Plan Review Details - Permit 08020032
Plan Review Stops For Permit 08020032
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-29 Cont ID  
Sent By jgomez Date 2008-02-29 Time 14:27 Rev Time 0.00
Received By jgomez Date 2008-02-29 Time 13:45 Sent To PC
Notes
2008-02-29 14:34:19BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL FOR GARAGE DOORS THAT MEETS
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT.
 ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL AS REQUIRED BYSEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 2- REVISE ENERGY CALCULATIONS.THEY ARE NO DONEAS
 WORST CASE SCENARIO, THEREFOREHOUSE ORIENTATION NEEDS
 TO MATCH ACTUAL HOUSE ORIENTATION. SEE SURVEY AND
 REVISE INFORMATION ON SHEET 2 AS REQUIRED.
 ALSO, REVISE OVERHANG HEIGHT AND LENGHTTO MATCH
 ACTUAL OVERHANG HEIGHT AND LENGHTSHOWN ON PLANS AND
 ELEVATIONS.
  
 3- ENGINEER WHO PREPARED THE SOIL TEST REPORT NEEDS TO
 PROVIDE HIS LICENSE NUMBER AND DATE WHEN IT WAS SEALED
 AS REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE AND SEC. 471 FLORIDA STATUTE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-08 Cont ID  
Sent By jgomez Date 2008-02-08 Time 16:52 Rev Time 0.00
Received By jgomez Date 2008-02-08 Time 16:52 Sent To PC
Notes
2008-02-08 16:58:51NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE. MAY BE DONE AT TIME OF PERMIT PICK
 UP.
  
 2- PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT. MAY BE DONE AT TIME OF PERMIT PICK
 UP.
  
 3- DESIGN PARAMETERS.WIND EXPOSURE CLASSIFICATION
 NEED TO BE CHANGED FROM "B" TO "C" AS REQUIRED BY SEC.
 R301.2.1.4(3)OF 2004 FLORIDA RESIDENTIALCODE.MORE
 THAN 600 FEET OF OPEN LAND ON ONE QUADRANT MAKES IT AN
 EXPOSURE "C".
 ALSO, NEED TO REVISE ALL THE DESIGN PRESSURES AS
 REQUIRED.
  
 NOTE: THIS NEEDS TO BE REVISED ONLOT 26 TOO.
  
 4-A) SOIL TEST REPORT NEEDS TO HAVE THE FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 B) SOIL TEST REPORT NEEDS TO REFER TO FBC 2004, NOT
 2001. REVISE AS REQUIRED.
  
 5- ENERGY CALCULATIONS:
 A) REVISE NAME OF BUILDER.
  
 B) REVISE UNDER ATTIC AREA AS REQUIRED BY SEC.
 13-604.1.A.1 FBC 2004.
  
 C) REVISE OVERHANG LENGTH AND HEIGHT TO MATCH ACTUAL
 FLOOR PLANS. AND ELEVATIONS.
  
 D) REVISE BUILDING ORIENTATION TO MATCH ACTUAL
 BUILDING ORIENTATION AND SHOW ALL OPENINGS. THERE ARE
 SOME OPENINGS THAT ARE MISSING.EG: THERE ARE NOT
 OPENINGS SHOWN FOR NORTH WALLS.SEE SURVEY FOR CORRECT
 BUILDING ORIENTATION AND REVISE AS REQUIRED.
  
 6- ARCHITECT TO DATE DRAWINGS AS REQUIRED BY SEC.
 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE.1/2008 IS
 NOT A COMPLETE DATE.
  
 7- NEED TO PROVIDE ONE BATHROOMWITH DOOR THAT ALLOWS
 MIN. 29" CLEAR OPENING. SEC. 11-11.1 FBC 2004.
  
 8-A) SPECIFY AREA OF PORCH ADJACENT TO THE LIVING
 ROOM TO PROPERLY ADJUST THE VALUATION AND RADON FEES.
  
 B) RECALCULATE ALL AREA ON SHEET A4 AND REVISE AS
 REQUIRED TO MATCH ACTUAL AREAS. EG: LANAI AREA IS
 INCORRECT.
  
 9- PROVIDE COMPLETE DETAILS/SECTIONS AND SPECIFICATIONS
 FOR CONSTRUCTION OF ROOF CUPOLAS TO VERIFY COMPLIANCE
 WITH SEC. R301.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 10- PROVIDE MANUFACTURER SPECIFICATIONS AND DETAILS FOR
 CONSTRUCTION OF ROOF COVER OVER CHIMNEY.CHIMNEY CAPS
 MAY INTERFERE WITH PROPER FIREPLACE FUNCTION AND MAY
 AFFECT MANUFACTURER WARRANTIES.
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING(NOT SIGNING AND SEALING) BY THE
 ARCHITECTAS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 12- PROVIDE PRODUCT APPROVALAS REQUIRED BY DCA RULE
 9B-72FOR WINDOW AND DOORS MULLIONS. AND, CLEARLY
 SPECIFY SIZE AND FASTENING TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES.
  
 13- SHEET A3:
 A) PROVIDE COMPLETE DETAILS/SPECS FORSCREEN
 ENCLOSURE AS REQUIRED BY SEC. R301.1 2004 FLORIDA
 RESIDENTIAL CODE.
  
 B) PROVIDE COMPLETE SPECS FOR TYPE OF COLUMNS AT THE
 ENDS OF LIVING ROOM WINDOWS,FAMILY ROOM BY THE FRENCH
 DOORSAND BY THE ENTRY PORCH. THERE ARE NO SPECS ON
 THE COLUMN LEGEND.
  
 C) PROVIDE COMPLETE DETAIL/SPECS FOR STEEL COLUMNS
 BETWEEN LIVING ROOM WINDOWS. NEED TO SPECIFY TOP AND
 BOTTOM CONNECTIONS. TO VERIFY COMPLIANCE WITH SEC.
 R301.1.
  
 D) PROVIDE COMPLETE DETAILS/SPECS FOR INSTALLATION
 OF STRUCTURALBUCKS IN STEEL COLUMNS AND ATTACHMENT OF
 WINDOWSIN LIVING ROOM AREA TO VERIFY COMPLIANCE WITH
 SEC. R301.1.
  
 14- SHEET A4:
 A) DOOR AND WINDOW BUCK DETAILS NEED TO BE
 COORDINATEDWITH DETAILS SHOWN ON SHEET A7. ALSO,
 PROVIDE DETAILS THAT COMPLY WITH SEC. R613.6.BUCK
 NEEDSTO PROVIDE FULL SUPPORT TO DOOR AND WINDOW.
  
 B) REVISE SIZE OF FIXED WINDOW IN MASTER BEDROOM.
 6060 FIXED WINDOW WAS DIVIDED INTO TWO TO SATISFY
 PRODUCT APPROVAL SIZE.
  
 15- SHEET A5: THERE ARE MANYTRUSSES THAT ARE MISSING
 THE CONNECTORS.SPECIFY CONNECTORS FOR ALL TRUSSES TO
 VERIFY COMPLIANCE WITH CALCULATED UPLIFT LOADS OF SEC.
 R301.1
 ALSO, THERE ARE SOME CONNECTORS THAT NEED TO BE
 COORDINATED FOR PROPER INSTALLATION. EG: CHECK
 CONNECTORS SPECIFIED ON GIRDER TRUSS ABOVE FAMILY ROOM
 AREA.REVIEWAND COORDINATE ALL SPECIFIED CONNECTORS
 TO MATCH PROPOSED INSTALLATION.
  
 16- SHEET A7:TYPICAL WALL SECTION:A) REVISE TILE
 INSTALLATION.20.0 UPLIFT RESISTANCE IS NOT ADEQUATE.
 SEE PRODUCT APPROVAL.
  
 B) INFORMATION FOR FOOTING DIMENSIONS ABOVE AND
 BELOW GRADEIS OVERLAPPING. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-24 Cont ID  
Sent By btrobaug Date 2008-09-24 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2008-09-24 Time 16:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-05 Cont ID  
Sent By btrobaug Date 2008-09-05 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2008-09-05 Time 14:26 Sent To PC
Notes
2008-09-05 15:06:30 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REVISION DENIED
 SAMRE COMMENT AS THE PREVIOUS REVISION:
  
 1} THE LOCATION OF THE SERVICE IS IN VIOLATION OF
 110.26.**SEE LOCATION BEHIND THE CONDENSER UNITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-22 Cont ID  
Sent By btrobaug Date 2008-08-22 Time 11:13 Rev Time 0.00
Received By btrobaug Date 2008-08-22 Time 11:05 Sent To PC
Notes
2008-08-22 11:13:46 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REVISION DENIED
  
 1} THE LOCATION OF THE SERVICE IS IN VIOLATION OF
 110.26.
  
 2} THERE IS NO INDICATION OF THE SCOPE OF THIS
 REVISION. INDICATE BY CLOUDS AND DELTA'S OR ANOTHER
 METHOD DEEMED ACCEPTABLE BY THE PROFESSION, THE CHANGES
 TO BE REVIEWED FOR THIS REVISION. 106.1.3FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By btrobaug Date 2008-02-25 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 16:01 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By dpalmer Date 2008-02-04 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2008-02-04 Time 12:53 Sent To M
Notes
2008-02-04 12:54:06** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON ELECTRICAL PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE PLANS ARE CALLING FOR SD AND LEGEND
 INDICATES SMOKE DETECTORS. PLEASE SEE NFPA-72
 DEFINITIONS AS SMOKE DETECTORS ARE ONLY DEVICES WHICH
 DETECT AND DO NOT SOUND AN ALARM.IF THESE ARE INDEED
 SMOKE DETECTORS, PLEASE SHOW THE FIRE ALARM PANEL,
 HORN/SOUNDING DEVICES ALONG WITH HORN LOCATIONS.
 IF THESE ARE INDEED SMOKE ALARMS WHICH DETECT AND SOUND
 AND ALARM, PLEASE ADJUST DESIGNATIONS AND SYMBOL
 LEGEND.
 PLEASE SEE 11.5.1.1, 11.8.3 AND FBC R313.
  
 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 THE PANELS ARE BOTH SHOWN AS MCB, (MAIN CIRCUIT
 BREAKERS) YET THE RISER SHOWS BOTH OF THESE AS MLO
 (MAIN LUG ONLY).
 FBC 106.1.2 ADMIN SECTION FOR COORDINATION.
 230, 215, 240, ETC
  
 4) NOTE: PLEASE SEE 2005 NEC FOR REQUIRED GFI
 PROTECTION OF ALL 15/20AMP RECEPTACLES/CIRCUITS LOCATED
 WITHIN 6FT OF LAUNDRY ROOM SINKS.
 PLEASE KNOW EVEN DEDICATED WASHER, DRYER RECEPTACLES
 ARE REQUIRED TO BE GFI PROTECTED. ** NOTE** AS THESE
 ARE REQUIRED TO BE SINGLE POINT OF USE, PLEASE BE SURE
 TO LIST BREAKER IN PANEL AS WELL.
 210.8A7** THIS WAS A CHANGE IN THE 2005 NEC.
  
 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS
 DINING ROOM, BREAKFAST AREA, BAR AREA AND AREAS OF THE
 LIKE REQUIRES RECEPTACLES TO BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. THIS WOULD MEANS *DINING ROOM
 RECETPS* 20A, #12, 1500 VA IN ADDITION TO THE TWO
 MINIMUM SMALL APPLIANCE CIRCUITS FOR SEPARATE OR
 ADDITIONAL CIRCUITS.
  
 6) NOTE: PLEASE BE SURE TO INCLUDE DESIGNATION FOR
 REQUIRED RECESSED LIGHTS PER 13-606.1.ABC.1.2.4
  
 7) NOTE: PLEASE INCLUDE LOADS FOR RECESSED LIGHTING PER
 220.14D.
 PLEASE SEE THE PLANS SHOW MORE THAN 60 RECESSED LIGHT
 FIXTURES. THESE ARE SHOWN ABOVE NORMAL GENERAL
 LIGHTING.
  
 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING
 REQUIRED.
 PLEASE SEE BEDROOM #4 FOR EXAMPLE AS THE SPACING WITHIN
 6FT OF DOORWAYS IN THREE LOCATIONS DO NOT MEET CODE.
  
 9) NOTE: PLEASE SEE MISSING THE MINIMUM CONDUCTOR SIZE
 FOR BATH GFI PER 210.11C3
 MUST BE #12 MINIMUM.
  
 10) NOTE: PLEASE SEE THERE ARE SEVERAL CONDUCTOR SIZES
 ON PANELS FOR BRANCH CIRCUITS WHICH NEED TO BE
 COMPLETED, CORRECTED AND COORDINATED. SOME EXAMPLES:
 PLEASE SEE THERE ARE BRANCH CIRCUIT CONDUCTORS MISSING
 AS NOTED FOR BATH ABOVE ALONG WITH COOK-TOP ETC.
 PLEASE SEE THERE ARE 20AMP BREAKERS ON #14AWG WHICH
 EXCEEDS THE RATING OF THE CONDUCTOR, SEE JACUZZI.
 PLEASE SEE THERE ARE NUMEROUS CIRCUITS WHERE THE
 CONDUCTORS ARE SHOWN EXCEEDING THE CIRCUIT SIZE. LARGER
 CONDUCTORS ARE NOT IN VIOLATION HOWEVER PLEASE SEE
 CIRCUITS SUCH AS WET BAR GFI WHICH SHOWS #6 FOR
 CIRCUIT. PLEASE SEE MICROWAVE WITH #8, REFRIGERATOR,
 SMALL APPLIANCES, GARAGE DOOR OPENERS ETC ALL WITH
 #10.
 PLEASE KNOW SOME OF THESE DEVICES AND BREAKERS ARE
 RATED TO THE #10, HOWEVER #6 WILL NOT WORK IN A GFI.
 THIS WOULD CREATE LISTING ISSUES WITH SEVERAL ITEMS.
 PLEASE COORDINATE ALL BRANCH CIRCUITS, PANEL SCHEDULES
 AND BREAKERS.
 240.4, 408.4, 310.16, 110.3, ETC
 FBC106.1.2, 106.3.5.4 ADMIN SECTION. COORDINATION.
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE *B* LOAD
 CALCULATIONS AS THE AIR HANDLER HEAT LOAD IS SHOWN AT
 100 % WHICH IS NOTED AS 8.8 KW. HOW IS THIS POSSIBLE
 WHEN THE LOAD ON THE PANEL SCHEDULE ALSO INDICATES THIS
 AS 10KW?
 PLEASE COORDINATED.
 240.4, 310.16, 220, 408.4
 FBC 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 11:20 Sent To Z
Notes
2008-09-26 11:21:06TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 09:00 Sent To E
Notes
2008-09-05 09:00:38TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-13 Cont ID  
Sent By adarroug Date 2008-08-13 Time 15:45 Rev Time 0.00
Received By adarroug Date 2008-08-13 Time 15:45 Sent To E
Notes
2008-08-13 15:46:21TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 09:12 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 09:12 Sent To Z
Notes
2008-02-21 09:12:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-08 Cont ID  
Sent By jgomez Date 2008-02-08 Time 16:58 Rev Time 0.00
Received By jgomez Date 2008-02-01 Time 16:44 Sent To  
Notes
2008-02-01 16:45:26TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By rkussner Date 2008-10-02 Time 08:45 Rev Time 0.00
Received By rkussner Date 2008-10-02 Time 08:45 Sent To  
Notes
2008-10-02 08:58:10***LANDSCAPE REVIEW FAILED***
  
 1. PROVIDE THE REQUIRED LANDSCAPE CALCULATIONS BASED
 UPON ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, SUCH AS TREES REQUIRED AND PROVIDED AND
 SHRUBS REQUIRED AND PROVIDED. PLEASE NOTE THAT IN ORDER
 TO COUNT TREES IN THE CALCULATIONS, THEY MUST BE AT
 MINIMUM OF 8 FEET IN HEIGHT.
  
 2. PROVIDE THE SIZE AND SPACING OF ALL PROPOSED PLANT
 MATERIAL--NOT JUST CONTAINER SIZE.
  
 3. IDENTIFY THE STREET AND SHOW THE RIGHT-OF-WAY ON THE
 LANDSCAPE PLAN. SHOW ANY EXISITING OR PROPOSED STREET
 TREES.
  
 4. PROVIDE THE LOCATION OF ANY TREES ON NEIGHBORING
 PROPERTIES THAT MAY GROW OVER THE PROPERTY LINE AND
 CREATE A CONFLICT WITH PROPOSED LANDSCAPING ON THIS
 SITEL.
  
 5. SHOW ALL PROPOSED UTILITIES, EASEMENTS AND ANYTHING
 ELSE THAT MAY INTERFERE WITH THE PROPOSED LANDSCAPING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By btrobaug Date 2008-02-26 Time 08:54 Rev Time 0.40
Received By tgordon Date 2008-02-22 Time 11:25 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 16:06 Rev Time 1.00
Received By tgordon Date 2008-02-04 Time 16:06 Sent To P
Notes
2008-02-04 16:20:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 2) PLEASE ADD THE JOB ADDRESS TO THE MECHANICAL PLAN,
 SEE 2004 WPB AMEND. 106.1.3.
  
 3) MODEL NUMBERS FOR A/C SYSTEMS 1 & 3 ON THE
 MECHANICAL PLAN COULD NOT BE FOUND ON THE ARI DIRECTORY
 WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 4) IF THE CORRECT MODEL NUMBER FOR CONDENSER UNIT #1 IS
 4TTR4030A THEN THE SYSTEM IS 13.75 SEER NOT 14 SEER
 (SEE ATTACHED ARI CERTIFICATE) IF SO PLEASE CORRECT
 MECHANICAL PLAN AND ENERGY CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 10:53 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 10:53 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-05 Cont ID  
Sent By jleech Date 2008-02-05 Time 08:49 Rev Time 0.00
Received By jleech Date 2008-02-05 Time 08:49 Sent To B
Notes
2008-02-05 08:54:25DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN;
 1) BATH 3 IS BACK TO BACK WITH CABANA BATH NOT
 BATH 2.
 2) ONLY ONE W/C ON FLOOR PLAN 2 ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-21 Cont ID  
Sent By choops Date 2008-02-21 Time 15:05 Rev Time 0.00
Received By choops Date 2008-02-21 Time 15:05 Sent To M
Notes
2008-02-21 15:06:00***APPROVED - RESUB #1***
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 10:02 Rev Time 0.00
Received By choops Date 2008-02-04 Time 10:02 Sent To E
Notes
2008-02-04 10:05:58***FAILED***
  
  
 1)THE PROVIDED LANDSCAPE PLAN SHALL INDICATE BOTH
 KIND AND SIZE OF PROPOSED LANDSCAPING.
  
 2)ELEVATIONS (SHEET A-1) SHALL SHOW HEIGHT
 DIMENSIONS FROM GRADE TO THE MIDPOINT OF THE ROOF'S
 PITCH.IT SHALL ALSO INDICATE THE HEIGHT DIMENSION
 FROM GRADE TO THE UPPERMOST POINT OF THE ACCESSORY
 TOWER.NOTE:TOWER MAY NOT EXCEED 33' IN HEIGHT,
 MEASURED FROM GRADE (30' ALLOWABLE + 10% FOR THE
 ACCESSORY).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - SF RACK