Plan Review Details - Permit 08020104
Plan Review Stops For Permit 08020104
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By shill Date 2008-04-10 Time 14:55 Rev Time 0.00
Received By shill Date 2008-04-10 Time 14:55 Sent To  
Notes
2008-04-10 15:14:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE VALUE FOR THE SITEWORK APPEARS LOW.PLEASE
 GIVE A BREAKDOWN OF VALUE, BY SQUARE FOOT, SUMMARIZING
 ALL WORK TO BE PERFORMED UNDER THIS SITEWORK PERMIT.
  
 2.THE PLANS DO NOT APPEAR ACCURATE AS TO SCOPE OF
 WORK.FOR INSTANCE, A HATCHED AREA IS SHOWN IN THE
 CENTER OF THE LARGE BUILDING AS AN ADDITION, BUT MY
 UNDERSTANDING IS THAT HALF OF THE BUILDING WAS TORN
 DOWN AND IS IN THE PROCESS OF BEING RECONSTRUCTED, WEST
 SIDE.CODE REQUIREMENTS FOR ACCESSIBILITY MAY BE
 AFFECTED BY SCOPE OF WORK, SEE OTHER COMMENTS.
  
 3.SEE FBC11-4.6.2, ACCESSIBLE PARKING SPACES SHALL BE
 DISPERSED AND LOCATED CLOSEST TO THE ACCESSIBLE
 ENTRANCES.
  
 4.AN EXISTING RAMP IS SHOWN ON THE WEST SIDE OF THE
 BUILDING.IS THIS RAMP COMPLIANT FOR ACCESSIBILITY
 FBC11-4.8 OR IS THIS FOR LOADING?
  
 5.SHOW THE ACCESSIBLE ROUTE AT THE REAR OF THE
 BUILDING, NORTH SIDE.THE EXIT DOOR APPEARS TO HAVE A
 LANDING, SEE FBC11-4.1.3(9), SAME NUMBER OF ACCESSIBLE
 MEANS OF EGRESS SHALL BE PROVIDED AS REQUIRED FOR
 EXITS.THE GRAPHIC SHOWS LANDSCAPING IN THIS AREA.IS
 THIS A REQUIRED ACCESSIBLE EXIT?THE ACCESSIBLE ROUTE
 TO GET AWAY FROM THE BUILDING IS NOT CLEARLY IDENTIFIED
 ON THE NORTH, EAST, AND WEST SIDES.IT IS MY
 UNDERSTANDING THAT A PORTION OF THE BUILDING IS NEW
 CONSTRUCTION; WAS TORN DOWN AND REBUILT.
  
 6. SHOW ALL REQUIRED DETECTABLE WARNINGS,
 FBC11-4.29.5.
  
 7. DECLARE TOTAL NUMBER OF PARKING SPACES AND NUMBER OF
 ACCESSIBLE SPACES, FBC11-4.1.2(5)(A).
  
 8.PLEASE SEE FBC11-4.1.6, OWNER HAS AN OBLIGATION TO
 PROVIDE ACCESSIBLE FEATURES EVEN WHEN THOSE FEATURES
 ARE NOT BEING ALTERED.THIS CODE SECTION AFFECTS OTHER
 COMMENTS.PLEASE CONTACT ME IF YOU NEED ASSISTANCE IN
 DETERMINING SCOPE OF REQUIRED CODE COMPLIANCE.
  
 9. SEE ADA 4.29.2* DETECTABLE WARNINGS ON WALKING
 SURFACES. DETECTABLE WARNINGS SHALL CONSIST OF RAISED
 TRUNCATED DOMES WITH A DIAMETER OF NOMINAL 0.9 IN (23
 MM), A HEIGHT OF NOMINAL 0.2 IN (5 MM) AND A
 CENTER-TO-CENTER SPACING OF NOMINAL 2.35 IN (60 MM) AND
 SHALL CONTRAST VISUALLY WITH ADJOINING SURFACES, EITHER
 LIGHT-ON-DARK, OR DARK-ON-LIGHT.
  
 A. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C3.
 HTTP://WWW.ACCESS-BOARD.GOV/ADAAG/DWS/UPDATE.HTM.
 TACTILE SURFACE SHOWN, PLEASE REVISE DETAIL TO SHOW
 TRUNCATED DOMES.
  
 B. REVISE CONCRETE SIDEWALK CURB RAMP DETAIL, SHEET C3,
 TO SHOW THE VISUAL CONTRAST REQUIRED.IF THE DESIGN
 INTENT AND COMPLIANCE ARE NOT CLEAR, CALCULATIONS PER
 ADA4.29.2 MAY BE REQUIRED.
  
 10. SHOW ALL REQUIRED DETECTABLE WARNING LOCATIONS ON
 THE PLAN, HAZARDOUS VEHICULAR AREAS, FBC11-4.29.5.
  
 11. C2, THE GRAPHIC FOR THE ACCESSIBLE ROUTE AND SOME
 OF THE PARKING LOT STRIPING IS THE SAME AS BUILDING
 ADDITION AREA.PLEASE REVISE SO THAT THE TWO ARE
 CLEARLY DEFINED.IDENTIFICATION OF THE STRIPING WOULD
 BE HELPFUL.
  
 12. SHEET C4, SECTION AA AND BB, PLEASE ADVISE AS TO
 WHERE THESE SECTIONS ARE SHOWN ON THE PLAN.REVISE TO
 CLEARLY SHOW COMPLIANCE WITH DETECTABLE WARNING
 REQUIREMENTS.
  
 13. C1, C2 SHOW EXISTING HANDICAP RAMPS AT VEHICULAR
 APPROACH (STREET TO PARKING LOT) AREAS.PLEASE PROVIDE
 A DETAIL TO SHOW COMPLIANCE WITH FBC11-4.29.5; NOTE
 THAT EXITING IS TO THE PUBLIC WAY FBC11, DEFINITIONS.
  
 14. SEE ATTACHED ACCESSIBLE PARKING DETAIL.PLEASE
 REVISE C4 TO BE CONSISTENT WITH THIS DETAIL WHICH IS
 REQUIRED BY MUNICIPAL CODE.NOTE THAT THE WHEEL STOP
 DIMENSION, ACCESSIBILITY SYMBOL COLOR AND SIZE DO NOT
 CONFORM TO THE STANDARD ADOPTED.
  
 15. PROVIDE A TYPICAL ACCESSIBLE PARKING SIGN,
 FBC11.4.6.4.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-03-28 Cont ID  
Sent By rchokshi Date 2008-03-28 Time 13:38 Rev Time 0.00
Received By rchokshi Date 2008-03-28 Time 13:22 Sent To B
Notes
2008-03-28 13:38:36FAILED FOR FOLLOWING REASONS:
  
 1.PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 DWG C-5 OF C-7 SAYS SEE DWG A1.3,THIS DWG WAS NOT IN
 THE PACKAGE YOU SUBMITTED. PLEASE SUBMIT DWG A1.3
 SHOWING LOCATION & DETAILS OF DUMPSTER PER CITY
 STANDARD.
  
 3. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 4. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 5. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVED.
  
 YOUR SFWMD COPY WAS ISSUED IN 1992. WE DO NOT ALLOW
 MORE THAN 5 YEAR OLD PERMIT. MAY BE YOU TAKE IT BACK TO
 SFWMD FOR REAPPROVAL.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-02-20 Cont ID  
Sent By rchokshi Date 2008-02-20 Time 13:54 Rev Time 0.00
Received By rchokshi Date 2008-02-20 Time 13:51 Sent To  
Notes
2008-02-20 13:54:41FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVED.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 14:00 Rev Time 0.00
Received By kdfreema Date 2008-03-26 Time 17:58 Sent To Z
Notes
2008-03-25 14:00:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 11:44 Sent To ENG
Notes
2008-02-11 11:44:35TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-02-20 Time   Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 11:03 Sent To  
Notes
2008-02-06 11:03:12TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-26 Cont ID  
Sent By kdfreema Date 2008-03-26 Time 17:58 Rev Time 0.00
Received By kdfreema Date 2008-03-26 Time 17:58 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By kdfreema Date 2008-02-28 Time 11:33 Rev Time 0.00
Received By kdfreema Date 2008-02-28 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By kdfreema Date 2008-02-11 Time 08:50 Rev Time 0.00
Received By kdfreema Date 2008-02-11 Time 08:50 Sent To I
Notes
2008-02-11 08:59:21***FAILED***
  
 1. PLEASE PROVIDE THE RECORDED DOCUMENTS SHOWING THAT
 THE 20- FOOT ALLEY EASEMENT HAS BEEN MODIFED AS SHOWN
 ON SHEET C-1. NOTE THAT ZONING WILL NOT PASS THESE
 PLANS UNTIL THAT DOCUMENTATION HAS BEEN PROVIDED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 OR [email protected] WITH QUESTIONS.