Plan Review Details - Permit 08020035
Plan Review Stops For Permit 08020035
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-02 Cont ID  
Sent By btrobaug Date 2008-05-02 Time 10:09 Rev Time 0.00
Received By btrobaug Date 2008-04-24 Time 15:24 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-18 Cont ID  
Sent By btrobaug Date 2008-03-18 Time 15:01 Rev Time 0.00
Received By btrobaug Date 2008-03-18 Time 14:43 Sent To PC
Notes
2008-03-18 14:51:18 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE.
  
 THE METER PURPOSED ORIGINALLY WAS SUBFED FROM AN
 EXISTING DISCONNECT, THERE FORE THE SAME SERVICE AS THE
 REST OF THE BUILDING. THIS PLAN SUBMITTED NOW FOR
 REVIEW INDICATES A NEW SERVICE TO THE METER IN
 VIOLATION OF THE ABOVE ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-08 Time 09:12 Rev Time 0.00
Received By btrobaug Date 2008-02-07 Time 14:02 Sent To I
Notes
2008-02-08 09:12:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SUBMIT THE FOLLOWING FOR REVIEW
  
 1} THIS APPLICATION INVOLVES SUB.METERING. IT IS THE
 DETERMINATION OF THIS OFFICE THAT ELECTRICALLY THE
 PLANS COMPLY WITH CODE IF THE LUGS IN THE 400 AMP METER
 ARE CORRECT FOR THE TAP PROPOSED. INDICATE WHICH TAP
 RULE IS BEING INVOLKED (PROVIDE CODE ARTICLE).
  
 2} SUBMIT A NOTORISED LETTER FROM THE OWNER OF THE
 EXISTING SERVICE, GRANTING PERMISSION FOR THE SUB
 METER.INDICATE WHERE THE EXISTING DISCONNECTING MEANS
 FOR THE 400 AMP SERVICE IS LOCATED, BOTH ON THE RISER
 AND ON A SITE PLAN, ALSO LOCATING THE PROPOSED
 EQUIPMENT ON THE SITE PLAN THAT COMPLIANCE WITH
 230.72(A)MAY BE REVIEWED.
  
 3} FOR RECORD RETENTION, THE ADDRESS OF THE JOB MUST BE
 ON THE PLANS. 106.1.3 FBC AS AMENDED.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 09:12 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 09:12 Sent To E
Notes
2008-03-17 09:13:07TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-08 Time 09:13 Rev Time 0.00
Received By btrobaug Date 2008-02-04 Time 08:44 Sent To PC
Notes
2008-02-04 08:44:33TO "E" BOX