Plan Review Details - Permit 08020094
Plan Review Stops For Permit 08020094
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-22 Cont ID  
Sent By mperson Date 2008-02-22 Time 16:24 Rev Time 0.00
Received By mperson Date 2008-02-06 Time 09:40 Sent To  
Notes
2008-02-06 09:40:43TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-03-31 Cont ID  
Sent By rbrown Date 2008-03-31 Time 12:39 Rev Time 0.00
Received By rbrown Date 2008-03-31 Time 12:39 Sent To  
Notes
2008-03-31 12:41:48PLUMBING SHEETS P-1, P-2, AND P-3 REVIEWED BY MIKE
 PERSON ON 3/27/08 UNDER MASTER PERMIT # 07070444

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-22 Cont ID  
Sent By mperson Date 2008-02-22 Time 12:59 Rev Time 0.00
Received By mperson Date 2008-02-22 Time 12:59 Sent To PC
Notes
2008-02-22 16:24:07PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1A) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1B ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 PLUMBING WITH THE2007 SUPPLEMENTS. (PLEASE INDICATE
 THE CODE CYCLE ON THE RESUBMITTED PLANS)
  
 2. PROVIDE TWO COPIES OF ARCHITECTURAL FLOOR PLANS
 WITH ROOM DEMINSIONS MIN 1/8 INCH SCALE. PER CITY OF
 WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.3, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 SECTION 106.1.2 ADDITIONAL DATA.
  
 3. SHEET P-1, PLEASE SHOW COMPLIANCE TO CHAPTER 11
 FLORIDA ACCESSIBILITY CODE FOR THE FOLLOWING FIXTURES.
 PLEASE PROVIDE ELEVATION DETAILS AND CLEALY INDICATE
 CLEAR FLOOR SPACE ON ARCHITECTURAL FLOOR PLANS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.18 URINALS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.18.2 HEIGHT. RIM MAXIMUM 17" A.F.F.
 11-4.18.3 CLEAR FLOOR SPACE. 30" X 48"
 11-4.18.4 FLUSH CONTROLS. MAXIMUM 44" A.F.F.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 (SINK IN LOUNGE 109)
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 4. SHEET P-1, STAPLES INDICATES EXISTING 6" RD,
 HOWEVER PERMIT INFORMATION INDICATES EXISTING BUILDING
 BEING DEMOLISHED. THE REFERENCED MASTER PERMIT
 #07070444 ON THE PERMIT APPLICATION IS ALSO INDICATING
 A NEWLY CONSTRUCTED BUILDING. SHEET M-2, OKEE SQUARE
 PHASE 1 PLUMBING PERMIT IS INDICATING AN 8" RWL DOWN TO
 STORM DRAIN WITH 10" X 6" OVERFLOW OPENINGS. PLEASE
 CORRELATE THE PLANS.
  
 5. SHEET P-1, STAPLES INDICATES EXISTING 4" AND 3"
 SANITARY LINES IN A BUILDING THAT HAS BEEN DEMOED.
 PLEASE CLARIFY HOW THERE ARE EXISTING SANITARY LINES IN
 A BUILDING THAT HAS BEEN COMPLETLY DEMOED. PER CITY OF
 WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. SHEET P-1, RTU CONDENSATE DRAIN LINES ARE BEING
 INDICATED AS DRAINING INTO EXISTING ROOF DRAINS (WHICH
 WERE DEMOED, SEE COMMENT #4). PER FBC PLUMBING SECTION
 314.2.1 CONDENSATE DISPOSAL. CONDENSATE FROM ALL
 COOLING COILS SHALL BE CONVEYED FROM THE DRAIN PAN TO
 AN APPROVED PLACE OF DISPOSAL. ROOF DRAINS ARE NOT AN
 APPROVED METHOD OF DISPOSAL. PLEASE INDICATE CONDENSATE
 DISPOSAL INTO A DRY WELL, CATCH BASIN, OR PLANTED
 AREA.
  
 7. IF IT IS THE INTENT OF THIS PERMIT TO BE FOR
 PLUMBING, PLEASE DELETE ALL AIR CONDITIONING RELATED
 ITEMS FROM SHEET M-3 OKEE SQUARE PHASE 1- PLUMBING
 PERMIT PLANS. PER CITY OF WPB AMENDMENTS TO CHAPTER 1,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. SHEET M-2, ROOF PLAN IS INDICATING 10 X 6 OPENING
 OVERFLOW DRAINAGE (TYPICAL) PLEASE CLARIFY AND CORRECT
 IF THIS OPENING IS 10" X 6". PER CITY OF WPB AMENDMENTS
 TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 9. SHEET M-3, IS INDICATING A PARAPET GUTTER DETAIL
 6'-9" WIDE WITH ROOF DRAINS. IS THIS PARAPET GUTTER
 6'-9" WIDE? WHAT IS THE DEPTH OF THE PARAPET GUTTER?
 THERE IS NO DETAIL OF THE 10 X 6 OVERFLOW DRAINAGE
 THATS BEING INDICATED ON SHEET M-2. PLEASE PROVIDE A
 DETAIL OF THE OVERFLOW DRAINAGE. PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS, 106.1.2 ADDITIONAL DATA AND FBC
 PLUMBING SECTION 1101.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy