| | BUILDING PLAN REVIEW |
| | PERMIT: 08020127 |
| | ADD: 1002 PASEO ANDORRA |
| | CONT: HUMBERTINA PRADO |
| | TEL: (561)502-9716 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST2-09-08 |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)106.3.3 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT 'APPROVAL |
| | FOR THE SHITTERS. |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | _XX_1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | XX_2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | _XX___ 3.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC |
| | R310. |
| | |
| | _XX___ 4.PROVIDE A FLOOR PLAN SHOWING WHERE THE |
| | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH |
| | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3 |
| | ABOVE. |
| | |
| | 3)THE PRODUCT APPROVAL SUBMITTED IS FOR SINGLE HUNG |
| | WINDOW; HOWEVER THE INFORMATION IN THE PACKAGE FROM THE |
| | MANUFACTURER IS STATING SLIDING WINDOWS (HORIZONTAL |
| | WINDOW). PLEASE SUBMIT THE CORRECT PRODUCT APPROVAL FOR |
| | THE WINDOWS MATCHING THE WINDOWS TO BE INSTALLED. |
| | |
| | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING |
| | LAND VALUE. OUR VALUATION REFERENCE IS ICC ( BVD) |
| | MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3* |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |