Plan Review Details - Permit 08010656
Plan Review Stops For Permit 08010656
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-06-15 Cont ID  
Sent By jwitmer Date 2009-06-15 Time 11:31 Rev Time 0.77
Received By jwitmer Date 2009-06-15 Time 11:31 Sent To PC
Notes
2009-06-15 11:32:43REVISION: REVISED C-4, C-6 AND ADDED C-11 TO SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2009-04-09 Cont ID  
Sent By jwitmer Date 2009-04-09 Time 09:28 Rev Time 0.77
Received By jwitmer Date 2009-04-09 Time 09:28 Sent To  
Notes
2009-04-09 09:30:41REVISION SUBMITTED (APRIL 1/09) SUBMITTED UNDER
 08010656 (FOUNDATION) SHOULD HAVE BEEN BROUGHT IN UNDER
 08050454 (SITE). TRANSFERRED OVER TO SITE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-31 Cont ID  
Sent By jwitmer Date 2009-03-31 Time 09:39 Rev Time 1.33
Received By jwitmer Date 2009-03-31 Time 09:39 Sent To  
Notes
2009-03-31 09:44:41REVISION # 1 DATED 03/24/09 S-1/S-8

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-21 Cont ID  
Sent By jwitmer Date 2008-07-21 Time 10:23 Rev Time 2.22
Received By jwitmer Date 2008-07-21 Time 10:23 Sent To  
Notes
2008-07-21 10:25:00BUILDING PLAN REVIEW
 PERMIT: 08010656
 ADD: 3415 S DIXIE HWY
 CONT: R & D CONSTRUCTION, INC.
 TEL: (561)889-1751
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: REVIEWED
  
 .
  
 1) BUILDING PROVISO 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2) BUILDING PROVISO 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 3) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT.
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 09:12 Rev Time 2.22
Received By jwitmer Date 2008-04-21 Time 09:12 Sent To  
Notes
2008-04-21 09:18:23BUILDING PLAN REVIEW
 PERMIT: 08010656
 ADD: 3415 S DIXIE HWY
 CONT: R & D CONSTRUCTION, INC.
 TEL: (561)889-1751
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B, INFORMATIONAL PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SECOND REQUEST, 2 REPORTS WERE SUBMITTED BUT THE
 RAISED SEAL WERE COPIES OF SIGNATURES NOT ORIGINAL.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G15-23.002 ENGINEERS
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) COMPLIED.
  
 4) BUILDING PROVISO 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUILDING PROVISO 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 6-9) COMPLIED.
  
 10) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION
 PERMIT.WHEN APPLICATION FOR A PERMIT TO ERECT OR
 ENLARGE A BUILDING HAS BEEN FILED, & PENDING ISSUANCE
 OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By jwitmer Date 2008-02-12 Time 20:45 Rev Time 1.55
Received By jwitmer Date 2008-02-12 Time 20:45 Sent To  
Notes
2008-02-12 21:27:15BUILDING PLAN REVIEW
 PERMIT: 08010656
 ADD: 3415 S DIXIE HWY
 CONT: R & D CONSTRUCTION, INC.
 TEL: (561)889-1751
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 6) SITE PLAN INDICATES A HANDICAPPED PARKING SPACE BUT
 NOT A ACCESSIBLE ACCESS AISLE
 5?-0? WIDE. SEE 11-4.6.3.
  
 7)THE PERMIT APPLICATION INDICATES THIS IS TO BE FOR
 FOUNDATION ONLY, WOULD THE PERMIT ALSO NEED TO INCLUDE
 STEM WALL ABOVE THE SLAB FOR BACKFILL AND GRADING
 PURPOSES?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) STATE RADON FEES ARE GOING TO NEED TO BE PAID IN THE
 AMOUNT OF $199.80 AT THE CITY?S CASHIER DESK BEFORE
 PERMIT ISSUANCE.
  
 10) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION
 PERMIT.WHEN APPLICATION FOR A PERMIT TO ERECT OR
 ENLARGE A BUILDING HAS BEEN FILED, & PENDING ISSUANCE
 OF SUCH PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTE: 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT
 SECTIONS OF THIS CODE SPECIFY DIFFERENT MATERIALS,
 METHODS OF CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-24 Cont ID  
Sent By btrobaug Date 2008-07-24 Time 16:27 Rev Time 0.00
Received By btrobaug Date 2008-07-24 Time 15:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2008-04-07 Time 14:47 Sent To  
Notes
2008-04-07 14:47:51** DENIED 2ND REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS/DETAIL FOR THE
 REQUESTED FOUNDATION PERMIT SCOPE OF WORK.
 PLEASE SEE 250.50 AS THE FOOTER STEEL IS REQUIRED TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 RESPONSE LETTER FROM ARCHITECT MENTIONS TO SEE PLANS
 WHICH WILL PART OF THE MAIN BUILDING PERMIT HOWEVER THE
 FOUNDATION STEEL IS PART OF THE SCOPE OF WORK FOR THIS
 PERMIT AND ELECTRICAL PLANS/DETAILS ARE REQUIRED.
 PLEASE SEE THE LETTER FROM THE ENGINEERING FIRM TEELE
 AND ASSOCIATES DOES NOT PROVIDE THE REQUIRED PLANS.
 THIS LETTER MAKES REFERENCE TO THE NEC AND 250.66B AND
 250.70 WITHOUT ACTUALLY SUBMITTING ANY PLANS. THE
 SHEETS ATTACHED TO THE LETTER ARE NOT FROM THE NEC/
 NFPA-70 2005.
 PLEASE ALSO KNOW THE CODE SECTION AS REFERENCE IN
 LETTER ONLY APPLIES IN CERTAIN CIRCUMSTANCES. THE
 SIZING OF THE GROUNDING ELECTRODE CONDUCTOR IS STILL
 REQUIRED TO MEET 250.66.
 PLEASE SUBMIT MINIMUM PLANS AS PREVIOUSLY NOTED.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: *** IMPORTANT ***
 PLEASE KEEP IN MIND AS SLAB WORK APPEARS TO BE PART OF
 THE PROPOSED FOUNDATION, ANY SLAB CONDUITS FOR
 ELECTRICAL WOULD NEED TO BE SHOWN ALSO AT THIS TIME. IF
 SLAB WORK WILL NOT CONTAIN ANY SLAB CONDUITS FOR ITEMS
 SUCH AS FLOOR BOXES, FEEDERS ETC THEN THIS WILL NOT BE
 NEEDED.
 ***
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By dpalmer Date 2008-01-31 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2008-01-31 Time 16:25 Sent To  
Notes
2008-01-31 16:25:52** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION MENTIONS
 PLANS AND SCOPE OF WORK FOR NEW BUILDING PREVIOUSLY
 SUBMITTED. PLEASE KNOW HOWEVER THE SCOPE OF WORK WAS
 FOR COMMERCIAL REMODEL ON PLANS APPLIED IN DEC 06 WAS
 NOT FOR A NEW BUILDING.
 PLEASE ALSO SEE THAT APPLIED PERMIT HAS ALSO ALREADY
 EXPIRED.
  
 2) NOTE: PLEASE SUBMIT GROUNDING ELECTRODE DETAIL FOR
 FOUNDATION AND ATTACHMENT(S) TO NEW FOOTER STEEL.
 250.50, 250.66.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 09:37 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 09:37 Sent To  
Notes
2008-02-27 09:41:37***FOUNDATION ONLY***
  
 NO LINES ASSOCIATED WITH FIRE PROTECTION EQUIPMENT
 SHALL RUN OR EXTEND BENEATH ANY PORTION OF THE
 FOUNDATION THAT WOULD IMPACT ABILITY TO REPAIR SYSTEM
 IF NEEDED.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-06-03 Cont ID  
Sent By jgomez Date 2009-06-03 Time 16:09 Rev Time 0.00
Received By jgomez Date 2009-06-03 Time 16:08 Sent To  
Notes
2009-06-03 16:09:41REVISION SENT TO JIM WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-06-03 Cont ID  
Sent By jgomez Date 2009-06-03 Time 11:19 Rev Time 0.00
Received By jgomez Date 2009-06-03 Time 11:19 Sent To  
Notes
2009-06-03 11:22:28TEMP. CONSTRUCTION FENCE REVISION SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 09:06 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 09:06 Sent To Z
Notes
2009-04-03 09:11:20TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 08:58 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 08:58 Sent To  
Notes
2009-04-03 09:03:38TO "C3"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-18 Cont ID  
Sent By adarroug Date 2009-03-18 Time 16:50 Rev Time 0.00
Received By adarroug Date 2009-03-18 Time 16:50 Sent To B
Notes
2009-03-18 16:51:22TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 14:28 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 14:28 Sent To  
Notes
2008-07-17 14:28:52TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 15:46 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 15:46 Sent To  
Notes
2008-04-02 15:49:51TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 09:46 Rev Time 0.00
Received By mwennerg Date 2008-01-28 Time 15:55 Sent To  
Notes
2008-01-29 10:56:171/29/08--TO "COMM" BD#42
2008-01-28 15:56:24TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-24 Cont ID  
Sent By mperson Date 2008-07-24 Time 11:30 Rev Time 0.00
Received By mperson Date 2008-07-24 Time 11:29 Sent To  
Notes
2008-07-24 11:48:28****************PROVISO****************
 PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 *105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF THE FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODE.
 NOTE: THE FOLLOWING FIXTURES SHALL BE COMPLIANT WITH
 THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE ALL
 SECTIONS.
 A} WATER COOLERS= 11-4.15.
 B} WATER CLOSET= SECTION 11-4.16.
 C} LAVATORIES= SECTION 11-4.19.
 D} SINKS= 11-4.24.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-11 Cont ID  
Sent By mperson Date 2008-04-11 Time 08:08 Rev Time 0.00
Received By mperson Date 2008-04-11 Time 08:08 Sent To  
Notes
2008-04-11 11:00:22PLUMBING PLAN REVIEW:
 DENIED 2ND TIME
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL AS
 THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS
 PLUMBING REVIEW COMMENTS.
  
 1. **OK** COMMENT ADDRESSED, LETTERS HAVE BEEN
 FORWARDED TO KEN CONRAD CHIEF BUILDING INSPECTOR.
  
 2. SHEET S1 IS INDICATING A BATHROOM WITH A WATER
 CLOSET AND LAVATORY AND SHEET S-1 IS INDICATING A 4"
 SLAB-ON-GRADE. IS IT THE INTENTOF THIS FOUNDATION
 PERMIT TO POUR THE SLAB ON GRADE WITHOUT THE
 UNDERGROUND PLUMBIMG BEING INSTALLED. PLEASE CLARIFY
 PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1.2 ADDITIONAL DATA REQUIRED.
 **RESONSE NOTED AND REVIEW OF THE NEW ATTACHED
 PLUMBING SHEETS WILL BE UNDER NEW COMMENTS.
  
 3. **PLUMBING PROVISO** PER CITY OF WPB AMENDMENTS TO
 CHAPTER 1, SECTION *105.13 PHASED PERMIT APPROVAL.
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF THE FOUNDATIONS. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY REQUIRED TO
 MEET THE REQUIREMENTS OF THE TECHNICAL CODE.
 **RESPONSE NOTED.
  
 THE FOLLOWING ARE NEW COMMENTS.
  
 4. SHEET C1 USE AND OCCUPANCY CLASSIFICATION IS
 INDICATING ON THE FIRST AND SECOND LEVEL THAT MODERATE
 HAZARD STORAGE IS IN GROUP S-1. WHAT TYPES AND QUANTITY
 OF HAZARDOUS MATERIALS ARE GOING TO BE STORED? PER
 (W.P.B.) SECTION 106.1.2 ADDITIONAL DATA AND FBC
 PLUMBING SECTION 411 EMERGENCY SHOWER AND EYEWASH
 STATIONS MAY BE REQUIRED.
  
 5. SHEET P1.1 INDICATES FOUR SEPERATE RETAIL SPACES.
 PLEASE CLARIFY IF THE RETAIL SPACES HAVE ONE OWNER OR
 IF THERE ARE FOUR SEPERATE OWNERS. PER FBC PLUMBING
 SECTION 403.6 PUBLIC FACILITIES.CUSTOMERS, PATRONS AND
 VISITORS SHALL BE PROVIDED WITH PUBLIC TOILET
 FACILITIES IN STRUCTURES AND TENANT SPACES INTENDED FOR
 PUBLIC UTILIZATION. PUBLIC TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE
 SPACE REQUIRED TO BE PROVIDED WITH PUBLIC TOILET
 FACILITIES AND THE PATH OF TRAVEL TO SUCH FACILITIES
 SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 M).
  
 6. SHEET P1.1 THE STORM DRAIN REQUIRES A TWO-WAY
 CLEANOUT OUTSIDE OF THE BUILDING. PER FBC PLUMBING
 SECTION 1101.8 CLEANOUTS REQUIRED (SECTION 708.3.5 ).
  
 7. SHEET P3.1 PLEASE CLARIFY IF THERE ARE PARAPET
 WALLS AND IF SO WHAT ARE THE CALCULATIONS? PER FBC
 PLUMING SECTION 1106.4 VERTICAL WALLS.
  
 8. SHEET P3.2 THE SQUARE FOOTAGE FOR RD-1 AND RD-2
 APPEARS LOW. MY CALCULATIONS COME TO 2517.5 SQ. FT. FOR
 RD-1 AND 2052 SQ. FT. FOR RD-2 AND THATS NOT
 CALCULATING IF THERE ARE PARAPET WALLS. PER FBC
 PLUMBING SECTION 1101.1 SCOPE AND 1106.4 VERTICAL
 WALLS.
  
 9. SHEET P4.1 PLUMBING SPECIFICATIONS (2) CODES AND
 STANDARDS (A) THE CODE STANDARDS REFERENCED ARE NOT
 COMPLIANT PLEASE DELETE THOSE CODE REFERENCE STANDARDS
 AND ADD IN ITS PLACE "FBC-2004 WITH 2007 REVISIONS".
  
 7. SHEET P4.1 PLUMBING SPECIFICATIONS (5) MATERIALS
 (F) AIR CHAMBERS ARE NOT APPROVED BY FBC PLUMBING
 SECTION 604.9 WATER HAMMER. HOWEVER IF IT IS THE INTENT
 TO USE AIR CHAMBERS THEY SHALL BE INSTALLED PER
 "STANDARD PDI-WH 201 RECHARGEABLE TYPE AIR CHAMBER. A
 DETAIL OF THIS TYPE OF AIR CHAMBER IS REQUIRED ON PLANS
 OR DELETE AIR CHAMBERS ON THE RESUBMITTAL.
  
 8. SHEET P4.1 SANITARY RISER A CLEANOUT IS REQUIRED AT
 THE BASE OF THE STACK ON RISER S-1, PER FBC PLUMBING
 SECTION 708.3.4 AND A TWO-WAY CLEANOUT IS REQUIRED AT
 THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER,
 PER FBC PLUMBING SECTION 708.3.5.
  
 9. SHEET P4.2 STORM RISERS CLEANOUTS ARE REQUIRED AT
 THE BASE OF THE VERTICAL STORM LEADERS, PER 1101.8
 (708.3.4) AND A TWO-WAY CLEANOUT IS REQUIRED ON THE
 HORIZONTAL STORM DRAINAGE PIPE OUTSIDE OF THE BUILDING,
 PER FBC PLUMBING 1101.8 (708.3.5).
  
 10. SHEET P4.2 STORM RISERS: THE STORM RISERS WERE
 REVIEWED PER MINIMUM REQUIREMENTS PER FBC PLUMBING
 TABLE 1106.3 SLOPE OF 1/8 INCH PER FOOT (1-PERCENT). IF
 IT IS THE INTENT OF THE DESIGNER TO USE OTHER SLOPE
 REQUIREMENTS IT MUST BE CLEARLY INDICATED ON THE PLANS.
 PLEASE CORRECT ALL MAIN UNDERGROUND HORIZONTAL STORM
 DRAINAGE PIPING SIZES FOR THE ROOF DRAINS. PLEASE
 CORRECT THE FOLLOWING BRANCHES TO THE ABOVE GROUND
 HORIZONTAL STORM DRAINAGE PIPE TO RD-1, RD-2, RD-3, AND
 RD-5. PLEASE CORRECT ALL MAIN ABOVE GROUND HORIZONTAL
 STORM DRAINAGE PIPE SIZES FOR THE EMERGENCY DRAINS.
 PLEASE CORRECT THE FOLLOWING BRANCHES TO THE ABOVE
 GROUND HORIZONTAL STORM DRAINAGE PIPE TO ED-3, AND
 ED-5. PER FBC PLUMBING TABLE 1106.3 (1-PERCENT SLOPE).
  
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 16:38 Rev Time 0.00
Received By mperson Date 2008-02-15 Time 16:38 Sent To  
Notes
2008-02-15 16:58:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: THERE ARE TWO EXPIRED PERMITS (PERMIT #
 06110395 & 06120401 BOTH FOR COM/REMOD) FOR THIS
 ADDRESS BY R & D CONTRACTORS, INC. WHICH IS THE SAME
 CONTRACTOR FOR THIS FOUNDATION PERMIT. THERE IS ALSO A
 FULL DEMO PERMIT THAT HAS BEEN ISSUED FOR THIS ADDRESS
 TO R & D CONTRACTORS, INC. IS THIS FULL DEMO PERMIT FOR
 THE BUILDINGS INDICATED IN THE EXPIRED PERMITS. PLEASE
 REFERENCE THE PERMIT INFORMATION SHEETS ATTACHED TO THE
 PLUMBING COMMENTS INDICATING THIS.
 **AN ORIGINAL NOTARIZED LETTER IS REQUIRED FROM R & D
 CONTRACTORS, INC. VOIDING OUT THE EXPIRED PERMITS OF
 06110395 AND 06120401 EVEN IF THE BUILDINGS HAVE BEEN
 DEMOED.
  
 2. SHEET S1 IS INDICATING A BATHROOM WITH A WATER
 CLOSET AND LAVATORY AND SHEET S-1 IS INDICATING A 4"
 SLAB-ON-GRADE. IS IT THE INTENTOF THIS FOUNDATION
 PERMIT TO POUR THE SLAB ON GRADE WITHOUT THE
 UNDERGROUND PLUMBIMG BEING INSTALLED. PLEASE CLARIFY
 PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1.2 ADDITIONAL DATA REQUIRED.
  
 3. **PLUMBING PROVISO** PER CITY OF WPB AMENDMENTS TO
 CHAPTER 1, SECTION *105.13 PHASED PERMIT APPROVAL.
 AFTER SUBMITTAL OF THE APPROPRIATE CONSTRUCTION
 DOCUMENTS, THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF THE FOUNDATIONS. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY REQUIRED TO
 MEET THE REQUIREMENTS OF THE TECHNICAL CODE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2009-06-05 Cont ID  
Sent By kdfreema Date 2009-06-05 Time 15:54 Rev Time 0.00
Received By kdfreema Date 2009-06-05 Time 15:54 Sent To  
Notes
2009-06-05 15:54:55***PROVISO***
  
 FABRIC SHALL BE NO LESS THAN 85 PERCENT OPAQUE AND
 COVER ENTIRE FENCE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 4 Status F Date 2009-04-07 Cont ID  
Sent By kdfreema Date 2009-04-07 Time 09:28 Rev Time 0.00
Received By kdfreema Date 2009-04-07 Time 09:28 Sent To  
Notes
2009-04-07 09:34:13***FAILED***
  
 TEMPORARY FENCE REVISION SUBMITTED 4/1/09
  
 1. THE TEMPORARY FENCE SHALL MEET ALL REQUIREMENTS
 FOUND WITHIN SEC. 94-450(E)(2) WHICH I HAVE INCLUDED IN
 THE PERMIT PACKAGE. TAKE SPECIAL NOTE OF SUB PARAGRAPH
 5 WHICH REQUIRES SCREENING MATERIAL TO BE ATTACHED TO
 THE FENCE.
  
 2. AS SHOWN, THE FENCE IS LOCATED WITHIN THE VISIBILITY
 TRIANGLE. ENSURE THAT THE CORNERS OF THE PROPERTY ARE
 NOT OBSTRUCTED. I HAVE INCLUDED A COPY OF THE VISIBLITY
 REQUIREMENTS IN THE PERMIT PACKAGE FOR YOUR REFERENCE.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-07-22 Cont ID  
Sent By kdfreema Date 2008-07-22 Time 08:54 Rev Time 0.00
Received By kdfreema Date 2008-07-22 Time 08:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By kdfreema Date 2008-04-08 Time 14:24 Rev Time 0.00
Received By kdfreema Date 2008-04-08 Time 14:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By kdfreema Date 2008-01-29 Time 09:53 Rev Time 0.00
Received By kdfreema Date 2008-01-29 Time 09:53 Sent To  
Notes
2008-01-29 10:28:14***FAILED***
  
 1. AS DISCUSSED BY PHONE, ZONING WILL BE UNABLE TO
 APPROVE PERMIT UNTIL THE PENDING EASEMENT ABANDONMENTS
 HAVE BEEN ACTED UPON BY THE CITY COMMISSION. THIS IS
 SCHEDULED FOR THE FEBRUARY 11, 2008, AGENDA.
  
 2. PLEASE PROVIDE TWO SIGNED AND SEALED SURVEYS WITH
 THE RESUBMITTAL.
  
 3. PLEASE REVISE SHEET S-1 TO SHOW PROPERTY LINES AND
 BUILDING SETBACKS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] WITH QUESTIONS.