Plan Review Details - Permit 08010681
Plan Review Stops For Permit 08010681
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-05 Cont ID  
Sent By rmcdouga Date 2008-02-05 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2008-02-05 Time 06:58 Sent To P
Notes
2008-02-05 10:21:442004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE TWO 2X8 GIRDERS SUPPORTING THE FLOOR, ROOF AND
 CEILING LOADS APPEAR TO EXCEED THE ALLOWABLE SPANS IN
 TABLE R502.2.4(1). PROVIDE CALCULATIONS.FBC 106.1.2*
 CITY AMENDMENTS
  
 4)THE FOUNDATION SPECIFIED DOES NOT APPEAR TO BE
 ADEQUATE TO RESIST UPLIFT AND OVER TURNING. SHOW
 COMPLIANCE WITH FBC R 401.2 AND R 403.1.1. PROVIDE
 CALCULATIONS.
  
 5) SPECIFY THE TYPE OF WINDOW (IE SINGLE HUNG, ETC.)
 THAT WILL BE INSTALLED IN THE BATHROOM. FBC 106.1.1*
 CITY AMENDMENTS
  
 6) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION AS
 REQUIRED BY FBC 13-600.
  
 7) SPECIFY THE WIND EXPOSURE CATEGORY, INTERNAL
 PRESSURE COEFFICIENT AND IMPORTANCE FACTOR ON THE
 PLANS. SEE R 301.2.1.4 AND ASCE7-02.
  
 8)SHOW COMPLIANCE WITH FBC R320.1
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION
 (SEE SECTION 202 , REGISTERED TERMITICIDE).
  
 9) SHOW COMPLIANCE WITH R319.1 LOCATION REQUIRED. IN
 AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE
 R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS.
 1.WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL
 FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD
 GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE
 EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA
 LOCATED WITHIN THE PERIPHERY OF THE BUILDING
 FOUNDATION.
  
 10) SHOW COMPLIANCE WITH R408.1 VENTILATION.
 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF
 UNDER-FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING
 SHALL BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING. THIS WILL NOT APPLY IF THERE IS NO FOUNDATION
 CURTAIN WALL, AS THE PLANS APPEAR TO INDICATE. PLEASE
 CLARIFY.
  
 11) THE WALL SECTION ON SHEET 2 SPECIFIES 2 X 6 RAFTERS
 AND THE NOTE ON THE ROOF FRAMING PLAN SPECIFIES 2 X 4
 ROOF FRAMING. PLEASE CLARIFY. FBC 106.1.1* CITY
 AMENDMENTS
  
 12) THE TYPICAL WINDOW AND DOOR DETAIL ON SHEET 2 IS
 FOR MASONRY AND STUCCO CONSTRUCTION. THIS PROJECT IS
 WOOD FRAME. PLEASE CORRECT. FBC 106.1.1* CITY
 AMENDMENTS
  
 13) PROVIDE A DETAIL OF THE LOAD BEARING SUPPORTING
 STRUCTURE WHERE THE CORNER OF THE EXISTING STRUCTURE'S
 WALL HAS BEEN REMOVED TO PROVIDE OPENINGS INTO THE
 ADDITION. FBC 106.1.2* CITY AMENDMENTS
  
 14) PROVIDE A DETAIL OF FRAMING AND CONNECTORS AT THE
 WINDOW OPENING. FBC 106.1.2* CITY AMENDMENTS
  
 15)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF FLORIDA OR MIAMI-DADE PRODUCT
 APPROVALS AS REQUIRED BY RULE 9B-72 FOR: WINDOW, METAL
 ROOFING, AND STORM PANELS.
  
 16)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 17)THE NOTES ON SHEET 1 SPECIFY THE 2004 CODES WITH
 2006 AMENDMENTS. THE CODE EDITION FOR THIS PROJECT IS
 THE 2004 FBC WITH 2007 REVISIONS. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-01-31 Cont ID  
Sent By btrobaug Date 2008-01-31 Time 07:19 Rev Time 0.00
Received By btrobaug Date 2008-01-31 Time 07:19 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 16:53 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 15:57 Sent To  
Notes
2008-01-29 16:01:47TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By tgordon Date 2008-01-31 Time 10:34 Rev Time 0.15
Received By tgordon Date 2008-01-31 Time 10:34 Sent To P
Notes
2008-01-31 10:34:59NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 16:44 Rev Time 0.00
Received By mperson Date 2008-02-05 Time 16:43 Sent To PC
Notes
2008-02-05 16:53:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2 NEW BATH SANITARY ISOMETRICPLUMBING RISER
 DIAGRAM: AT A MINIMUM THE SANITARY ISOMETRIC RISER
 DIAGRAM MUST REFLECT THE FLOOR PLAN. THE SUBMITTED NEW
 BATH PLUMBING RISER IS NOT AN ISOMETRIC AND DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE REFERENCE THE SANITARY
 ISOMETRIC PLUMBING RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN ATTACHED TO THESE PLUMBING COMMENTS. PER FBC
 PLUMBING SECTION *701.1 SCOPEAND SECTION *901.1
 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-01-30 Cont ID  
Sent By choops Date 2008-01-30 Time 09:27 Rev Time 0.00
Received By choops Date 2008-01-30 Time 09:27 Sent To E
Notes
2008-01-30 09:28:02***APPROVED***
  
  
  
  
 SENT TO "E" - SF RACK