| 2008-01-29 16:34:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.SHUTTER SPAN FOR ACCORDION SHUTTERS SHOULD |
| | CORRELATE WITH THE OPENING HEIGHT (BLADE LENGTH). |
| | PLEASE REVISE INSTALLATION SCHEDULE. |
| | |
| | 2.SEE OPENING 5.AN OPENING OF 57", WITH 3" EDGE |
| | DISTANCE TOP AND BOTTOM, SHOULD HAVE A SPAN OF |
| | APPROXIMATELY 61".SEE THE ANCHOR CHART ON SHEET 8. |
| | YOU HAVE HIGHLIGHTED THE "CONCRETE" COLUMN BUT SHOULD |
| | BE USING THE "MASONRY" COLUMN AS YOU HAVE SPECIFIED |
| | BLOCK AS THE SUBSTRATE ON THE INSTALLATION SCHEDULE. 7" |
| | SPACING IS REQUIRED FOR THE BOTTOM. |
| | |
| | 3.SEE OPENING 8.FOR A SPAN OF APPROXIMATELY 110", |
| | (NOTE THAT YOU STATE IT IS 320", PLEASE REVISE) YOU |
| | MUST USE THE COLUMN FOR NOTE 3, 3 1/2" AND 5" ANCHOR |
| | SPACING REQUIRED.IF THE SUBSTRATE IS CONCRETE, 9" AND |
| | 6" REQUIRED, NOT 9" AND 9" AS SPECIFIED ON THE |
| | INSTALLATION SCHEDULE. |
| | |
| | 4.PLEASE CHECK ALL OPENINGS; THESE COMMENTS MAY APPLY |
| | TO OTHER OPENINGS AS NOT ALL WERE CHECKED. |