| 2008-02-04 12:54:06 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE STATED ON ELECTRICAL PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE CALLING FOR SD AND LEGEND |
| | INDICATES SMOKE DETECTORS. PLEASE SEE NFPA-72 |
| | DEFINITIONS AS SMOKE DETECTORS ARE ONLY DEVICES WHICH |
| | DETECT AND DO NOT SOUND AN ALARM.IF THESE ARE INDEED |
| | SMOKE DETECTORS, PLEASE SHOW THE FIRE ALARM PANEL, |
| | HORN/SOUNDING DEVICES ALONG WITH HORN LOCATIONS. |
| | IF THESE ARE INDEED SMOKE ALARMS WHICH DETECT AND SOUND |
| | AND ALARM, PLEASE ADJUST DESIGNATIONS AND SYMBOL |
| | LEGEND. |
| | PLEASE SEE 11.5.1.1, 11.8.3 AND FBC R313. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE |
| | THE PANELS ARE BOTH SHOWN AS MCB, (MAIN CIRCUIT |
| | BREAKERS) YET THE RISER SHOWS BOTH OF THESE AS MLO |
| | (MAIN LUG ONLY). |
| | FBC 106.1.2 ADMIN SECTION FOR COORDINATION. |
| | 230, 215, 240, ETC |
| | |
| | 4) NOTE: PLEASE SEE 2005 NEC FOR REQUIRED GFI |
| | PROTECTION OF ALL 15/20AMP RECEPTACLES/CIRCUITS LOCATED |
| | WITHIN 6FT OF LAUNDRY ROOM SINKS. |
| | PLEASE KNOW EVEN DEDICATED WASHER, DRYER RECEPTACLES |
| | ARE REQUIRED TO BE GFI PROTECTED. ** NOTE** AS THESE |
| | ARE REQUIRED TO BE SINGLE POINT OF USE, PLEASE BE SURE |
| | TO LIST BREAKER IN PANEL AS WELL. |
| | 210.8A7** THIS WAS A CHANGE IN THE 2005 NEC. |
| | |
| | 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS |
| | DINING ROOM, BREAKFAST AREA, BAR AREA AND AREAS OF THE |
| | LIKE REQUIRES RECEPTACLES TO BE ON ONE OR MORE OF THE |
| | SMALL APPLIANCE CIRCUITS. THIS WOULD MEANS *DINING ROOM |
| | RECETPS* 20A, #12, 1500 VA IN ADDITION TO THE TWO |
| | MINIMUM SMALL APPLIANCE CIRCUITS FOR SEPARATE OR |
| | ADDITIONAL CIRCUITS. |
| | |
| | 6) NOTE: PLEASE BE SURE TO INCLUDE DESIGNATION FOR |
| | REQUIRED RECESSED LIGHTS PER 13-606.1.ABC.1.2.4 |
| | |
| | 7) NOTE: PLEASE INCLUDE LOADS FOR RECESSED LIGHTING PER |
| | 220.14D. |
| | PLEASE SEE THE PLANS SHOW MORE THAN 60 RECESSED LIGHT |
| | FIXTURES. THESE ARE SHOWN ABOVE NORMAL GENERAL |
| | LIGHTING. |
| | |
| | 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING |
| | REQUIRED. |
| | PLEASE SEE BEDROOM #4 FOR EXAMPLE AS THE SPACING WITHIN |
| | 6FT OF DOORWAYS IN THREE LOCATIONS DO NOT MEET CODE. |
| | |
| | 9) NOTE: PLEASE SEE MISSING THE MINIMUM CONDUCTOR SIZE |
| | FOR BATH GFI PER 210.11C3 |
| | MUST BE #12 MINIMUM. |
| | |
| | 10) NOTE: PLEASE SEE THERE ARE SEVERAL CONDUCTOR SIZES |
| | ON PANELS FOR BRANCH CIRCUITS WHICH NEED TO BE |
| | COMPLETED, CORRECTED AND COORDINATED. SOME EXAMPLES: |
| | PLEASE SEE THERE ARE BRANCH CIRCUIT CONDUCTORS MISSING |
| | AS NOTED FOR BATH ABOVE ALONG WITH COOK-TOP ETC. |
| | PLEASE SEE THERE ARE 20AMP BREAKERS ON #14AWG WHICH |
| | EXCEEDS THE RATING OF THE CONDUCTOR, SEE JACUZZI. |
| | PLEASE SEE THERE ARE NUMEROUS CIRCUITS WHERE THE |
| | CONDUCTORS ARE SHOWN EXCEEDING THE CIRCUIT SIZE. LARGER |
| | CONDUCTORS ARE NOT IN VIOLATION HOWEVER PLEASE SEE |
| | CIRCUITS SUCH AS WET BAR GFI WHICH SHOWS #6 FOR |
| | CIRCUIT. PLEASE SEE MICROWAVE WITH #8, REFRIGERATOR, |
| | SMALL APPLIANCES, GARAGE DOOR OPENERS ETC ALL WITH |
| | #10. |
| | PLEASE KNOW SOME OF THESE DEVICES AND BREAKERS ARE |
| | RATED TO THE #10, HOWEVER #6 WILL NOT WORK IN A GFI. |
| | THIS WOULD CREATE LISTING ISSUES WITH SEVERAL ITEMS. |
| | PLEASE COORDINATE ALL BRANCH CIRCUITS, PANEL SCHEDULES |
| | AND BREAKERS. |
| | 240.4, 408.4, 310.16, 110.3, ETC |
| | FBC106.1.2, 106.3.5.4 ADMIN SECTION. COORDINATION. |
| | |
| | 11) NOTE: PLEASE SEE PANEL SCHEDULE *B* LOAD |
| | CALCULATIONS AS THE AIR HANDLER HEAT LOAD IS SHOWN AT |
| | 100 % WHICH IS NOTED AS 8.8 KW. HOW IS THIS POSSIBLE |
| | WHEN THE LOAD ON THE PANEL SCHEDULE ALSO INDICATES THIS |
| | AS 10KW? |
| | PLEASE COORDINATED. |
| | 240.4, 310.16, 220, 408.4 |
| | FBC 106.1.2 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |