Plan Review Details - Permit 08010692
Plan Review Stops For Permit 08010692
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-04-29 Cont ID  
Sent By mperson Date 2008-04-29 Time 14:01 Rev Time 0.00
Received By mperson Date 2008-04-29 Time 14:01 Sent To PC
Notes
2008-04-29 14:03:48REVISION #01: "OK" DELETE ONE FUTURE FIRE PLACE, TWO
 DRYERS & MOVED TANKLESS WATER HEATER.
  
 ****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-01-31 Cont ID  
Sent By mperson Date 2008-01-31 Time 10:29 Rev Time 0.00
Received By mperson Date 2008-01-31 Time 10:29 Sent To PC
Notes
2008-01-31 10:35:19****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 16:20 Sent To G
Notes
2008-04-28 16:20:37TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By mperson Date 2008-01-31 Time 10:35 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 15:45 Sent To  
Notes
2008-01-29 15:45:16TO "G" BOX