| Plan Review Stops For Permit 08020108 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-06-23 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-06-23 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-28 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-05-28 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2008-05-28 14:24:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 1.ALL SHEETS ARE TO INCLUDE THE DATE, FS481, | | | FAC61G1-15.23.002.THE ATTORNEY FOR THE FLORIDA BOARD | | | OF ARCHITECTS HAS ADVISED THAT THE REVISION DATE DOES | | | NOT MEET THIS REQUIREMENT; THE SIGNATURE/SEAL MUST BE | | | DATED. | | | | | | 3RD REVIEW, SOME SHEETS HAD A DATE ADDED BY HAND, | | | OTHERS HAD ONE ADDED BY STAMP (EITHER METHOD | | | ACCEPTABLE), BUT SOME SHEETS (SUCH AS D3.1D) ON ONE SET | | | STILL DO NOT HAVE A DATE.PLEASE ADDRESS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-24 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-24 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2008-04-24 13:25:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1-5. ADDRESSED. | | | | | | 4.FIRST REVIEW; AL2.1, OCCUPANT LOAD IS DECLARED | | | BASED ON 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2, | | | CLARIFY USE OF THIS AREA.IS THIS AN EMERGENCY ROOM OR | | | AN INPATIENT TREATMENT AREA?THE AREA IS LABELED | | | PEDIATRIC ED AND HAS AN AMBULANCE PORTE COCHERE | | | OUTSIDE.PLEASE REVISE OCCUPANT LOAD AND RELATED | | | REQUIREMENTS. | | | | | | SECOND REVIEW; MY APOLOGIES IF MY COMMENT WAS NOT | | | CLEAR.SEE FBC TABLE 1004.1.2, OUTPATIENT AREAS | | | REQUIRE 100SF/PERSON.ISN'T AN EMERGENCY DEPARTMENT | | | PRIMARILY OUTPATIENT?OTHER AREAS WERE REVISED AS | | | "SLEEPING" WITH AN OCCUPANT LOAD OF 120.INPATIENT | | | TREATMENT AREAS CAN BE 240, BUT OUTPATIENT IS 100SF PER | | | OCCUPANT.PLEASE CLARIFY USE OF THE SPACE OR REVISE | | | THE OCCUPANT LOAD ACCORDINGLY (100SF PER PERSON). | | | | | | 5.PREVIOUS COMMENT NOT ADDRESSED.PLEASE SEE SHEET | | | A5.1, DETAILS 20 AND 21, XRAY ROOM IS MARKED AS ED120, | | | BUT SHEET A2.2 XRAY IS MARKED AS ED121.EITHER THE | | | FLOOR PLAN OR THE DETAILS ARE INCORRECT AS THEY DO NOT | | | MATCH.DETAILS FOR XRAY ROOM IS REQUIRED BY FBC435; | | | PLEASE CLARIFY LOCATION/CORRELATE DETAILS WITH THE | | | FLOOR PLAN. | | | | | | 6-7. ADDRESSED. | | | | | | NEW COMMENT: | | | | | | 8.ALL SHEETS ARE TO INCLUDE THE DATE, FS481, | | | FAC61G1-15.23.002.THE ATTORNEY FOR THE FLORIDA BOARD | | | OF ARCHITECTS HAS ADVISED THAT THE REVISION DATE DOES | | | NOT MEET THIS REQUIREMENT; THE SIGNATURE/SEAL MUST BE | | | DATED. | | | | | | 9.THE ARCHITECT IS TO CERTIFY THE ENERGY CALCS. | | | ENERGY CALCS TO BE IN A CODE COMPLIANT FORMAT; PLEASE | | | SEE ELECTRIC COMMENTS (INCORRECT YEAR USED, FBC2001 | | | RATHER THAN FBC2004). | | | | | | 10. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, | | | FBC13-103.1. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-27 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-27 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2008-02-27 17:30:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.REVISE GOVERNING CODE (FBC2004 WITH 2007 | | | SUPPLEMENTS/REVISIONS).X1.1. | | | | | | 2.CLARIFY BUILDING TYPE 1B WITH FIRE RESISTANCE OF | | | 3-2-2.PLEASE DECLARE REQUIRED FIRE RESISTANCE BY | | | COMPONENT (WALL, FLOOR, ROOF, ETC.). FBC TABLE 602. | | | | | | 3.DECLARE OCCUPANCY FBC3. | | | | | | 4.AL2.1, OCCUPANT LOAD IS DECLARED BASED ON | | | 240SF/OCCUPANT.SEE FBC TABLE 1004.1.2, CLARIFY USE OF | | | THIS AREA.IS THIS AN EMERGENCY ROOM OR AN INPATIENT | | | TREATMENT AREA?THE AREA IS LABELED PEDIATRIC ED AND | | | HAS AN AMBULANCE PORTE COCHERE OUTSIDE.PLEASE REVISE | | | OCCUPANT LOAD AND RELATED REQUIREMENTS. | | | | | | 5.SHEET A5.1, ROOM 121 XRAY APPEARS TO HAVE AN | | | INCORRECT ROOM DESIGNATION AND DETAIL MARKER 21 A5.1 | | | APPEARS TO BE MISSING FROM THE FLOOR PLAN A2.2, OR THE | | | ROOM 120 ON THE FLOOR PLAN IS MISLABELED AS EXISTING | | | TREATMENT. | | | | | | 6.DETAIL MARKER 7 A5.3 (TOILET) ON SHEET A2.2 DOES | | | NOT CORRELATE WITH THE DETAIL (CORRIDOR). | | | | | | 7.SHOW MANEUVERING CLEARANCE PULL SIDE FBC11-25 FOR | | | THE DOOR AT RECEPTION ED131. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-06-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-20 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-20 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-05-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-22 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-22 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2008-05-22 11:09:22 | ** DENIEDREVIEW** | | | | | | | | | | | | 1) NOTE: PLEASE SEE THE METHOD *C* CALCULATIONS | | | SUBMITTED ARE NOT FILLED OUT COMPLETELY. SHEET REQUIRES | | | THE PERSON PREPARING THE DOCUMENT AS WELL AS THE OWNER | | | AGENT. | | | | | | 13-103.1, FS 471.025 | | | FBC 106.1.2, | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-27 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-27 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2008-03-27 08:37:04 | ** DENIED2ND REVIEW** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY | | | REQUESTED LIGHTING PERFORMANCE CALCULATIONS PER FBC | | | 13-415.2. | | | PLEASE SEE THE PREVIOUS REVIEW NOTES ALSO NOTED THIS | | | PROJECT IS UNDER THE 2004 FBC W/2007 REVISIONS. | | | PLEASE SEE THERE IS NOW A NEW FORM 400D-01 SUBMITTED IN | | | RESPONSE TO PREVIOUS COMMENT HOWEVER THIS 400D -01 IS | | | FROM THE 2001 FBC WHICH IS NO LONGER IN ADOPTION. | | | THE RESPONSE LETTER EVEN STATES THE FORM 400D FROM FBC | | | CHAPTER 13 WILL BE SUBMITTED. PLEASE VERIFY CODE. | | | PLEASE SEE THE ADOPTION OF THE 2004 FBC WAS OCTOBER | | | 1ST, 2005.HOW IS IT POSSIBLE THAT FORM D WHICH IS | | | FROM THE 2001 FBC IS BEING FILLED OUT, SIGNED DATED AND | | | SEALED BY THE ENGINEER OF RECORD WHEN THE CODE CHANGED | | | ALMOST THREE YEARS AGO? | | | ONE COPY OF THE SUBMITTED CALCULATIONS ARE BEING | | | RETAINED BY THIS OFFICE. | | | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.1 ETC. | | | ** THIS 2004 FBC WAS REVISED THREE TIMES WITH | | | SUPPLEMENTS SINCE ITS ADOPTION IN OCT 05. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH SPECIFICALLY | | | REQUESTED TO STATE MINIMUM RELEVANT CODES ON PLANS. | | | THE RESPONSE WAS THIS WAS DONE IN DIVISION SPECS, | | | HOWEVER DIVISION SPECS ARE NOT PART OF THE RECORD PLANS | | | OR DOCUMENTS SIGNED, DATED OR SEAL BY THE DESIGN | | | PROFESSIONAL. | | | AS STATED ON PREVIOUS REVIEW PLEASE BE SURE ELECTRICAL | | | PLANS CONTAIN THE RELEVANT CODES. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NPFA-101 | | | 2002 NFPA-72 | | | 2002 NFPA-99 | | | | | | ** PLEASE SEE THAT NOT ALL CODES REFLECTED ON THE | | | DIVISION SPEC SHEET ARE CURRENT ADOPTED STANDARDS. | | | PLEASE LIST THE ABOVE ON PLANS. | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WHICH GAVE | | | SOME EXAMPLES OF OVER CURRENT PROTECTION WHICH IS SHOWN | | | TOO HIGH FOR THE TRANSFORMERS AS SHOWN ON RISER. PLEASE | | | SEE FOR EXAMPLE THE OCP FOR TRANSFORMERS FROM GHC TO | | | TXRL3 WHICH IS A 25KVA UNIT WITH 100AMP OCP AND TGLC | | | WHICH IS 30KVA UNIT WITH 80A OCP. | | | PLEASE SEE THESE DO NOT CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE GHC. | | | PLEASE SEE 450.3, 240.4, AND 310.16 ETC AND COORDINATE | | | ALL ON RISER WITH PANELS AND MINIMUM CODE REQUIREMENTS. | | | THE ABOVE ARE GIVEN AS EXAMPLES AS DONE ON PREVIOUS | | | REVIEW AND THIS OFFICE IS NOT LISTING ALL POSSIBLE. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH | | | RESPECT TO MINIMUM ADA LEVELS FOR DEVICES TO BE STATED | | | ON PLANS. RESPONSE MENTIONS THIS IS DONE IN DIVISION | | | SPECS. THIS IS NOT ACCEPTABLE AS THE RECORD SET OF | | | PLANS ARE REQUIRED TO CONTAIN THE *MINIMUM* LEVELS | | | ALONG WITH * MINIMUM* DESIGN. 11-4.28.1,.2,.3(4). | | | | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-02-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-10 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-10 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2008-02-11 10:45:09 | ** DENIED REVIEW ** | | | | | | 1) NOTE:PLEASE SEE THE PLANS NEED TO CONTAIN THE | | | FOLLOWING RELEVANT CODES STATED FOR DESIGN. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | ** CODES NEED TO BE ON BOTH ARCHITECTURAL AND | | | ELECTRICAL SHEETS. | | | | | | ** PLEASE SEE THERE PLACES ON COVER SHEET WHICH STATES | | | A 2006 FBC INSTEAD OF 2004. | | | PLEASE KNOW EVEN WHEN THE CODE CHANGES ON THE FOLLOWING | | | CODE CHANGE CYCLE IT WILL BE THE 2007. THIS IS NOTED | | | FOR INFORMATION ONLY. | | | PLEASE ADJUST NOTES. | | | | | | 2) NOTE: PLEASE CLARIFY THE GFI PROTECTIONFOR | | | EXISTING OR NEW PER517.17B IN THE SELECTIVE | | | COORDINATION DOCUMENTS SUBMITTED PER 240.12 AND ON | | | RISER ON SHEET E0.2. | | | | | | 3) NOTE: PLEASE SEE THE LIGHTING PLANS CONTAIN OS | | | DEVICES HOWEVER THESE ARE LISTED ON SYMBOL LEGEND AND | | | DO NOT CONTAIN ANY MAXIMUM TIMES. | | | PLEASE SUBMIT DETAIL FOR DEVICE. ARE THESE LOW VOLTAGE? | | | LINE VOLTAGE? CONTAIN POWER PACKS ETC? | | | 13-415.1.ABC.1.1, .1.2 (WITH EXCEPTIONS OF SOME | | | AREAS). | | | FBC 106.1.2 FOR ADDITIONAL INFORMATION NEEDED ON | | | PLANS. | | | | | | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR FA | | | DEVICES PER FBC 11-4.28.1,.2 AND .3 (4). | | | | | | 5) NOTE: PLEASE SEE 450.3 WHICH PERMITS A MAXIMUM OVER | | | CURRENT PROTECTION OF THE TRANSFORMER AT 125%. THERE IS | | | EXCEPTIONS (SEE TABLE NOTES) AND IF MEETING EXCEPTIONS | | | PLEASE SUBMIT ALL INFORMATION ON TYPE OF TRANSFORMER. | | | IF THIS IS A STANDARD TRANSFORMER NOT MEETING | | | EXCEPTIONS, PLEASE ADJUST FOR 125% MAX. | | | TXRL3. | | | | | | ** PLEASE SEE TCGLD AND TGLD ARE OK. | | | | | | ** PLEASE SEE EXISTING TCGLC AND TGLC ARE TOO HIGH | | | DEPENDING ON TRANSFORMER. THIS COULD BE A SAFETY/FIRE | | | HAZARD ISSUE. | | | PLEASE CONFIRM TYPE OF TRANSFORMER ETC AT THIS TIME. | | | TCGLC SHOULD BE MAX 50AMPS AND TGLC SHOULD BE 70AMPS | | | MAX. | | | | | | 6) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS PER 13-415.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE/REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-04-10 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-04-10 |
Time |
14:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-03-13 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-03-13 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2008-03-13 13:53:16 | ***DENIED*** | | | | | | 1) PLEASE SEE MECHANICAL COMMENTS REGARDING DUCT | | | LOCATIONS RELATIVE TO FIRE RATED PARTITIONS. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) SITE TO BE CLEANED OF EXCESSIVE CONSTRUCTION DEBRIS | | | DAILY. | | | | | | 4) PLEASE ADD NOTE TO DOOR SCHEDULE INDICATING FIRE | | | RATED DOORS TO BE PROVIDED WITH UL LISTED CLOSERS. | | | | | | 5) PLEASE IDENTIFY DOORS PROVIDED WITH PANIC HARDWARE | | | IN DOOR SCHEDULE. | | | | | | 6) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 7) BUILDING FIRE PROTECTION EQUIPMENT TO BE MAINTAINED. | | | IN ADDITION TO THE FIRE SPRINKLER SYSTEM, SEPARATE SHOP | | | DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-06 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-06 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2008-06-06 14:40:31 | TO "COMM" BD#47--PLANS ON RACK/1 ROLL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-05-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-08 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-08 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2008-05-08 11:46:23 | TO "COMM" BD#22 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-24 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-24 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2008-03-24 08:22:46 | TO "COMM" BD#37 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-03-13 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-02-06 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-02-06 13:41:20 | TO "COMM" BD#38 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-28 |
Time |
08:21 |
Rev Time |
2.00 |
| Received By |
tgordon |
Date |
2008-03-28 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2008-03-28 08:43:14 | *** PROVISO *** | | | 1) UNWANTED FIRE DAMPERS AT THE SMOKE PARTITIONS WILL | | | NEED TO BE REMOVED AND NOT LOCKED OPEN, PER 2004 FBC/M | | | 607.2. | | | | | | 2) AFTER REMOVING UNWANTED FIRE DAMPERS AND REPLACING | | | THE DUCT SECTION SEAL AROUND PENETRATIONS TO PREVENT | | | FREE PASSAGE OF SMOKE, PER 2004 FBC 710.6. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-29 |
Time |
14:06 |
Rev Time |
4.00 |
| Received By |
tgordon |
Date |
2008-02-29 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2008-02-29 15:08:03 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | *** THE FALLOWING NOTES PERTAIN TO MECHANICAL PLAN PAGE | | | M1.01 NEW CONSTRUCTION. | | | | | | 1) SEE 16X12 RETURN AIR DUCT FROM ROOM ED118 TO WEST | | | CORRIDOR IS PENETRATING A 1HR. RATED PARTITION (SEE | | | YELLOW HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 | | | FBC/M 607.5.3. | | | | | | 2) SEE 16X10 SUPPLY AIR DUCT SAME AS ABOVE IS | | | PENETRATING A 1HR. RATED PARTITION (SEE YELLOW HIGH | | | LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.3. | | | | | | 3) SEE 12X8 SUPPLY AIR DUCT IN WEST CORRIDOR IS | | | PENETRATING A 1HRS. RATED PARTITION (SEE YELLOW HIGH | | | LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 | | | OR STATE THE EXCEPTION BEING MET. | | | | | | 4) SEE 2HRS RATED PARTITION SEPARATING THE NORTH PART | | | OF THE WING FROM THE SOUTH 6 DUCTS HAVE FIRE DAMPERS | | | BUT NEED TO BE SMOKE DAMPERS (SEE YELLOW HIGH LIGHT ON | | | PLAN), PLEASE CORRECT PER 2004 FBC/M 607.5.4 OR STATE | | | THE EXCEPTION BEING MET. | | | | | | 5) SEE 18X16 AND 26X18 DUCTS PENETRATING THE EAST END | | | OF THE 2HRS RATED PARTITION (SEE YELLOW HIGH LIGHT ON | | | PLAN), PLEASE COMPLY WITH 2004 FBC/M 607.5.4 OR STATE | | | THE EXCEPTION BEING MET. | | | | | | 6) SEE 54X16 RETURN AIR DUCT AT THE SOUTHEAST CORNER OF | | | PLAN IS PENETRATING A 1HR. RATED PARTITION (SEE YELLOW | | | HIGH LIGHT ON PLAN), PLEASE COMPLY WITH 2004 FBC/M | | | 607.5.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
P |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-03-05 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-03-05 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2008-03-05 14:39:02 | PROVISO; | | | 1 MED-GAS PERMIT REQUIRED, BY A LICENSED MED-GAS | | | CONTRACTOR. COPIES OF PICTURE CERIFICATIONS FROM | | | QUALIFIER, INSTALLER, AND BRAZER MUST BE WITH PERMIT | | | APPLICATION. | | | 2. A CERTIFIED COPY OFTHE MEDICAL GAS TEST REPORT MUST | | | BE AVAILABLE AT THE TIME OF CITY INSPECTORS FINAL | | | MED-GAS INSPECTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-03-05 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-03-05 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|