Plan Review Details - Permit 08020108
Plan Review Stops For Permit 08020108
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-23 Cont ID  
Sent By shill Date 2008-06-23 Time 11:55 Rev Time 0.00
Received By shill Date 2008-06-23 Time 11:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-28 Cont ID  
Sent By shill Date 2008-05-28 Time 14:16 Rev Time 0.00
Received By shill Date 2008-05-28 Time 14:16 Sent To  
Notes
2008-05-28 14:24:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.ALL SHEETS ARE TO INCLUDE THE DATE, FS481,
 FAC61G1-15.23.002.THE ATTORNEY FOR THE FLORIDA BOARD
 OF ARCHITECTS HAS ADVISED THAT THE REVISION DATE DOES
 NOT MEET THIS REQUIREMENT; THE SIGNATURE/SEAL MUST BE
 DATED.
  
 3RD REVIEW, SOME SHEETS HAD A DATE ADDED BY HAND,
 OTHERS HAD ONE ADDED BY STAMP (EITHER METHOD
 ACCEPTABLE), BUT SOME SHEETS (SUCH AS D3.1D) ON ONE SET
 STILL DO NOT HAVE A DATE.PLEASE ADDRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-24 Cont ID  
Sent By shill Date 2008-04-24 Time 12:27 Rev Time 0.00
Received By shill Date 2008-04-24 Time 12:27 Sent To  
Notes
2008-04-24 13:25:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1-5. ADDRESSED.
  
 4.FIRST REVIEW; AL2.1, OCCUPANT LOAD IS DECLARED
 BASED ON 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2,
 CLARIFY USE OF THIS AREA.IS THIS AN EMERGENCY ROOM OR
 AN INPATIENT TREATMENT AREA?THE AREA IS LABELED
 PEDIATRIC ED AND HAS AN AMBULANCE PORTE COCHERE
 OUTSIDE.PLEASE REVISE OCCUPANT LOAD AND RELATED
 REQUIREMENTS.
  
 SECOND REVIEW; MY APOLOGIES IF MY COMMENT WAS NOT
 CLEAR.SEE FBC TABLE 1004.1.2, OUTPATIENT AREAS
 REQUIRE 100SF/PERSON.ISN'T AN EMERGENCY DEPARTMENT
 PRIMARILY OUTPATIENT?OTHER AREAS WERE REVISED AS
 "SLEEPING" WITH AN OCCUPANT LOAD OF 120.INPATIENT
 TREATMENT AREAS CAN BE 240, BUT OUTPATIENT IS 100SF PER
 OCCUPANT.PLEASE CLARIFY USE OF THE SPACE OR REVISE
 THE OCCUPANT LOAD ACCORDINGLY (100SF PER PERSON).
  
 5.PREVIOUS COMMENT NOT ADDRESSED.PLEASE SEE SHEET
 A5.1, DETAILS 20 AND 21, XRAY ROOM IS MARKED AS ED120,
 BUT SHEET A2.2 XRAY IS MARKED AS ED121.EITHER THE
 FLOOR PLAN OR THE DETAILS ARE INCORRECT AS THEY DO NOT
 MATCH.DETAILS FOR XRAY ROOM IS REQUIRED BY FBC435;
 PLEASE CLARIFY LOCATION/CORRELATE DETAILS WITH THE
 FLOOR PLAN.
  
 6-7. ADDRESSED.
  
 NEW COMMENT:
  
 8.ALL SHEETS ARE TO INCLUDE THE DATE, FS481,
 FAC61G1-15.23.002.THE ATTORNEY FOR THE FLORIDA BOARD
 OF ARCHITECTS HAS ADVISED THAT THE REVISION DATE DOES
 NOT MEET THIS REQUIREMENT; THE SIGNATURE/SEAL MUST BE
 DATED.
  
 9.THE ARCHITECT IS TO CERTIFY THE ENERGY CALCS.
 ENERGY CALCS TO BE IN A CODE COMPLIANT FORMAT; PLEASE
 SEE ELECTRIC COMMENTS (INCORRECT YEAR USED, FBC2001
 RATHER THAN FBC2004).
  
 10. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By shill Date 2008-02-27 Time 17:30 Rev Time 0.00
Received By shill Date 2008-02-27 Time 17:30 Sent To  
Notes
2008-02-27 17:30:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.REVISE GOVERNING CODE (FBC2004 WITH 2007
 SUPPLEMENTS/REVISIONS).X1.1.
  
 2.CLARIFY BUILDING TYPE 1B WITH FIRE RESISTANCE OF
 3-2-2.PLEASE DECLARE REQUIRED FIRE RESISTANCE BY
 COMPONENT (WALL, FLOOR, ROOF, ETC.). FBC TABLE 602.
  
 3.DECLARE OCCUPANCY FBC3.
  
 4.AL2.1, OCCUPANT LOAD IS DECLARED BASED ON
 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2, CLARIFY USE OF
 THIS AREA.IS THIS AN EMERGENCY ROOM OR AN INPATIENT
 TREATMENT AREA?THE AREA IS LABELED PEDIATRIC ED AND
 HAS AN AMBULANCE PORTE COCHERE OUTSIDE.PLEASE REVISE
 OCCUPANT LOAD AND RELATED REQUIREMENTS.
  
 5.SHEET A5.1, ROOM 121 XRAY APPEARS TO HAVE AN
 INCORRECT ROOM DESIGNATION AND DETAIL MARKER 21 A5.1
 APPEARS TO BE MISSING FROM THE FLOOR PLAN A2.2, OR THE
 ROOM 120 ON THE FLOOR PLAN IS MISLABELED AS EXISTING
 TREATMENT.
  
 6.DETAIL MARKER 7 A5.3 (TOILET) ON SHEET A2.2 DOES
 NOT CORRELATE WITH THE DETAIL (CORRIDOR).
  
 7.SHOW MANEUVERING CLEARANCE PULL SIDE FBC11-25 FOR
 THE DOOR AT RECEPTION ED131.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-20 Cont ID  
Sent By dpalmer Date 2008-06-20 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2008-06-20 Time 12:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 11:09 Sent To  
Notes
2008-05-22 11:09:22** DENIEDREVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE METHOD *C* CALCULATIONS
 SUBMITTED ARE NOT FILLED OUT COMPLETELY. SHEET REQUIRES
 THE PERSON PREPARING THE DOCUMENT AS WELL AS THE OWNER
 AGENT.
  
 13-103.1, FS 471.025
 FBC 106.1.2,
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-27 Cont ID  
Sent By dpalmer Date 2008-03-27 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2008-03-27 Time 08:36 Sent To  
Notes
2008-03-27 08:37:04** DENIED2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED LIGHTING PERFORMANCE CALCULATIONS PER FBC
 13-415.2.
 PLEASE SEE THE PREVIOUS REVIEW NOTES ALSO NOTED THIS
 PROJECT IS UNDER THE 2004 FBC W/2007 REVISIONS.
 PLEASE SEE THERE IS NOW A NEW FORM 400D-01 SUBMITTED IN
 RESPONSE TO PREVIOUS COMMENT HOWEVER THIS 400D -01 IS
 FROM THE 2001 FBC WHICH IS NO LONGER IN ADOPTION.
 THE RESPONSE LETTER EVEN STATES THE FORM 400D FROM FBC
 CHAPTER 13 WILL BE SUBMITTED. PLEASE VERIFY CODE.
 PLEASE SEE THE ADOPTION OF THE 2004 FBC WAS OCTOBER
 1ST, 2005.HOW IS IT POSSIBLE THAT FORM D WHICH IS
 FROM THE 2001 FBC IS BEING FILLED OUT, SIGNED DATED AND
 SEALED BY THE ENGINEER OF RECORD WHEN THE CODE CHANGED
 ALMOST THREE YEARS AGO?
 ONE COPY OF THE SUBMITTED CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.1 ETC.
 ** THIS 2004 FBC WAS REVISED THREE TIMES WITH
 SUPPLEMENTS SINCE ITS ADOPTION IN OCT 05.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY
 REQUESTED TO STATE MINIMUM RELEVANT CODES ON PLANS.
 THE RESPONSE WAS THIS WAS DONE IN DIVISION SPECS,
 HOWEVER DIVISION SPECS ARE NOT PART OF THE RECORD PLANS
 OR DOCUMENTS SIGNED, DATED OR SEAL BY THE DESIGN
 PROFESSIONAL.
 AS STATED ON PREVIOUS REVIEW PLEASE BE SURE ELECTRICAL
 PLANS CONTAIN THE RELEVANT CODES.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NPFA-101
 2002 NFPA-72
 2002 NFPA-99
  
 ** PLEASE SEE THAT NOT ALL CODES REFLECTED ON THE
 DIVISION SPEC SHEET ARE CURRENT ADOPTED STANDARDS.
 PLEASE LIST THE ABOVE ON PLANS.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH GAVE
 SOME EXAMPLES OF OVER CURRENT PROTECTION WHICH IS SHOWN
 TOO HIGH FOR THE TRANSFORMERS AS SHOWN ON RISER. PLEASE
 SEE FOR EXAMPLE THE OCP FOR TRANSFORMERS FROM GHC TO
 TXRL3 WHICH IS A 25KVA UNIT WITH 100AMP OCP AND TGLC
 WHICH IS 30KVA UNIT WITH 80A OCP.
 PLEASE SEE THESE DO NOT CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE GHC.
 PLEASE SEE 450.3, 240.4, AND 310.16 ETC AND COORDINATE
 ALL ON RISER WITH PANELS AND MINIMUM CODE REQUIREMENTS.
 THE ABOVE ARE GIVEN AS EXAMPLES AS DONE ON PREVIOUS
 REVIEW AND THIS OFFICE IS NOT LISTING ALL POSSIBLE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO MINIMUM ADA LEVELS FOR DEVICES TO BE STATED
 ON PLANS. RESPONSE MENTIONS THIS IS DONE IN DIVISION
 SPECS. THIS IS NOT ACCEPTABLE AS THE RECORD SET OF
 PLANS ARE REQUIRED TO CONTAIN THE *MINIMUM* LEVELS
 ALONG WITH * MINIMUM* DESIGN. 11-4.28.1,.2,.3(4).
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 10:44 Sent To  
Notes
2008-02-11 10:45:09** DENIED REVIEW **
  
 1) NOTE:PLEASE SEE THE PLANS NEED TO CONTAIN THE
 FOLLOWING RELEVANT CODES STATED FOR DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** CODES NEED TO BE ON BOTH ARCHITECTURAL AND
 ELECTRICAL SHEETS.
  
 ** PLEASE SEE THERE PLACES ON COVER SHEET WHICH STATES
 A 2006 FBC INSTEAD OF 2004.
 PLEASE KNOW EVEN WHEN THE CODE CHANGES ON THE FOLLOWING
 CODE CHANGE CYCLE IT WILL BE THE 2007. THIS IS NOTED
 FOR INFORMATION ONLY.
 PLEASE ADJUST NOTES.
  
 2) NOTE: PLEASE CLARIFY THE GFI PROTECTIONFOR
 EXISTING OR NEW PER517.17B IN THE SELECTIVE
 COORDINATION DOCUMENTS SUBMITTED PER 240.12 AND ON
 RISER ON SHEET E0.2.
  
 3) NOTE: PLEASE SEE THE LIGHTING PLANS CONTAIN OS
 DEVICES HOWEVER THESE ARE LISTED ON SYMBOL LEGEND AND
 DO NOT CONTAIN ANY MAXIMUM TIMES.
 PLEASE SUBMIT DETAIL FOR DEVICE. ARE THESE LOW VOLTAGE?
 LINE VOLTAGE? CONTAIN POWER PACKS ETC?
 13-415.1.ABC.1.1, .1.2 (WITH EXCEPTIONS OF SOME
 AREAS).
 FBC 106.1.2 FOR ADDITIONAL INFORMATION NEEDED ON
 PLANS.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FA
 DEVICES PER FBC 11-4.28.1,.2 AND .3 (4).
  
 5) NOTE: PLEASE SEE 450.3 WHICH PERMITS A MAXIMUM OVER
 CURRENT PROTECTION OF THE TRANSFORMER AT 125%. THERE IS
 EXCEPTIONS (SEE TABLE NOTES) AND IF MEETING EXCEPTIONS
 PLEASE SUBMIT ALL INFORMATION ON TYPE OF TRANSFORMER.
 IF THIS IS A STANDARD TRANSFORMER NOT MEETING
 EXCEPTIONS, PLEASE ADJUST FOR 125% MAX.
 TXRL3.
  
 ** PLEASE SEE TCGLD AND TGLD ARE OK.
  
 ** PLEASE SEE EXISTING TCGLC AND TGLC ARE TOO HIGH
 DEPENDING ON TRANSFORMER. THIS COULD BE A SAFETY/FIRE
 HAZARD ISSUE.
 PLEASE CONFIRM TYPE OF TRANSFORMER ETC AT THIS TIME.
 TCGLC SHOULD BE MAX 50AMPS AND TGLC SHOULD BE 70AMPS
 MAX.
  
 6) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-10 Cont ID  
Sent By mwennerg Date 2008-04-10 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2008-04-10 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By mwennerg Date 2008-03-13 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2008-03-13 Time 13:46 Sent To  
Notes
2008-03-13 13:53:16***DENIED***
  
 1) PLEASE SEE MECHANICAL COMMENTS REGARDING DUCT
 LOCATIONS RELATIVE TO FIRE RATED PARTITIONS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) SITE TO BE CLEANED OF EXCESSIVE CONSTRUCTION DEBRIS
 DAILY.
  
 4) PLEASE ADD NOTE TO DOOR SCHEDULE INDICATING FIRE
 RATED DOORS TO BE PROVIDED WITH UL LISTED CLOSERS.
  
 5) PLEASE IDENTIFY DOORS PROVIDED WITH PANIC HARDWARE
 IN DOOR SCHEDULE.
  
 6) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 7) BUILDING FIRE PROTECTION EQUIPMENT TO BE MAINTAINED.
 IN ADDITION TO THE FIRE SPRINKLER SYSTEM, SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 14:34 Sent To  
Notes
2008-06-06 14:40:31TO "COMM" BD#47--PLANS ON RACK/1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 11:38 Sent To  
Notes
2008-05-08 11:46:23TO "COMM" BD#22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 08:22 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 08:22 Sent To  
Notes
2008-03-24 08:22:46TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-13 Cont ID  
Sent By mwennerg Date 2008-03-13 Time 13:59 Rev Time 0.00
Received By mwennerg Date 2008-02-06 Time 13:36 Sent To  
Notes
2008-02-06 13:41:20TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-28 Cont ID  
Sent By tgordon Date 2008-03-28 Time 08:21 Rev Time 2.00
Received By tgordon Date 2008-03-28 Time 08:21 Sent To  
Notes
2008-03-28 08:43:14*** PROVISO ***
 1) UNWANTED FIRE DAMPERS AT THE SMOKE PARTITIONS WILL
 NEED TO BE REMOVED AND NOT LOCKED OPEN, PER 2004 FBC/M
 607.2.
  
 2) AFTER REMOVING UNWANTED FIRE DAMPERS AND REPLACING
 THE DUCT SECTION SEAL AROUND PENETRATIONS TO PREVENT
 FREE PASSAGE OF SMOKE, PER 2004 FBC 710.6.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By tgordon Date 2008-02-29 Time 14:06 Rev Time 4.00
Received By tgordon Date 2008-02-29 Time 14:06 Sent To  
Notes
2008-02-29 15:08:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 *** THE FALLOWING NOTES PERTAIN TO MECHANICAL PLAN PAGE
 M1.01 NEW CONSTRUCTION.
  
 1) SEE 16X12 RETURN AIR DUCT FROM ROOM ED118 TO WEST
 CORRIDOR IS PENETRATING A 1HR. RATED PARTITION (SEE
 YELLOW HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004
 FBC/M 607.5.3.
  
 2) SEE 16X10 SUPPLY AIR DUCT SAME AS ABOVE IS
 PENETRATING A 1HR. RATED PARTITION (SEE YELLOW HIGH
 LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.3.
  
 3) SEE 12X8 SUPPLY AIR DUCT IN WEST CORRIDOR IS
 PENETRATING A 1HRS. RATED PARTITION (SEE YELLOW HIGH
 LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4
 OR STATE THE EXCEPTION BEING MET.
  
 4) SEE 2HRS RATED PARTITION SEPARATING THE NORTH PART
 OF THE WING FROM THE SOUTH 6 DUCTS HAVE FIRE DAMPERS
 BUT NEED TO BE SMOKE DAMPERS (SEE YELLOW HIGH LIGHT ON
 PLAN), PLEASE CORRECT PER 2004 FBC/M 607.5.4 OR STATE
 THE EXCEPTION BEING MET.
  
 5) SEE 18X16 AND 26X18 DUCTS PENETRATING THE EAST END
 OF THE 2HRS RATED PARTITION (SEE YELLOW HIGH LIGHT ON
 PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 OR STATE
 THE EXCEPTION BEING MET.
  
 6) SEE 54X16 RETURN AIR DUCT AT THE SOUTHEAST CORNER OF
 PLAN IS PENETRATING A 1HR. RATED PARTITION (SEE YELLOW
 HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M
 607.5.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2008-03-05 Cont ID  
Sent By jleech Date 2008-03-05 Time 14:23 Rev Time 0.00
Received By jleech Date 2008-03-05 Time 14:20 Sent To  
Notes
2008-03-05 14:39:02PROVISO;
 1 MED-GAS PERMIT REQUIRED, BY A LICENSED MED-GAS
 CONTRACTOR. COPIES OF PICTURE CERIFICATIONS FROM
 QUALIFIER, INSTALLER, AND BRAZER MUST BE WITH PERMIT
 APPLICATION.
 2. A CERTIFIED COPY OFTHE MEDICAL GAS TEST REPORT MUST
 BE AVAILABLE AT THE TIME OF CITY INSPECTORS FINAL
 MED-GAS INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-03-05 Cont ID  
Sent By jleech Date 2008-03-05 Time 15:01 Rev Time 0.00
Received By jleech Date 2008-03-05 Time 14:59 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved