| Plan Review Stops For Permit 08010746 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-02-21 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-02-21 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-02-01 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-02-01 |
Time |
13:20 |
Sent To |
PC |
|
| Notes |
| 2008-02-01 13:30:31 | COMMERCIAL ROOFING PERMIT, BUILDING REVIEWFIRST | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PERMIT APPLICATION STATES NON INSULATED ROOF DECK, | | | BUT SELECTEDROOFASSEMBLYON PAGES 38 & 39 OF NOA | | | 03-0430.13 SUBMITTEDIS FOR INSULATEDROOF ASSEMBLY. | | | CLARIFY IF SELECTED ASSEMBLY IS INSULATEDOR | | | NON-INSULATED AND PROVIDE MATCHING INFORMATION. | | | ALSO, CLEARLY MARK WHICH SPECIFICINSULATION ASSEMBLY | | | IS GOING TO BE USED TO VERIFY COMPLIANCE WITH THE | | | UPLIFT DESIGN PRESSURES OF SEC. 1609 FBC 2004. | | | | | | 2-PERMIT VALUATION WAS UPDATED TO $119,500 AS | | | REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | OWES $95.95. | | | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
|