED TO BE 1'6" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE PER FIGURE 11-30E.
 PLEASE CHANGE DETAIL.
  
 9. PLEASE SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH SECTION 11-4.15 AND
 ALL SUBSECTIONS. AT LEAST 50% OF DRINKING FOUNTAINS
 PROVIDED SHALL BE ACCESSIBLE PER SECTION
 11-4.1.3(10)(B).
  
 10. SHT FD1 EQUIPMENT SCHEDULE ITEMS FS0593 & SB0036
 WATER FILTERS SHALL MEET THE REQUIREMENTS OF NSF-42.
 SECTION 611.1. PLEASE SUBMIT MANUF. SPECIFICATION
 SHEETS INDICATING COMPLIANCE.
  
 11. SHT P100 KEY NOTES #2 & #3 ALL PIPING SHALL BE
 SHOWN FOR STORM AND SANITARY WITHIN THE FOOTPRINT OF
 THE BUILDING AND TO 5 FEET OUTSIDE THE BUILDING. THIS
 PIPING SHALL BE INSTALLED BY THE PLUMBING CONTRACTOR
 NOT THE SITE UTILITY CONTRACTOR AS INDICATED PER
 FLORIDA STATUTES 489. SHOW ALL PIPE SIZES, CLEANOUTS,
 OFFSETS, DFU'S FOR SANT. AND ALL PIPE SIZE, OFFSETS,
 C/O'S, SQUARE FOOTAGE ETC. PER TABLES 710.1, 710.2,
 1106.3 AND SECTIONS 708 & 1101.8.
  
 12. SHT P300 DETAIL #4/P300 SHOWS THE TOP OF THE HUB TO
 BE 1/2" ABOVE FINISHED FLOOR. SECTION 802.3.2 REQUIRES
 THE TOP OF THE HUB TO BE 1" ABOVE FINISHED FLOOR.
 PLEASE CORRECT DETAIL.
  
 13. SHT P300 3" FLOOR DRAIN IN MECHANICAL ROOM 003
 INDICATES DETAIL 4/P601. DETAIL 4/P601 IS A GREASE
 INTERCEPTOR DETAIL. PLEASE CLARIFY. SECTION 106.1.1.
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. ALSO THEPHOTO PROCESSING MAY BE REQUIRED
 TO INSTALL A NEUTRALIZING TANK. PLEASE CONTACT RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE AT (561)644-1821, OR
 BY FAX (561) 822-2287, OR E-MAIL [email protected]. A
 WRITTEN DETERMINATION FOR BOTH ISSUES SHALL BE
 SUBMITTED WITH PLANS INDICATING THE REQUIREMENT
 OUTCOME. ARTICLE III SECTION 90-124(7).
  
 15. SHT P301 DETAIL #5 THERMAL EXPANSION CONTROL IS
 REQUIRED AT THE WATER HEATER PER SECTION 607.3.2.
 PLEASE INDICATE METHOD.
  
 16. SUBMIT AN ISOMETRIC RISER DIAGRAM FOR THE 10" AREA
 DRAINS AT THE TRUCK RAMP/LOADING AREA SHOWN ON SHT
 P110. SHOW ALL PIPE SIZES AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SHOW THE SQUARE FOOTAGE
 DRAINED BY EACH DRAIN AND SUBMIT CALCULATIONS SHOWING
 THE VERTICAL CONTRIBUTION ADDED TO EACH AREA. SHOW THE
 TERMINATION POINT OF PIPING. SECTIONS 106.3.5.1.3, 1106
 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 17. SHT P302 FILTERS FOR FCW-F, (FS-0593), SHALL MEET
 THE REQUIREMENTS OF NSF-42. SECTION 611.1. PLEASE
 SUBMIT MANUF. SPECIFICATION SHEETS.
  
 18. SHT P302 THE RO SYSTEM SHALL MEET THE REQUIREMENTS
 OF NSF-58. SECTION 611.2. PLEASE SUBMIT MANUF.
 SPECIFICATION SHEETS.
  
 19. SHT P311 DETAIL #3 THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD.
  
 20. SHT P351 DETAIL #5 THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD.
  
 21. SHT P501 DETAILS #2 & #5 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. PLEASE
 SHOW THE WATER HAMMER ARRESTORS NEAR THE FIXTURES.
  
 22. SHT P501 DETAILS #1, #3 & #4 SUBMIT HORIZONTAL
 BUILDING STORM & SANITARYDRAIN ISOMETRIC RISER
 DIAGRAMS FOR THE UNDERGROUND PIPING TO 5FT OUTSIDE THE
 BUILDING. SHOW ALL PIPE SIZE, CLEANOUTS, OFFSETS DFU'S
 FOR SANT. AND ALL PIPE SIZE, C/O'S, OFFSETS, SQUARE
 FOOTAGE ETC. PER TABLES 710.1, 710.2, 1106.3 AND
 SECTIONS 106.3.5.1.3, 708 & 1101.8.
  
 23. SUBMIT VACUUM/CONDENSATE ISOMETRIC RISER DIAGRAM
 SHOWING ALL PIPE SIZES, OFFSETS, VENTS AS WELL AS THE
 TERMINATION POINT FOR THE SYSTEM. SECTION 106.3.5.1.3.
  
 24. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING IS
 REQUIRED FOR THE GAS PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--LENGHTS OF CUT SECTIONS NOT SHOWN.
  
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED WHEN
 COMMENT 24(A) SUBMITTED.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. THE LOCATION OF THE GAS METER, THE GENERATOR AND
 ASSOCIATED GAS PIPING SHALL BE INDICATED ON THE
 PLUMBING SHEETS TO VERIFY THE GAS ISOMETRIC PIPING.
 SECTION 106.1.2.
  
 25. PLANS ARE NOT 100% COMPLETE AT THIS TIME AND MORE
 COMMENTS MAY FOLLOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 9 Status P Date 2009-09-23 Cont ID  
Sent By jroach Date 2009-09-23 Time 18:24 Rev Time 0.00
Received By jroach Date 2009-09-23 Time 18:24 Sent To  
Notes
2009-09-23 18:27:22ZONING PLAN REVIEW
  
 PERMIT NO.: 08020128
 ADDRESS: 1760 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: BRETT HANSEN
 TELEPHONE NO.: 813.957.0570
 SCOPE OF REVIEW: REVISIONS TO SHEETS A020, A151, A217,
 A362, AND A611
  
 REVIEW STATUS: PASSED WITH PROVISO(S)
  
 THIS REVIEW IS SUBJECT TO THE FOLLOWING PROVISO(S):
  
 1) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO), THE CIVIL, SITE, AND LANDSCAPE PLANS SHALL BE
 REVISED TO SHOW THE MODIFICATIONS TO THE EXTERIOR (I.E.
 SIDEWALKS, STEPS, ETC.)
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 8 Status P Date 2009-07-30 Cont ID  
Sent By jroach Date 2009-07-30 Time 11:58 Rev Time 0.00
Received By jroach Date 2009-07-30 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 7 Status F Date 2009-07-14 Cont ID  
Sent By jroach Date 2009-07-14 Time 16:21 Rev Time 0.00
Received By jroach Date 2009-07-14 Time 16:21 Sent To  
Notes
2009-07-14 16:27:10ZONING PLAN REVIEW
  
 PERMIT NO.: 08020128
 ADDRESS: 1760 PALM BEACH LAKES BLVD.
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: REVISIONS
  
 REVIEW STATUS: ALL REVISIONS SUBMITTED ARE PASSED,
 EXCEPT SHEETS A152 AND A161, WHICH ARE FAILED. PLEASE
 SEE COMMENTS BELOW.
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURSUANT TO THE AMERICANS WITH DISABILITIES ACT
 (ADA) GUIDELINE, DETECTABLE WARNINGS SHALL CONSIST OF
 RAISED TRUNCATED DOMES WITH A DIAMETER OF NOMINAL 0.9
 IN (23 MM), A HEIGHT OF NOMINAL 0.2 IN (5 MM) AND A
 CENTER-TO-CENTER SPACING OF NOMINAL 2.35 IN (60 MM) AND
 SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER
 LIGHT-ONDARK, OR DARK-ON-LIGHT. THE MATERIAL USED TO
 PROVIDE CONTRAST SHALL BE AN INTEGRAL PART OF THE
 WALKING SURFACE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 6 Status P Date 2009-02-10 Cont ID  
Sent By jroach Date 2009-02-10 Time 18:53 Rev Time 0.00
Received By jroach Date 2009-02-10 Time 18:53 Sent To  
Notes
2009-02-10 18:59:40ZONING PLAN REVIEW
  
 PERMIT NO.: 08020128
 ADDRESS: 1760 PALM BEACH LAKES BOULEVARD
 CONTRACTOR/CONTACT: BRETT NANSEN
 TELEPHONE NO.: (813) 957.0570
  
 REVIEW STATUS: REVISIONS PASSED
  
 REVISIONS TO THE FOLLOWING SHEETS HAVE BEEN APPROVED,
 SUBJECT TO THE PROVISOS IDENTIFIED ON SHEET C-100 OF
 THE APPROVED PLANS:
  
 SHEET A110
 SHEET A111
 SHEET A151
 SHEET A201
  
 PLEASE NOTE THAT PURSUANT TO AN EMAIL TO SCOTT
 COPENHARVE (RYAN COMPANIES), CITY STAFF WOULD LIKE TO
 LOOK INTO RELOCATING SOME OF THE PROPOSED PARKING LOT
 SITE LIGHTING TO REDUCE CONFLICTS WITH THE PROPOSED
 LANDSCAPE MATERIAL. IT APPEARS THAT SOME OF THE LIGHTS
 MAY INTERFERE WITH THE FUTURE GROWTH OF THE TREES,
 INHIBITING THE TREES, AS WELL AS THE EFFECTIVENESS OF
 THE LIGHTING. PLEASE CONTACT ME FURTHER REGARDING THIS
 TOPIC OF DISCUSSION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 5 Status P Date 2008-09-12 Cont ID  
Sent By jroach Date 2008-09-12 Time 15:12 Rev Time 0.00
Received By jroach Date 2008-09-12 Time 15:12 Sent To  
Notes
2008-09-12 15:17:37***PASSED WITH PROVISOS***
  
 SEE SHEET C-100 FOR A LIST OF GENERAL PROVISOS, WHICH
 INCLUDE THE FOLLOWING:
  
 1) ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT, AND SHALL CONFORM TO THE REGULATIONS OF THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT.
  
 2) ALL REMOVAL AND RELOCATION OF TREES SHALL BE DONE
 IN ACCORDANCE WITH APPROVED TREE ALTERATION PERMIT.
  
 3) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY, THE FOLLOWING SHALL OCCUR:
  
 3A) THE SHOPPING CART CONTAINMENT SYSTEM SHALL BE
 INSTALLED.
  
 3B) THE CITY OF WEST PALM BEACH CRIME PREVENTION
 OFFICER SHALL BE PROVIDED WITH A WALK-THROUGH OF THE
 FACILITY AND SHALL APPROVE THE SECURITY PLAN, INCLUDING
 THE PLACEMENT OF CAMERAS, SECURITY PERSONNEL, ETC.
  
 3C) THE POLICE SUBSTATIONS SHALL BE PROVIDED WITH
 ELECTRIC, PHONE, AND DATA CONNECTIONS, AS WELL AS
 DESK/WORK SPACE, AND A MONITOR CONNECTED TO THE
 SECURITY SYSTEM.
  
 3D) THREE (3) PARKING SPACES, AS DESIGNED ON THE
 APPROVED PLAN, SHALL BE DESIGNATED AS "POLICE ONLY"
 SPACES.
  
 3E) THE ENTIRE PROPERTY SHALL BE REPLATTED BY
 SUBMITTING AN APPLICATION TO THE CITY'S PLANNING AND
 ZONING DEPARTMENT.
  
 THE FOLLOWING PROVISOS ARE SPECIFIC TO THE SHEET
 INDICATED:
  
 1) SHEET G-002 - THIS SHEET IS TO SHOW THE LOCATION OF
 THE BUILDING ONLY. SHEET C-106 SHALL BE USED AS THE
 MASTER SITE PLAN.
  
 2) SHEET A-151 - SEE SHEET C-203 FOR THE PARKING STALL
 LAYOUT. ADDITIONALLY, SMALL CAR SPACES, AS INDICATED ON
 SHEET C-106, SHALL BE DESIGNATED AS SUCH.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-07-23 Cont ID  
Sent By jroach Date 2008-07-23 Time 14:45 Rev Time 0.00
Received By jroach Date 2008-07-23 Time 14:45 Sent To  
Notes
2008-07-23 15:00:23***PASSED WITH PROVISOS***
  
 1) ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT, AND SHALL CONFORM TO THE REGULATIONS OF THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT.
  
 2) ALL REMOVAL AND RELOCATION OF TREES SHALL BE DONE IN
 ACCORDANCE WITH APPROVED TREE ALTERATION PERMIT.
  
 3) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING SHALL OCCUR:
  
 A) THE SHOPPING CART CONTAINMENT SYSTEM SHALL BE
 INSTALLED.
  
 B) THE CITY OF WEST PALM BEACH CRIME PREVENTION OFFICER
 SHALL BE PROVIDED WITH A WALK-THROUGH OF THE FACILITY
 AND SHALL APPROVE THE SECURITY PLAN, INCLUDING THE
 PLACEMENT OF CAMERAS, SECURITY PERSONNEL, ETC.
  
 C) THE POLICE SUBSTATIONS SHALL BE PROVIDED WITH
 ELECTRIC, PHONE, AND DATA CONNECTIONS, AS WELL AS
 DESK/WORK SPACE, AND A MONITOR CONNECTED TO THE
 SECURITY SYSTEM.
  
 D) THREE (3) PARKING SPACES, AS DESIGNED ON THE
 APPROVED PLAN, SHALL BE DESIGNATED AS "POLICE ONLY"
 SPACES.
  
 E) THE ENTIRE PROPERTY SHALL BE REPLATTED BY SUBMITTING
 AN APPLICATION TO THE CITY'S PLANNING AND ZONING
 DEPARTMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-07-23 Cont ID  
Sent By jroach Date 2008-07-23 Time 14:45 Rev Time 0.00
Received By jroach Date 2008-07-22 Time 16:35 Sent To  
Notes
2008-07-22 16:38:56REVIEW CANNOT BE COMPLETED UNTIL INFORMATION HAS BEEN
 PROVIDED REGARDING POTENTIAL DEED RESTRICTION FROM 1975
 REGARDING BUILDING SETBACK OFF OF PALM BEACH LAKES
 BOULEVARD.STAFF HAS CONTACTED ED STACKER, ATTORNEY
 FOR TARGET, REGARDING THIS MATTER.HE HAS FORWARDED IT
 ON TO TARGET TO BE ADDRESSED.ZONING WILL PASS THE
 REVIEW UPON RECEIPT OF INFORMATION THAT THE DEED
 RESTRICTION HAS BEEN REMOVED.IF IT HAS NOT BEEN
 ADDRESSED PRIOR TO COMPLETION OF REVIEW BY THE OTHER
 TRADES, ZONING WILL FAIL THIS REVIEW AND PASS IT UPON
 RESUBMITTAL.
  
 CONTACT JOHN ROACH, SENIOR PLANNER, FOR ADDITIONAL
 INFORMATION AND/OR QUESTIONS REGARDING THIS MATTER.
 (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By jroach Date 2008-06-10 Time 15:47 Rev Time 0.00
Received By jroach Date 2008-06-10 Time 15:47 Sent To  
Notes
2008-06-10 15:57:03***FAILED***
  
 1) PRIOR TO SUBMISSION FOR A BUILDING PERMIT, THE WEST
 PALM BEACH POLICE DEPARTMENT - CRIME PREVENTION UNIT
 SHALL REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS.
 PLEASE PROVIDE A LETTER INDICATING THEIR APPROVAL OF
 SUCH.PLEASE CONTACT KELLY CARSILLO AT (561)
 822-1620.
  
 2) A UNITY OF TITLE SHALL BE RECORDED IN THE PUBLIC
 RECORDS OF PALM BEACH COUNTY, ENCOMPASSINGN ALL OF THE
 PROPERTY OWNED BY TARGET.A COPY OF THE RECORDED
 VERSION SHALL BE PROVIDED PRIOR TO ISSUANCE OF A
 BUILDING PERMIT.
  
 3) PLEASE PROVIDE DOCUMENTATION THAT TARGET HAS CLOSED
 ON THAT PORTION OF THE MCDONALD'S PARKING LOT THAT IS
 PROPOSED TO BE INCLUDED WITHIN THE DEVELOPMENT.
  
 4) PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 WHEN MEASURED IN A RESIDENTIAL ZONING DISTRICT.THERE
 IS A SMALL AREA NEAR THE SOUTHEAST CORNER OF THE
 BUILDING, JUST OUTSIDE OF THE PROPERTY LINE, THAT
 EXCEEDS THESE LEVELS.A PROVISO CAN BE ISSUED FOR THIS
 IF IT IS THE ONLY THING THAT NEEDS TO BE REVISED...A
 REVISION TO THE PERMIT WILL NEED TO BE SUBMITTED PRIOR
 TO THE INSTALLATION OF THE ON-SITE LIGHTING SHOWING THE
 CORRECT LEVELS.
  
 5)PROOF OF A POSTED BOND SHALL BE PROVIDED FOR LAND
 STABILIZATION, EROSION CONTROL, ETC.
  
 6) PLEASE PROVIDE INFORMATION REGARDING THE PLACEMENT
 OF THE SHOPPING CART CONTAINMENT SYSTEM...IT APPEARS TO
 EXTEND OUSIDE OF TARGET'S PROPERTY.
  
 7) WHEEL STOPS WILL BE REQUIRED FOR ALL PARKING SPACES
 NOT LOCATED UNDER THE BUILDING.A PROVISO CAN BE
 ISSUED FOR THIS.
  
 FYI...THE IMPROVEMENTS SHOWN ON THE MCDONALD'S PORTION
 OF THE PROJECT WILL NEED TO BE INSTALLED PRIOR TO THE
 ISSUANCE OF A CERTIFICATE OF OCCUPANCY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By jroach Date 2008-03-06 Time 19:11 Rev Time 0.00
Received By jroach Date 2008-03-06 Time 19:11 Sent To  
Notes
2008-03-06 19:41:24***FAILED***
  
 1) PLANS DO NOT MATCH THOSE APPROVED BY THE CITY
 COMMISSION (ORDINANCE 4091-07).A MAJOR AMENDMENT TO
 THE COMMERCIAL PLANNED DEVELOPMENT (CPD) WILL BE
 REQURIED.THIS IS CURRENTLY IN PROCESS.UPON APPROVAL
 OF THE NEW PLANS BY THE COMMISSION, ALL PERMIT DRAWINGS
 WILL NEED TO MATCH THOSE APPROVED.
  
 THE FOLLOWING ARE SOME COMMENTS PROVIDED AS AN FYI AND
 SHOULD BE ADDRESSED....A FULL ZONING REVIEW WILL BE
 COMPLETED UPON SUBMITTAL OF THE PLANS, FOLLOWING
 APPROVAL BY THE CITY COMMISSION:
  
 A) PRIOR TO SUBMISSION FOR A BUILDING PERMIT, THE WEST
 PALM BEACH POLICE DEPARTMENT - CRIME PREVENTION UNIT
 SHALL REVIEW AND APPROVE ALL CONSTRUCTION DRAWINGS.
 PLEASE PROVIDE A LETTER INDICATING THEIR APPROVAL OF
 SUCH.PLEASE CONTACT KELLY CARSILLO AT (561)
 822-1620.
  
 B) A PLAT SHALL BE APPROVED BY THE CITY AND THEN
 RECORDED PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 C) THE POLICE SUBSTATION LOCATED ON THE PARKING LEVEL
 SHALL CONTAIN ELECTRIC, PHONE, DATA CONNECTION,
 DESK/WORKSPACE, AND A VIDEO MONITOR CONNECTED TO THE
 SECURITY SYSTEM.
  
 D) THREE (3) POLICE-ONLY PARKING SPACES SHALL BE
 PROVIDED NEAR THE POLICE SUBSTATION.
  
 E) A CURRENT AND ACCURATE SURVEY SHALL BE PROVIDED WITH
 EACH SET OF SITE PLANS.
  
 F) WORK IS BEING SHOWN ON THE ADJACENT PROPERTY.
 PLEASE COORDINATE THIS WITH THE CITY'S CONSTRUCTION
 SERVICES DEPARTMENT.
  
 G) PHOTOMETRIC LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 WHEN MEASURED IN A RESIDENTIAL ZONING DISTRICT (SOUTH
 PROPERTY LINE).ADJUST LEVELS ACCORDINGLY.
  
 H) ARCHITECTURAL ELEMENTS WERE TO BE BUILD AROUND THE
 SCUPPERS ON THE REAR ELEVATION AND EXTEND THE ENTIRE
 HEIGHT OF THE BUILDING.THESE WERE TO PROVIDE
 ARTICULATION IN THE REAR BUILDING FACADE.THESE ARE
 NOT SHOWN ON THE PROPOSED ELEVATIONS.
  
 I) ENSURE COMPLIANCE AND PROVIDE THE DOCUMENTATION
 REQUIRED BY ORDINANCE NO. 4060-07 (SEE ATTACHED),
 INCLUDING STORMWATER POLLUTION PREVENTION PLAN, EROSION
 CONTROL BOND, LAND STABLIZATION BOND, TEMPORARY
 CONSTRUCTION FENCING, ETC.PLEASE REFER TO THE
 ATTACHED ORDINANCE AND RESOLUTION REGARDING SUCH.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1448.