| Plan Review Stops For Permit 08020059 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-10 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-10 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-19 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-19 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2008-02-19 15:27:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.STATE DESIGN CRITERIA FOR POOL SAFETY, FBC | | | R4101.17.YOU CANNOT CITE CODE SECTIONS ONLY TO SHOW | | | CODE COMPLIANCE, FBC*106.2.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-14 |
Time |
10:39 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-15 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-15 |
Time |
10:24 |
Sent To |
B |
|
| Notes |
| 2008-02-15 10:25:35 | NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-13 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-13 |
Time |
16:06 |
Sent To |
P |
|
| Notes |
| 2008-03-13 16:07:31 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-29 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-29 |
Time |
14:07 |
Sent To |
Z |
|
| Notes |
| 2008-02-29 14:08:14 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-19 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-05 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2008-02-05 13:19:59 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-17 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-17 |
Time |
08:40 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-06 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-06 |
Time |
13:51 |
Sent To |
B |
|
| Notes |
| 2008-03-06 14:14:10 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE | | | OF CONTINUITY. | | | | | | 1) SHEET 2, PIPING SCHEMATIC: THE HEAT PUMP IS MISSING | | | FROM THE PIPING SCHEMATIC. AT A MINIMUM THE PIPING | | | SCHEMATIC SHALL REFECT THE POOL DATA & EQUIPMENT DETAIL | | | OF SHEET 1. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, | | | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS | | | AND SECTION 106.1.2 ADDITIONAL DATA. | | | | | | **THE HEAT PUMP THAT WAS ADDED TO THE RESUBMITTED | | | PIPING SCHEMATIC ON SHEET 2, WAS HAND WRITTEN WITH NO | | | INDICATION THAT IT WAS ADDED BY THE DESIGN PROFESSIONAL | | | ALAN GERWIG PE NO. 39481. PER CHAPTER 471, FLORIDA | | | STATUTES ANY REVISIONS TO THE CONSTRUCTION DOCUMENTS | | | SHALL BE BY THE DESIGN PROFESSIONAL OF RECORD. | | | | | | ** ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH | | | REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION | | | 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. | | | NOTE: A TRANSMITTAL LETTER IS HELPFUL | | | | | | 2) **OK** COMMENT ADDRESSED. | | | | | | 3)**OK** COMMENT ADDRESSED. | | | | | | 4)**OK** COMMENT ADDRESSED. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-15 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-15 |
Time |
10:03 |
Sent To |
G |
|
| Notes |
| 2008-02-15 10:24:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1) SHEET 2, PIPING SCHEMATIC: THE HEAT PUMP IS MISSING | | | FROM THE PIPING SCHEMATIC. AT A MINIMUM THE PIPING | | | SCHEMATIC SHALL REFECT THE POOL DATA & EQUIPMENT DETAIL | | | OF SHEET 1. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, | | | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS | | | AND SECTION 106.1.2 ADDITIONAL DATA. | | | | | | 2) FBC-2004 SEC. 424.2.6.6.5, OR | | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | | NOT GREATER THAN 12" BELOW THE MINIMUM | | | OPERATING WATER LEVEL OR AS AN | | | ATTACHMENT TO THE SKIMMER.(DETAIL | | | REQUIRED FOR THE CLEANING LINE WITH THE MAKE AND MODEL | | | NUMBER OR SUBMIT MANUFACTURE SPECIFICATION SHEET) | | | | | | 3) FBC-2004 SEC. 424.2.14.1, OR | | | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. (MANUFACTURE | | | SHEETS REQUIRED CLEARLY INDICATING THE MAKE, MODEL | | | NUMBER AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY, PLEASE SUBMIT) | | | | | | 4) FBC-2004 SEC. 424.2.14.2, OR | | | FBCR-2004 SEC. R4101.14.2 WATER | | | RETENTION, PROVIDE A POSITIVE MEANS OF | | | RETAINING WATER IN THE HEATER WHEN PUMP | | | IS SHUT OFF.(MANUFACTURE SHEETS | | | REQUIRED, PLEASE SUBMIT) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-03 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-03 |
Time |
08:43 |
Sent To |
P |
|
| Notes |
| 2008-03-03 08:44:38 | ***APPROVED - RESUB #1*** | | | | | | PROVISO:A FENCE PERMIT SHALL BE PULLED IF ONE DOES | | | NOT EXIST ALREADY. | | | | | | | | | | | | | | | SENT TO "P" - MP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-02-13 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-02-11 |
Time |
14:18 |
Sent To |
E |
|
| Notes |
| 2008-02-13 08:25:31 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. PER SECTION 94-304(D)(2)(B), EVERY SWIMMING POOL | | | SHALL BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH | | | IS INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN | | | THE OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIN WHICH A | | | SWIMMING POOL IS LOCATED.BARRIERS OR FENCES SHALL BE | | | AT LEAST 4 FEET IN HEIGHT ABOVE GRADE.PROVIDE THE | | | LOCATION OF THE FENCE AROUND THE SWIMMING POOL ON BOTH | | | COPIES OF SURVEY.PLEASE NOTE THAT A FENCE PERMIT | | | SHALL BE SUBMITTED PRIOR TO THE APPROVAL OF THIS | | | PERMIT. | | | | | | 2. PER SECTION 94-304(D)(2)(C), ACCESS TO AN ACCESSORY | | | SWIMMING POOL MUST BE THROUGH A BUILDING OR THROUGH A | | | SELF-CLOSING AND SELF-LATCHING GATE OR THROUGH A SCREEN | | | ENCLOSURE DOOR WITH LATCHES PLACED AT LEAST 54 INCHES | | | ABOVE BOTTOM OF GATE.PROVIDE ACCESS/GATE TO SWIMMING | | | POOL ON BOTH COPIES OF SURVEY. | | | | | | 3. PER SECTION 94-305(B)(4), MECHANICAL (POOL) | | | EQUIPMENTS MAY NOT PROJECT MORE THAN FOUR FEET INTO A | | | SETBACK.PROVIDE SETBACK DIMENSIONS TO POOL EQUIPMENT | | | ON BOTH COPIES OF SURVEY. | | | | | | COMMENT/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|