| 2008-02-04 16:35:27 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| | BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| | INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| | SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| | INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE |
| | MITIGATION. |
| | |
| | _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| | MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG.PROVIDE |
| | THE MISSING NOA SHEETS. |
| | |
| | _XX_4.)FOR THE FLAT ROOF, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| | SHEET). |
| | |
| | _XX_ 6.)PLEASE PROVIDE INFORMATION IN REGARDS TO |
| | OCCUPANCY OF THE TWO UNITS. |
| | |
| | _XX_ 7.)SEE PRODUCT LIMITATION #7.IF CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT ARE REQUIRED FOR ENHANCED FASTENING PER NOA, |
| | THIS WOULD BE REQUIRED AT TIME OF RESUBMITTAL.PLEASE |
| | SEE GENERAL LIMITATION #7, LAST PAGE OF THE NOA. |