Plan Review Details - Permit 08020050
Plan Review Stops For Permit 08020050
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-20 Cont ID  
Sent By rmcdouga Date 2009-01-20 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2009-01-20 Time 13:41 Sent To  
Notes
2009-01-20 13:43:08REVISION TO INSTALL OVERHEAD GARAGE DOOR IS OK. PRODUCT
 APPROVAL WAS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-12 Cont ID  
Sent By rmcdouga Date 2008-11-12 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2008-11-12 Time 15:58 Sent To  
Notes
2008-11-12 15:59:24REVISION TO REPLACE ONE WINDOW IN KITCHEN IS OK.
 PRODUCT APPROVALS WERE SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-21 Cont ID  
Sent By rmcdouga Date 2008-07-21 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2008-07-21 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-12 Cont ID  
Sent By kconrad Date 2008-02-12 Time 08:39 Rev Time 0.00
Received By kconrad Date 2008-02-12 Time 08:39 Sent To  
Notes
2008-02-12 08:41:24PRE-INSPECT PERFORMED BY #3615. REQUIRE STRUCTURAL
 EXTERIOR WALL FRAMING DETAILS AND EXTERIOR DOOR PRODUCT
 APPROVALS. ALSO A SEPARATE MEP PERMITS SHALL BE
 OBTAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-07 Cont ID  
Sent By rmcdouga Date 2008-02-07 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2008-02-07 Time 14:00 Sent To  
Notes
2008-02-07 14:52:382004 FBC W/2007 REVISIONS
 REPAIR
  
 DENIED BY BUILDING
  
 1) A NOTICE OF COMMENCEMENT WILL BE REQUIRED. THE WORK
 ON THE PROJECT IS REQUIRED TO START WITHIN 90 DAYS OF
 THE RECORDING OF THE NOC OR IT WILL BE VOID.
  
 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION, SIZES AND TYPES ( WOOD, STEEL, GLAZED, ETC.)
 OF DOORS THAT ARE BEING REPLACED. FBC 106.1.1* CITY
 AMENDMENTS
  
 3) THE PRODUCT APPROVAL SUBMITTED FOR THE DOORS
 CONTAINS THREE DIFFERENT NOAS AND TWO OF THEM ARE
 EXPIRED. THE ONE THAT THAT IS NOT EXPIRED IS FOR DOORS
 WITH GLASS IN THEM. PROVIDE TWO COPIES OF CURRENT
 PRODUCT APPROVALS FOR THE DOOR TYPES THAT ARE BEING
 REPLACED. FAC RULE 9B-72.
  
 4) THE EXTENT OF THE REPAIRS FOR THE SCREEN ROOM IS NOT
 INDICATED. THEREFORE, NO COMMENTS AT THIS TIME. A
 PRE-INSPECTION IS RECOMMENDED TO DETERMINE THE EXTENT
 OF THE WORK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-02-05 Cont ID  
Sent By btrobaug Date 2008-02-05 Time 11:03 Rev Time 0.00
Received By btrobaug Date 2008-02-05 Time 10:54 Sent To P
Notes
2008-02-05 11:03:35 
  
  
  
 NO ELECTRICAL PLANS SUBMITTED AND NO ELECTRICAL PERMIT
 APPLIED FOR./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-14 Cont ID  
Sent By adarroug Date 2009-01-14 Time 16:19 Rev Time 0.00
Received By adarroug Date 2009-01-14 Time 16:19 Sent To B
Notes
2009-01-14 16:19:30TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 13:18 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 13:18 Sent To B
Notes
2008-11-07 13:19:14TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-16 Cont ID  
Sent By adarroug Date 2008-07-16 Time 11:56 Rev Time 0.00
Received By adarroug Date 2008-07-16 Time 11:56 Sent To P
Notes
2008-07-16 11:56:54TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-07 Cont ID  
Sent By rmcdouga Date 2008-02-07 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2008-02-04 Time 14:32 Sent To  
Notes
2008-02-04 14:33:10TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-02-06 Cont ID  
Sent By tgordon Date 2008-02-06 Time 13:57 Rev Time 0.15
Received By tgordon Date 2008-02-06 Time 13:57 Sent To B
Notes
2008-02-06 13:58:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-07-17 Cont ID  
Sent By mperson Date 2008-07-17 Time 11:09 Rev Time 0.00
Received By mperson Date 2008-07-17 Time 11:09 Sent To B
Notes
2008-07-17 11:12:23NOTE: PLUMBING HAS A STAND ALONE PERMIT #08030470,
 ISSUED 3/20/08. **MRPERSON**

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By mperson Date 2008-02-06 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2008-02-07 Time 13:59 Sent To M
Notes
2008-02-06 11:52:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. ONLY ONE COPY OF A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM WAS SUBMITTED WITH THE PERMIT
 APPLICATION.PER CITY WPB AMENDMENTS TO CHAPTER 1,
 SECTION *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND STRUCTURAL
 OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS WITH
 EACH APPLICATION FOR A PERMIT.
  
 2. THERE WERE NO FLOOR PLAN DRAWINGS SUBMITTED WITH
 THE PERMIT APPLICATION CLEARLY INDICATING THE BATHROOM,
 KITCHEN, AND LAUNDRY ROOM LAYOUTS. PLEASE PROVIDE THE
 FOLLOWING PER CITY WPB AMENDMENTS TO CHAPTER 1, SECTION
 *106.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM
 CLEARLY INDICATING THE SCOPE OF WORK OF THE PERMIT
 APPLICATION.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 CITY WPB AMENDMENTS TO CHAPTER 1, SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 **THE SUBMITTED PLUMBING SANITARY ISOMETRIC RISER
 DIAGRAM NEEDS SIGNATURES.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  