Plan Review Details - Permit 08020119
Plan Review Stops For Permit 08020119
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-02-07 Cont ID  
Sent By mcarsill Date 2008-02-07 Time 16:01 Rev Time 0.00
Received By mcarsill Date 2008-02-07 Time 15:41 Sent To  
Notes
2008-02-07 15:57:111. THE EXISTING FIRE DEPARTMENT CONNECTIONS LOCATED ON
 THE EXISTING RISER MUST PROPERLY SWIVEL AND BE EQUIPPED
 WITH PROTECTIVE CAPS.
  
 2. THE NEW FIRE SPRINKLER HEAD INSTALLATION TO COMPLY
 WITH NFPA 13.
  
 3. THE ENTIRE EXISTING FIRE SPRINKLER SYSTEM IS TO MEET
 MINIMUM CODE REQUIREMENTS AS A RECENT INSPECTION REPORT
 FOR THE SYSTEM DECLARED DEFICIENICES.
  
 4. A SPARE HEAD BOX WITH APPROPRIATE STYLE FIRE
 SPRINKLERS ALONG WITH A WRENCH SHALL BE PROVIDED.
  
 5. ANY FIRE SPRINKLER SYSTEM DEFICIENCIES DISCOVERED
 DURING THE NEW INSTALLATION OF FIRE SPRINKLER HEADS
 MUST BE REPAIRED.
  
 6. WHEN THE NEW REPAIRS ARE COMPLETE, THE FIRE
 SPRINKLER SYSTEM SHALL PROVIDE THE PROTECTION FOR WHICH
 IT WAS INTENDED.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-07 Cont ID  
Sent By mawillia Date 2008-02-07 Time 18:31 Rev Time 0.00
Received By mawillia Date 2008-02-06 Time 14:34 Sent To  
Notes
2008-02-06 14:34:17TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved