Plan Review Details - Permit 08020059
Plan Review Stops For Permit 08020059
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 09:28 Rev Time 0.00
Received By shill Date 2008-03-10 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By shill Date 2008-02-19 Time 15:18 Rev Time 0.00
Received By shill Date 2008-02-19 Time 15:18 Sent To  
Notes
2008-02-19 15:27:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.STATE DESIGN CRITERIA FOR POOL SAFETY, FBC
 R4101.17.YOU CANNOT CITE CODE SECTIONS ONLY TO SHOW
 CODE COMPLIANCE, FBC*106.2.2.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-02-14 Cont ID  
Sent By btrobaug Date 2008-02-14 Time 10:54 Rev Time 0.00
Received By btrobaug Date 2008-02-14 Time 10:39 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-02-15 Cont ID  
Sent By mperson Date 2008-02-15 Time 10:24 Rev Time 0.00
Received By mperson Date 2008-02-15 Time 10:24 Sent To B
Notes
2008-02-15 10:25:35NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 16:06 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 16:06 Sent To P
Notes
2008-03-13 16:07:31TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 14:07 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 14:07 Sent To Z
Notes
2008-02-29 14:08:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-19 Cont ID  
Sent By shill Date 2008-02-19 Time 15:27 Rev Time 0.00
Received By shill Date 2008-02-05 Time 13:19 Sent To  
Notes
2008-02-05 13:19:59TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-17 Cont ID  
Sent By mperson Date 2008-03-17 Time 08:40 Rev Time 0.00
Received By mperson Date 2008-03-17 Time 08:40 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-06 Cont ID  
Sent By mperson Date 2008-03-06 Time 13:51 Rev Time 0.00
Received By mperson Date 2008-03-06 Time 13:51 Sent To B
Notes
2008-03-06 14:14:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY.
  
 1) SHEET 2, PIPING SCHEMATIC: THE HEAT PUMP IS MISSING
 FROM THE PIPING SCHEMATIC. AT A MINIMUM THE PIPING
 SCHEMATIC SHALL REFECT THE POOL DATA & EQUIPMENT DETAIL
 OF SHEET 1. PER CITY OF WPB AMENDMENTS TO CHAPTER 1,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 AND SECTION 106.1.2 ADDITIONAL DATA.
  
 **THE HEAT PUMP THAT WAS ADDED TO THE RESUBMITTED
 PIPING SCHEMATIC ON SHEET 2, WAS HAND WRITTEN WITH NO
 INDICATION THAT IT WAS ADDED BY THE DESIGN PROFESSIONAL
 ALAN GERWIG PE NO. 39481. PER CHAPTER 471, FLORIDA
 STATUTES ANY REVISIONS TO THE CONSTRUCTION DOCUMENTS
 SHALL BE BY THE DESIGN PROFESSIONAL OF RECORD.
  
 ** ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL
  
 2) **OK** COMMENT ADDRESSED.
  
 3)**OK** COMMENT ADDRESSED.
  
 4)**OK** COMMENT ADDRESSED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By mperson Date 2008-02-15 Time 10:03 Rev Time 0.00
Received By mperson Date 2008-02-15 Time 10:03 Sent To G
Notes
2008-02-15 10:24:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) SHEET 2, PIPING SCHEMATIC: THE HEAT PUMP IS MISSING
 FROM THE PIPING SCHEMATIC. AT A MINIMUM THE PIPING
 SCHEMATIC SHALL REFECT THE POOL DATA & EQUIPMENT DETAIL
 OF SHEET 1. PER CITY OF WPB AMENDMENTS TO CHAPTER 1,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 AND SECTION 106.1.2 ADDITIONAL DATA.
  
 2) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.(DETAIL
 REQUIRED FOR THE CLEANING LINE WITH THE MAKE AND MODEL
 NUMBER OR SUBMIT MANUFACTURE SPECIFICATION SHEET)
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED CLEARLY INDICATING THE MAKE, MODEL
 NUMBER AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By choops Date 2008-03-03 Time 08:43 Rev Time 0.00
Received By choops Date 2008-03-03 Time 08:43 Sent To P
Notes
2008-03-03 08:44:38***APPROVED - RESUB #1***
  
 PROVISO:A FENCE PERMIT SHALL BE PULLED IF ONE DOES
 NOT EXIST ALREADY.
  
  
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By adavila Date 2008-02-13 Time 08:24 Rev Time 0.00
Received By adavila Date 2008-02-11 Time 14:18 Sent To E
Notes
2008-02-13 08:25:31PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PER SECTION 94-304(D)(2)(B), EVERY SWIMMING POOL
 SHALL BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH
 IS INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN
 THE OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIN WHICH A
 SWIMMING POOL IS LOCATED.BARRIERS OR FENCES SHALL BE
 AT LEAST 4 FEET IN HEIGHT ABOVE GRADE.PROVIDE THE
 LOCATION OF THE FENCE AROUND THE SWIMMING POOL ON BOTH
 COPIES OF SURVEY.PLEASE NOTE THAT A FENCE PERMIT
 SHALL BE SUBMITTED PRIOR TO THE APPROVAL OF THIS
 PERMIT.
  
 2. PER SECTION 94-304(D)(2)(C), ACCESS TO AN ACCESSORY
 SWIMMING POOL MUST BE THROUGH A BUILDING OR THROUGH A
 SELF-CLOSING AND SELF-LATCHING GATE OR THROUGH A SCREEN
 ENCLOSURE DOOR WITH LATCHES PLACED AT LEAST 54 INCHES
 ABOVE BOTTOM OF GATE.PROVIDE ACCESS/GATE TO SWIMMING
 POOL ON BOTH COPIES OF SURVEY.
  
 3. PER SECTION 94-305(B)(4), MECHANICAL (POOL)
 EQUIPMENTS MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK.PROVIDE SETBACK DIMENSIONS TO POOL EQUIPMENT
 ON BOTH COPIES OF SURVEY.
  
 COMMENT/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.