| 2008-02-04 15:00:29 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PER 230.2 NUMBER OF SERVICES: |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE.PLEASE INDICATE UNDER WHICH EXCEPTION THE |
| | SECOND SERVICE WOULD MEET. |
| | |
| | 2}PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED IF |
| | THE SERVICE IS ALLOWED. WE ARE SPECIFICALLY CONCERNED |
| | WITH GROUPING ISSUES PER 230.72. |
| | |
| | 3} PER 110.9 AND 110.10 PROVIDE THE AIC CALCULATION AND |
| | THE RATING OF THE EQUIPMENT TO BE INSTALLED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |