Plan Review Details - Permit 08010592
Plan Review Stops For Permit 08010592
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By jwitmer Date 2008-03-17 Time 12:27 Rev Time 48.00
Received By jwitmer Date 2008-03-17 Time 12:27 Sent To  
Notes
2008-03-17 12:37:10BUILDING PLAN REVIEW
 PERMIT: 08010592
 ADD: 510 4TH STREET
 CONT:TRENTO CONSTRUCTION CO
 TEL: (786)631-5616
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW ?PLAN REVIEW?
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) PLEASE PROVIDE A COPY OF THE UNITY OF TITLE FOR
 BLOCK 16 OF PLAT CLOWS ADDITION, AND THE NORTHERN HALF
 OF 4TH STREET.THE UNITY OF TITLE SUBMITTED IS FOR
 BLOCK 27 OR THE SOUTH TOWER. NOTE, THE LANGUAGE IN THE
 UNITY OF TITLE FOR THE SOUTH BLOCK 27 THERE IS A TRUE
 PROPERTY LINE BETWEEN BLOCK 27 AND BLOCK 16 WHICH THIS
 BUILDING WILL BE BUILT UPON.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE.
  
 4) THIS BUILDING IS TO BE CLASSIFIED AS A ?THRESHOLD
 BUILDING? BY FLORIDA STATUTE 553.71
 ANDREQUIRING 3 SETS OF ALL DOCUMENTS TO BE SUBMITTED
 TO THE BUILDING DEPARTMENT, PLANS ,REPORTS, PRODUCT
 APPROVALS AND SUBMITTALS. 109.3.6.*
  
 5)INFORMATIONAL: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 7) SHEET AN-1.0:110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. NOTE IF A BUILDING PERMIT IS NOT APPLIED FOR
 BEFORE OCT.1 2008 THE 2007 FLORIDA BUILDING CODE WILL
 BE ADOPTED AND ENACTED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 THIS BUILDING IS CLASSIFIED AS A MIXED USE OCCUPANCY,
 MISSING THE RETAIL ON THE FIRST FLOOR.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.COMPLIED.
 D) THE OCCUPANT LOAD, SEE 1004.
 E. ) NUMBER OF UNITS
 F ) NUMBER OF FLOORS
 G ) NUMBER OF BEDROOMS
 H ) NUMBER OF ROOMS
 I ) NUMBER OF BEDROOMS
 J ) SQ. FT. LIV SPACE/ FL
 K) SQ. FT. FOOTPRINT
 L ) TOTAL SQUARE FOOT WITHIN BUILDING
  
 7C) PLANS INDICATE THAT A SEPARATE PERMIT WILL BE
 REQUIRED FOR. NOTE THIS STRUCTURE IS DESIGNED AS AN
 ENCLOSED STRUCTURE WITH A INTERNAL PRESSURE COEFFICIENT
 OF +/-0.18 REQUIRING
 GLAZED OPENING PROTECTION TO COMPLETE THE ENVELOPE OF
 THE BUILDING, REQUIRING THE EXTERIOR WINDOWS AND DOORS
 AS PART OF THIS PERMIT PACKAGE, 106.3.5.1.1(8) BEFORE
 THE BUILDING PERMIT WILL BE ISSUED.
  
 8)SHEET AN-2.0:
 8A) GRIDLINE A & A.1 WHICH IS THE SOUTH BASEMENT WALL,
 NO WALL IDENTIFICATION TAGS.
  
 8B) NOTE, THERE CAN BE NO OPENINGS THROUGH TO THE SOUTH
 GARAGE, THIS IS A TRUE PROPERTY LINE, THERE IS NO
 LONGERA PUBLIC ACCESS RIGHT OF WAY, (PUBLIC STREET)
 SEE TABLE 704.8.
  
 8C) STAIRWELL# 1 PLEASE PROVIDE WALL IDENTIFICATION
 TAGS, 106.1.2 & 707.4.
  
 8D) STAIRWELL DOORS LISTED ON SHEET AN-8.0DOOR # 3 ARE
 INDICATED AS A ?B? LABEL DOOR REFLECTING THE AMBIENT
 TEMPERATURE RISE BUT THE DOOR SCHEDULE FAILS TO
 IDENTIFY IN HOURS THE ASSEMBLY RATING, PLEASE SEE TABLE
 715.3.
  
 8E) THE ELEVATOR DOORS LISTED ON SHEET AN-8.0 DOOR # 12
 ARE LISTED AS A ?B? LABEL DOOR BUT THE HOUR RATING IS
 NOT PROVIDED.
  
 8F) REFERENCE ** PLEASE CORRECT FROM THE SFBC AND
 SECTION TO THE CURRENT CODE.
  
 9) SHEET AN-2.1:
 9A) THIS SHEET INDICATES A DROP OFF OR LOADING ZONE AT
 THE FRONT CURB LINE. THIS SHEET NOR
 AN-1.2 INDICATE AACCESS AISLE 60 INCHES BY 20FEET,
 PLEASE SEE THE REQUIREMENTS
 OF 11-4.6.6. PLEASE SEE 11-4.29.5 DETECTABLE WARNINGS
 AT HAZARDOUS VEHICULAR AREAS.
  
 9B)PLEASE SEE STAIR#2 & STAIR#4, THEY BOTH DROP YOU
 OUTSIDE OF THE 2 HR RATED ENCLOSURE WHILE STILL WITHIN
 THE FOOTPRINT OF THE BUILDING. PLEASE SEE 403.13 AND
 1019.1.8.1. STAIRWELL# 4 ALSO DROPS YOU IN A TRAFFIC
 AREA WITH NO SIDEWALK OR WALKWAY.
  
 9C) THIS COMMENT WILL STAND FOR ALL EXIT ENCLOSURES 4
 STORIES OR MORE THAN HEIGHT, ALL DOORS THAT ARE
 DESIGNATED BY DOOR# 3 ARE TO BE 90 MINUTE OPENING
 PROTECTION SEE TABLE 715.3.
  
 9D) IN THE NORTHEAST CORNER OF THE GARAGE BY PARKING
 SPACE# 12 THERE IS A DOOR # 04 WHICH IS AN EXIT THAT
 ALSO LEADS DIRECTLY INTO THE TRAFFIC LANE WITH NO
 WALKWAYS LEADING TO THE PUBLIC WAY. SEE EXIT DISCHARGE&
 11-4.1.3(8)(A) &(B).
  
 9E) BOTH THE LAUNDRY ROOM AND TRASH ROOM ARE BOTH
 CONSIDERED TERMINATION ROOMS REQUIRING THE DOOR TO HAVE
 BE ? HR OPENING PROTECTION. SEE 707.13.4. THIS DOOR IS
 TO BE SELF-CLOSING OR AUTOMATIC CLOSING UPON THE
 DETECTION OF SMOKE.
  
 9F) DOORS THAT LEAD FROM THE LOBBY INTO THE PARKING
 GARAGE ARE LED INTO THE GARAGE BY DOOR# 14, PLEASE
 CORRECT THE DOOR SCHEDULE AND PROVIDE HR RATING SEE
 TABLE 302.3.2 AND TABLE 715.3.
  
 9G) THE RETAIL TENANT SPACE WITH 828 SQ FT IS INDICATED
 WITH THE TENANT SEPARATION WALLS AS NON-RATED WALLS,
 PLEASE SEE 708.3.& 302.2.
  
 9H) THE FIRE CONTROL ROOM IS TO BE SEPARATED BY A
 1-HOUR RATED WALL AND OPENING PROTECTIVES. SEE DOOR 15
 IS NOT PROVIDED IN HOURS THE FIRE RATING PLEASE
 CORRECT, TABLE 715.3.
  
 9I) MISSING WALL IDENTIFICATION TAG FOR THE WALL THAT
 SEPARATES THE LOBBY ANDBICYCLE STORAGE AREA.
  
 9J)RESTROOMS NEXT TO BICYCLE STORAGE NEED ACCESSIBLE
 RESTROOMS11-4.16. SHOWER ROOMS NEXT TO THE BICYCLE
 STORAGEPLEASE SEE 11-4.21.7. CURBS. 11-4.21.4 GRAB
 BARS. THE
 RESTROOMS ARE MISSING THE SINK IN THE STALL, SEE
 FLORIDA ACCESSIBILITY COMMON AREAS 11-4.22.4/
 11-4.17.3.& 11-4.13.7 DOORS IN SERIES.
  
 9K) FIRE PUMP ROOM IS INDICATED AS A LOUVER IN THE 2 HR
 RATED WALL AND NOTE TO SEE MECHANICAL PLAN MN-2.04 NO
 MENTION OF FIRE DAMPER IN THE RATED WALL. SEE TABLE
 716.3.1.
  
 9L) DOOR # 16 THE BACK OF THE RETAIL TENANT SPACES AND
 THE DOOR LEADING TO THE MEETING ROOM IS IDENTIFIED AS
 DOOR TYPE M A PAIR OF LOUVERED DOORS. PLEASE SEE TENANT
 SEPARATION REQUIREMENTS AND RATINGS.
  
 10) SHEET AN2.2:
 10A) PLEASE PROVIDE CALCULATIONS FOR WHAT AREA IS TO BE
 CONSIDERED A MEZZANINE. SEE 505.2
 THE AGGREGATE AREA OF A MEZZANINE WITHIN A ROOM SHALL
 NOT EXCEED ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE
 IN WHICH THEY ARE LOCATED. IT APPEARS THIS IS A SECOND
 FLOOR.
  
 10B) DOOR # 14 IS THE REFUSE CHUTE ACCESS ROOM
 REQUIRING A ? HR OPENING PROTECTIVE. PLEASE CORRECT
 DOOR SCHEDULE DOOR CLASSIFICATION AND RATING 707.13.3.
  
 10C) THE REFUSE SHAFT WALL IS NOT TAGGED ON THIS SHEET.
 707.4.
  
 10D)STAIR# 4 THE MEZZANINE LEVEL IT APPEARS THAT
 WITHIN THE STAIRWELL THERE IS A WALL NOT RATED, THIS
 WALL APPEARS TO BE THE EXIT PASSAGE WAY ON THE FIRST
 FLOOR LEVEL AND PART OF THE EXIT ENCLOSURE. PLEASE TURN
 TO PN-2.05 IT APPEARS THAT WITHIN THE ENCLOSURE THERE
 ALSO RUNS A 3? SANITARY STACK AND AIR ADMITTANCE
 DEVICE. 707.7.1 & 1019.1.2.
  
 10E) PLEASE SEE STAIRWELL# 3 AND 3 INCH STACK IN
 STAIRWELL, 707.7.1 & 1019.1.2.
  
 10F)STAIRWELL# 1THE MEZZANINE LEVEL APPEARS AGAIN
 TO HAVE A LARGE VOID SPACE FROM THE FIRST FLOOR, PLEASE
 SEE PN-2.06 WHERE BOTH A 3? AND 4? RISER DROP BELOW THE
 2ND FLOOR SLAB AND ARE PICKED UP IN THE MEZZANINE LEVEL
 STAIRWELL, MEZZANINE LEVEL VOID. SEE 707.7.1 &
 1019.1.2.
  
 11) SHEET AN-2.3:
 11A) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS, MISSING THE REQUIRED ELEVATOR LOBBY:
 707.14.1ELEVATOR LOBBY. ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS REQUIRED BY SECTION
 1016.1 SHALL BE PROVIDED WITH AN ELEVATOR LOBBY AT EACH
 FLOOR CONTAINING SUCH A CORRIDOR. THE LOBBY SHALL
 SEPARATE THE ELEVATORS FROM THE CORRIDOR BY FIRE
 PARTITIONS AND THE REQUIRED OPENING PROTECTION.
 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE.
 SEE ALSO CODE COMMENTARY.
  
 11B) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS,VARIOUS CONDO UNITS DO NOT PROVIDE WALL
 TAGS IDENTIFYING THE WALLS BETWEEN UNITS AND OR UNITS
 AND ASSOCIATED ROOMS SUCH AS THE MEETING ROOMS AND OR
 BUSINESS CENTER.
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC ) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 11C) THIS COMMENT WILL STAND FOR THE 2ND THROUGH THE
 8TH FLOORS. PROVIDE INFORMATION AS TO HOW CODE
 COMPLIANCE WILL BE ACHIEVED FOR : 1207.3
 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 11D) EAST END OFTHE BUILDING TENANT STORAGE UNIT AND
 DOOR#18 ARE TO RESIST THE PASSAGE OF SMOKE PLEASE
 PROVIDE SEE 302.1.1.1 AND 710.5.2.
  
 11E) EAST END OF THE BUILDING THE MAIN ELECTRIC ROOM
 WALL COMMON TO CONDO UNIT IS INDICATED TO BE A ?P-2?
 TYPE PARTITION, PLEASE PROVIDE THE STC RATING FOR THIS
 WALL 1207.2
 AIR-BORNE SOUND.
  
 12)SHEET AN-2.4:
 12A) GRID LINE O-4 THERE IS A ROOM THAT IS NOT
 IDENTIFIED THE MECHANICAL PLAN INDICATES A MECHANICAL
 ELECTRICAL ROOM. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 12B) JUST ADJACENT THERE APPEARS TO BE A SPACE OR VOID
 AREA THAT APPEARS TO BE A SHAFT, ADDITIONAL INFORMATION
 REQUIRED, 106.1.2.THIS COMMENT WILL SERVE FOR ALL
 FLOORS.
  
 12C) THE LINEN ACCESS ROOM AND REFUSE ACCESS ROOMS ARE
 NOT IDENTIFIED NOR WALL TAGS PROVIDED WITH WALL
 RATINGS, PLEASE IDENTIFY.707.13.3.
  
 12D) GRID LINE G1 BETWEEN 15& 16 THERE IS A VOID SPACE
 ON THIS PLAN PLEASE IDENTIFY THIS SPACE IT APPEARS THIS
 MAY BE A SHAFT REQUIRING 2 HR CONSTRUCTION. 707.4. THIS
 AREA DOES APPEAR TO BE CONSISTENT ON ALL FLOORS .THIS
 COMMENT WILL SERVE FOR ALL FLOORS.
  
 12E) GRID LINE G BETWEEN 3 & 4 APPEAR TO HAVE THE SAME
 VOID AREA IS SHAFT WALL CONSTRUCTION REQUIRED TO BE 2
 HR. 707.4. THIS COMMENT WILL SERVE FOR ALL FLOORS.
  
 12F) GRID LINE N & 15.1 IT APPEARS TO BE A VOID SPACE
 IS THIS SHAFT WALL CONSTRUCTION REQUIRED TO BE 2 HR
 707.4. THIS COMMENT WILL SERVE FOR ALL FLOORS.
  
 13) SHEET AN-2.8ROOF DECK:
 13A)NOTE THERE ARE TWO AREAS OF THE ROOF THAT HAVE ROOF
 DRAINS BUT NO OVERFLOW EMERGENCY SCUPPERS:
 13A) (1) ON GRID LINE E2 JUST TO THE RIGHT OF
 ELEVATOR# 5.
 13A)(2) NORTH OF GRID LINE M AND EAST OF GRID LINE
 13,
 IN BOTH CASES THE SURROUNDING OVERFLOW SIZE HAS STAYED
 THE SAME BUT THE VOLUME THAT WOULD HAVE BEEN DOUBLED
 ISN?T INDICATED WITH LARGER OVERFLOW SCUPPERS? 1503.4.
  
 13B) ELEVATOR# 5 INDICATES AN ELEVATOR EQUIPMENT ROOM
 WITH NO WALL RATINGS, PLEASE SEE
 3006.4.
  
 13C) POOL DECK SHEET AN-6.2 INDICATES THE ELEVATOR AND
 POOL DECK, WITH A STORAGE ROOM
 WHAT HAPPENS TO THE ELEVATOR HOIST WAY TO THE WEST SIDE
 DOES IT ALSO BECOME A SINGLE ELEVATOR TO THIS FLOOR
 LEVEL?
  
 13D)FOR THE METAL STAIRS AND GRANDSTAND PLEASE
 PROVIDE THE MINIMUM LIVE LOADS THESE AREAS ARE TO BE
 DESIGNED TO. ONCE THESE FACTORS ARE KNOWN SHOP DRAWINGS
 TO FOLLOW AFTER PERMITTING. TABLE 1607.1.
 13E) THE 48? HIGH POOL GATE SEPARATING THE SKY CINEMA
 AND POOL DECK IS MISSING THE 18?
 ON THE LATCH SIDE. SEE A117.1 98 TABLE 404.2.4.1 FIGURE
 404.2.4.1(A).
  
 13F) SHEET AN-7.5 THE RESTROOMS ARE MISSING THE SINK IN
 THE STALL, SEE FLORIDA ACCESSIBILITY COMMON AREAS
 11-4.22.4/ 11-4.17.3.
  
 14) STAIR IDENTIFICATION:
 14A) PLEASE SEE 1019.1.6 FOR REQUIREMENTS FOR AN
 APPROVED BARRIER AT THE LEVEL OF EXIT DISCHARGE TO
 PREVENT PERSONS FROM UNINTENTIONALLY CONTINUING INTO
 THE LEVELS BELOW.
 THIS COMMENT WILL HOLD FOR ALL STAIRS THAT LEAD BELOW
 GRADE.
  
 14B) STAIR FLOOR NUMBERING SIGNAGE REQUIRED PLEASE SEE
 1019.1.7 FOR REQUIRED SIGNAGE, FLOOR LEVEL, THE
 TERMINUS OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE
 AND THE IDENTIFICATION OF THE STAIR AND AVAILABILITY OF
 ROOF ACCESS. THIS STATEMENT WILL SERVE FOR ALL
 STAIRWELLS AFFECTED.
  
 14C) 1019.1.8 PLEASE SEE 1019.1.8 SMOKE PROOF
 ENCLOSURES. PLEASE PROVIDE CODE COMPLIANCE FOR SMOKE
 PROOF ENCLOSURES OR PRESSURIZED STAIRWAY IN ACCORDANCE
 WITH 909.20.
  
 15) SHEET AN-6.9
 15A) DETAIL# 8 INDICATES THE USE OF 3/4INCH CDX PLYWOOD
 SHEATHING. PLEASE SEE TABLE 601 FOOTNOTE ?(2). PLEASE
 PROVIDE WHAT TYPE OF SHEATHING WILL BE USED SINCE THE
 CDX PLYWOOD WILL NOT MEET THE REQUIREMENT F FOOTNOTE
 ?C?
  
 15B) PLEASE NOTE THAT ANY FABRIC CANOPIES SHOWN ON THE
 PLANS WILL REQUIRE A SEPARATE PERMIT AND ASSOCIATED
 FEES. 108.3.
  
 16) SHEET AN-6.13:
 16A) THE PLANS INDICATE THE USE OF 4X10, 4X12 CYPRESS
 WOOD BEAMS AND T& G SHEATHING.
 PLEASE SEE THE REQUIREMENTS FOR USING FIRE RETARDANT
 TREATED WOOD IN TYPE I-A BUILDINGS
 SEE TABLE 601 FOOTNOTE( C )(2) (III) .
  
 16B) NOTE THAT AS DETAILED THE ROOFING NAILS WILL
 PENETRATE THE T&G SHEATHING AND WILL BE VISIBLE. SEE
 1507.3.6THE FASTENER SHALL PENETRATE THE DECK A
 MINIMUM OF 0.75 INCHES OR
 THROUGH THE THICKNESS OF THE DECK, WHICHEVER IS LESS.
  
  
 17) AN-6.16:
 17A) THE PLANS SHOW SEVERAL CUT DETAILS SECTION G SHEET
 A9.1 THIS SHEET IS MISSING FROM THE PLANS, IT IS SHOWN
 ON THE INDEX SHEET.
  
 17B) THE MISSING SHEET A9.1 SECTION G & K DOES NEED TO
 SHOW COMPLIANCE WITH FLASHINGS SEE 1405.3. SEE SILLS,
 PROJECTING TRIM AND COPINGS.
  
 17C)DETAIL G SHEET A9.2 IS A TYPICAL SLIDING GLASS
 DOOR DETAIL, PLEASE SEE COMMENT ABOVE ABOUT FLASHINGS.
 THE REAL ISSUE IS HOW YOU INTEND TO COMPLY WITH FAIR
 HOUSING,
 SLIDING SECONDARY DOORS AT CONCRETE LANDINGS. FROM THE
 INTERIOR FINISH FLOOR TO THE TOP OF THE TRACK THE
 HEIGHT CHANGE IS TO BE I/4? IT CAN BE ?? IF A FILLER
 WITH A 1:2 SLOPE IS APPLIED.
 THEN THE MAX DROP OF 4? TO THE FINISHED CONCRETE
 BALCONY DECK BELOW. SEE ATTACHMENT.
 THE FAIR HOUSING ACT MADE IT LAW A NATIONAL STANDARD
 FOR BUILDINGS AND FACILITIES PROVIDING ACCESSIBILITY
 AND USABILITY FOR PHYSICALLY HANDICAPPED PEOPLE. THE
 GUIDELINES ARE NOT MANDATORY BUT INTENDED TO PROVIDE A
 SAFE HARBOR FOR COMPLIANCE WITH THE ACCESSIBILITY
 REQUIREMENTS OF THE FAIR HOUSING ACT.
  
 ATTACHED IS ONE OTHER METHOD OF MEETING THESE
 REQUIREMENTS. IT HAS BEEN REVIEWED BY THE CITY?S
 ATTORNEYS AS WELL AS REVIEW BY FAIR HOUSING, NOTE THIS
 DOCUMENT DOES HAVE TO BE RECORDED BY THE COUNTY CLERK.
  
 18) SHEET AN-9.4, DETAILS FOR EXPANSION JOINT
 MATERIALS, PLEASE PROVIDE MANUFACTURERS SPEC FOR FIRE
 RATING OF SLABS TABLE 601. 3HR FLOOR CONSTRUCTION, 1 HR
 REDUCTION FOR FIRE SPRINKLERS.
  
 19)SHEET AN-2.21: THIS COMMENT WILL BE FOR ALL
 FLOORS.
 19A) THIS SHEET DOES NOT IDENTIFY THE SECONDARY SLIDING
 GLASS DOORS LEADING TO THE UNIT BALCONIES. 106.1.2
 ADDITIONAL INFORMATION REQUIRED. PLEASE SEE DOOR
 SCHEDULE LOCATED ON SHEET AN-8.0.SLIDING GLASS DOORS
 NUMBERED 9 & 10 WILL REQUIRE A CLEAR MEASUREMENT OF 32?
 FAIR HOUSING ANSI A117.1-1998 404.2.3. CLEAR WIDTH.
  
 19B) PLEASE ALSO INDICATE COMPLIANCE WITH ANSI
 A117.1-98 SECTION 404.2.7 COMPLIANCE WITH DOOR HARDWARE
 FOR SLIDING GLASS DOORS.
  
 20) SHEET AN-2.23- AN-2.30 THE DOORS TO THE INTERIOR
 OF THE UNITS ARE NOT IDENTIFIED PER THE DOOR SCHEDULE.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2.FAIR HOUSING
 CHAPTER # 4.
  
 21) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 22) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 A) FIXED GLASS
 B) STOREFRONT
 C) CASEMENT WINDOWS
  
  
 D) MULLIONS- IF NOT PART OF THE PRODUCT APPROVAL
 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE
 DESIGNED TO TRANSFER THE DESIGN PRESSURE
 LOADS APPLIED BY THE WINDOW AND DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBSTRATE.
  
 1714.5.5.4 STRUCTURAL SAFETY FACTOR.
 MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF
 ONE-AND-ONE-HALF TIMES THE DESIGN
 PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR
 ASSEMBLIES TO BE SUPPORTED WITHOUT
 EXCEEDING THE APPROPRIATE MATERIAL STRESS LEVELS.
 IF TESTED BY AN APPROVED LABORATORY,
 THE ONE AND ONE-HALF TIMES THE DESIGN PRESSURE
 LOAD SHALL BE SUSTAINED FOR 10
 SECONDS, AND THE PERMANENT DEFORMATION SHALL NOT
 EXCEED 0.4 PERCENT OF THE MULLION
 SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN
 PRESSURE LOAD IS REMOVED.
  
 E) WALL LOUVERS
 F) GLAZED DOORS
 G) GLAZED DOORS WITH SIDELIGHTS
 H) SLIDING GLASS DOORS
 22I) EXTERIOR SWING METAL DOORS
 EXTERIOR DOOR ASSEMBLIES NOT COVERED BY SECTION
 1715.4.2 OR SECTION 1714.5.3.1
 SHALL BE TESTED FOR STRUCTURAL INTEGRITY IN
 ACCORDANCE WITH ASTM E 330 PROCEDURE A,
 AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN
 PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED
 FOR 10 SECONDS WITH NO PERMANENT DEFORMATION OF
 ANY MAIN FRAME OR PANEL MEMBER
 IN EXCESS OF 0.4 PERCENT OF ITS SPAN AFTER THE
 LOAD IS REMOVED. HIGH-VELOCITY HURRICANE
 ZONES SHALL COMPLY WITH TAS 202. AFTER EACH
 SPECIFIED LOADING, THERE SHALL BE NO
 GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS,
 HARDWARE PARTS, OR ANY OTHER
 DAMAGE WHICH CAUSES THE DOOR TO BE INOPERABLE.
 THE MINIMUM TEST SIZES AND MINIMUM DESIGN
 PRESSURES SHALL BE AS INDICATED IN
 TABLE 1714.5.3 .
 22J) EXTERIOR ROLL UP DOORS
 22K) ROOFING ASSEMBLIES:
 1) FLAT ROOFING SYSTEMS
 2)ROOFING TILE & UNDERLAYMENT?S
 PLEASE SUBMIT INFORMATION ON HOW THE
 RIDGE TILE ARE GOING TO BE SECURED TO THE
 ROOFING SYSTEM.1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION
 1609 OR IN ACCORDANCE WITH FRSA/RTI
 INSTALLATION MANUAL. 1507.3.8
 APPLICATION. TILE SHALL BE APPLIED ACCORDING TO THE
 MANUFACTURER?S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA/RTI 07320- 04.
 3) ROOFING FASTENERS- SPRAYED OR MECHANICAL
 4) PRE-ENGINEERED A/C STANDS
  
 23)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 24) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 25) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By dpalmer Date 2008-02-14 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2008-02-11 Time 11:32 Sent To  
Notes
2008-02-16 11:56:05NOTE ADDED:
  
 PLEASE SEE UNITS WHICH CONTAIN A NOTE FOR AN EF-2 YET
 THE PLANS DO NOT SHOW ANY EF-IN UNITS.
2008-02-14 19:17:572008-02-14 19:17:57
  
 *** DENIED***
  
 CANNES WEST PALM
  
 1) NOTE: PLEASE KNOW THIS PROJECT WAS ONLY SUBMITTED
 FOR PLAN REVIEW AND NOT FOR PERMIT. ONCE ALL REVIEW
 COMMENTS ARE ADDRESSED PLANS WILL STILL REMAIN IN *F*
 STATUS UNTIL PERMIT HAS BEEN APPLIED FOR.
 ONCE PERMIT IS APPLIED FOR, REVIEW FOR ITEMS SUCH AS
 LICENSING ETC WILL BE DONE AT THAT TIME.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON BOTH THE ELECTRICAL AS WELL AS THE
 ARCHITECTURAL COVER SHEETS. SOME OF THE FOLLOWING MAY
 ALREADY BE PRESENT HOWEVER SOME ARE NOT AT THIS TIME.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA72
 2002 NFPA-110
 2003 NFPA-20
  
 ** SOME OF THESE ARE ALREADY SHOWN BUT NOT ALL AND NOT
 ON ELECTRICAL PLANS.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT THE EDITION ADOPTED BY THE FBC 13-400.3.A.
 PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT COMPLY
 WITH THE FBC. MOST IMPORTANTLY THE ELECTRICAL LIGHTING
 ON PLANS DOES NOT CORRELATE THE CALCULATIONS. FOR THE
 REMAINDER OF THIS COMMENT THE INPUT DATA REPORT WILL BE
 NOTED AT IDR.
  
 A) ** PLEASE SEE THE LIGHTING FOR INTERIOR LIGHTING ON
 PLANS DOES NOT COORDINATE WITH THE IDR FOR THE NUMBER
 OF FIXTURES, THE TYPES OF FIXTURES OR THE WATTAGES OF
 FIXTURES. FOR EXAMPLE: THE IDR FOR INTERIOR SHOWS A
 TOTAL OF 8 LIGHT FIXTURES ON THE INTERIOR OF THE
 BUILDING. HOW IS THIS POSSIBLE WHEN THE PLANS SHOWS
 HUNDREDS AND HUNDREDS OF LIGHTS??
  
 B) ** PLEASE SEE THE IDR FOR EXTERIOR LIGHTING
 INFORMATION. THE IDR SHOWS ABSOLUTELY NO EXTERIOR
 LIGHTING FIGURED INTO THE CALCULATIONS. HOW IS THIS
 POSSIBLE WHEN THE PLANS SHOWS ONCE AGAIN HUNDREDS OF
 FIXTURES.
  
 THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEAS BE SURE
 THAT ALL LIGHTING ON PLANS COORDINATES WITH THE
 LIGHTING IN THE IDR SUBMITTED.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, 13-415.2.ABC.1.3
 ETC 13-415.1.A, 13-400.3.A ETC.
 PLEASE SEE METHOD SUBMITTED IS CURRENTLY IN QUESTION AS
 THE BUILDING CONTAINS *SHELL* PORTIONS WHICH ARE NOT
 KNOWN AT THIS TIME.
 PLEASE SEE 13-400.2.A.2 AS METHOD *A* MAY ONLY BE USED
 ONCE ALL ITEMS BEING INSTALLED ARE COMPLETED AND KNOWN.
 IF THERE ARE ITEMS NOT KNOWN BEING FUTURE, THEN THE
 ONLY OTHER CHOICE WOULD BE METHOD *B* FOR WHICH SECTION
 13-415.1.B, 13-400.3.B APPLIES.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY ALSO
 TOUCH ON THIS SAME TOPIC.
  
 4) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PLANS WITH
 MINIMUM REQUIRED CONTROLS FOR FBCCHAPTER 13,
 13-415.1.ABC.1.1, .1.2 , .1.3 AND .1.4.
 PLEASE KNOW BASED ON PLANS WHICH ONLY SHOW STANDARD
 SWITCHES WHICH ARE WHAT THE SYMBOL LEGEND STATES AND
 SHOWS NO LIGHTING CONTROLS WHICH ARE REQUIRED ARE IN
 THE DESIGN FOR THE BUILDING AT THIS TIME.
 PLEASE SEE PLANS DO CONTAIN A NOTE FOR SOME KIND OF
 J-BOX IN STAIR WAYS FOR LIGHTING CONTROLS HOWEVER NO
 SYSTEM OR PROPOSED ITEMS FOR DESIGN COULD BE LOCATED.
 PLEASE BE SURE TO SEE NOT ONLY CHAPTER 10 OF THE FBC
 FOR OCCUPANCY SENSING DEVICES PERMITTED ON EMERGENCY
 EGRESS LIGHTS BUT NFPA-101 7.8.1.2.2 AUTOMATIC, MOTION
 SENSOR'"TYPE LIGHTING SWITCHES SHALL BE PERMITTED
 WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH
 CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE
 ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE
 DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY
 OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING
 UNITS. PLEASE SEE NOTES BELOW WHICH WILL AFFECT EGRESS
 LIGHTING AS SHOWN.(FAIL SAFE ON)
 PLEASE KNOW AS THERE IS MUCH INFORMATION NOT SUBMITTED
 OR PART OF THE DESIGN, THERE MAY VERY WELL BE NEW
 COMMENTS ONCE PLANS ARE RESUBMITTED FOR THE NEXT
 REVIEW.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS SHOWS
 505 4TH STREET WHEN THE APPLIED LOCATIONS IS 510 4TH
 STREET. PLEASE BE SURE EACH BUILDING SET OF PLANS FOR
 EACH SEPARATE PERMIT CONTAINS THE CORRECT ADDRESS ON
 TITLE BLOCKS.
 FBC 106.5 ADMIN SECTION.
 FAC 61G1-16.004, FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE HOUSE BILL 7121 FOR REQUIRED
 ON-SITE FUEL FOR BACK UP OF A GENERATOR IN A
 RESIDENTIAL HIGH-RISE BUILDING.
 PLEASE KNOW THAT BESIDES THE REQUIRED ITEMS PER NEW
 STATE STATUTES, PLEASE BE AWARE THAT IF THE BUILDING IS
 GOING TO BE OCCUPIED UNDER THE POWER OF THE GENERATOR
 ONLY, OTHER SYSTEMS SUCH AS VENTILATION ETC WILL NEED
 TO BE PART OF THE DESIGN OF FUEL CONSUMPTION ALONG WITH
 ALL OTHER LIFE SAFETY SYSTEMS.
 THIS WILL NEED TO BE GONE OVER ON THE PHONE OR IN
 PERSON TO CLARIFY WHAT IS REALLY NEEDED.
  
 7) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS. THE GENERATOR, FUEL
 TANK(S), FIRE PUMP, FIRE PUMP CONTROLLER AND BOTH MTS
 AND ATS DEVICES.
 THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME.
 NEC 90.7, 110.3, NFPA-20, NFPA-110 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE THE GENERATOR AS SHOWN ON PLANS
 DOES INDICATE THE PRIME-MOVER OR FUEL SOURCE? PLEASE
 SEE NFPA-110, NFPA-70
 THERE ARE TOO MANY CODE SECTIONS TO LIST FOR REQUIRED
 ITEMS.
 PLEASE SEE NFPA-110 FOR LOCATION OF THE REQUIRED
 GENERATOR.
 PLEASE SEE THAT ALL ITEMS SHALL MEET ALL CHAPTERS
 HOWEVER MORE SPECIFIC PER THIS REVIEW CHAPTER 7. PLEASE
 SEE VENTILATION, LIGHTING LEVELS, LOCATION OF EQUIPMENT
 ETC.
 MAY NOT TAKE THE VENTILATION FROM ADJACENT ROOMS, MUST
 COME DIRECTLY FROM OUTSIDE.
 PLEASE KNOW THERE ARE TOO MANY CODE SECTIONS TO NOTE AT
 THIS TIME.7.1, 7.2, 7.3, 7.4, 7.5 ETC
 PLEASE SEE THAT THE MINIMUM LIGHTING LEVELS SHALL MEET
 30FT CANDLES. THIS WILL BE NOTED IN NOTE BELOW FOR
 PHOTO-METRICS LEVELS.
 PLEASE SEE 700.12B (1), (3), 701.11B(1),(3) , ETC
  
 9) NOTE: PLEASE SEE SOME A-SHEETS WHICH CONTAIN HAND
 DRAWN ITEMS WHICH CAN NOT BE MADE TO SIGNED AND SEALED
 PLANS.
 FS 481.221, 471.023
 THIS COMMENT IS NOTED FOR ALL PLANS AND FOR ALL
 REVIEWS.
  
 10) NOTE: PLEASE SEE MISSING RATED SEPARATION WHICH
 WILL BE A PART OF BUILDING SEPARATION. PLEASE ALSO KNOW
 THE ELECTRICAL SYSTEMS ON EACH SIDE OF THIS PROPOSED
 WALL AND FIRE RATED DOORS SHALL BE SEPARATED. PLEASE
 SEE THE LOCATION OF THE MAIN ELECTRICAL ROOM AS SHOWN
 IS NOT ACCEPTABLE TO THIS AHJ. THIS CREATES A MAJOR
 LIFE SAFETY HAZARD. EMERGENCY PERSONNEL DO NOT HAVE
 DIRECT AND IMMEDIATE ACCESS TO THE MAIN ELECTRICAL
 ROOM. THE LOCATION SHALL BE AT A NEAREST POINT OF
 ENTRANCE INTO THE BUILDING. . THE LOCATION WILL NEED TO
 BE DETERMINED BEFORE RESUBMITTED PLANS. SOME ITEMS WERE
 ALREADY GONE OVER WITH THE ELECTRICAL ENGINEER AFTER
 PLANS WERE SUBMITTED.
 230.2, 230.70, 230.71, 230.72 ETC
  
 11) NOTE: PLEASE SEE NEC 230.2 AND NFPA-110 FOR THE
 ACCEPTABLE LOCATION OF EPSS EQUIPMENT.
 PLEASE SEE NFPA-1107.2.2, 7.1.5, 7.2.1 ETC WHICH DOES
 NOT PERMIT THIS EQUIPMENT IN THE SAME ROOM AS THE
 NORMAL ELECTRICAL EQUIPMENT. PLEASE SEE 7.2.2.1 WHICH
 DOES ALLOW THE ATS/ TRANSFER EQUIPMENT IN THE SAME ROOM
 AS LONG AS TWICE THE DISTANCES FROM OTHER EQUIPMENT PER
 110.26 IS PROVIDED. PLEASE SEE THE NEC WHICH STATES
 THIS EQUIPMENT SHALL BE SUFFICIENTLY REMOTE.NFPA-70
 DOES NOT GIVE A DEFINITION FOR WHAT SUFFICIENTLY REMOTE
 IS HOWEVER NFPA-110 DOES PROVIDEDEFINITION OF LEVEL 1
 OR LEVEL 2 SYSTEMS NOT TO BE LOCATE WITH IN THE SAME
 ROOM.
 PLEASE RE-LOCATE.
  
 12) NOTE: PLEASE SEE MISSING INFORMATION FOR THE FIRE
 PUMP. PLEASE SEE NFPA-20CHAPTERS AND NFPA-70. MORE
 SPECIFIC PLEASE SEE CHAPTERS 9 AND 10 OF NFPA-20 AND
 NEC 695 FOR FIRE PUMPS.
 COULD NOT LOCATE INFORMATION ON REQUIRED LOCKED ROTOR
 CURRENT SETTINGS WHICH NEEDS TO BE SHOWN ON PLANS.
 COULD NOT LOCATE INFORMATION ON ISOLATION SWITCH(S),
 BY-PASS, ETC
 COULD NOT LOCATE THE MINIMUM REQUIRE ON-SITE FUEL FOR A
 MINIMUM OF 8HRS OF RUN TIME AT 100%. PLEASE BE SURE TO
 SEE NOTES ABOVE WITH RESPECT TO THE ALLOWANCE FOR HOUSE
 BILL 7121. IF BUILDING IS UNDER OCCUPANCY FOR THE
 PERIOD AS SPECIFIED THEN PLEASE SEE THAT THE FIRE PUMP
 SHALL HAVE THE REMAINDER OF ON-SITE FUEL FOR ANY GIVEN
 TIME DURING OCCUPANCY.
  
 13) NOTE: PLEASE SEE NFPA-1107.1.5 AND NFPA-70
 CHAPTERS 700 AND 701 WHICH DOES PERMIT OPTIONAL
 STAND-BY EQUIPMENT BEING FED FROM THE GENERATOR WHICH
 ALSO FEEDS LIFE SAFETY AND LEGALLY REQUIRED LOADS
 HOWEVER NO PROVISIONS FOR LOAD SHEDDING WAS INDICATED
 ON PLANS.
 PLEASE KNOW AT THIS TIME BASED ON THE PLANS, AND OTHER
 REQUIRED SYSTEMS THE GENERATOR IS NOT OF SUFFICIENT
 SIZE FOR ALL REQUIRED SYSTEMS.
 PLEASE ALSO PROVIDE LOAD SHEDDING DETAIL FOR THE UNITS
 MTS PANELS WHICH ARE FED FROM EU-2.
 PLEASE KNOW AS THERE ARE SEVERAL CHANGES NEEDED MANY
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 14) NOTE: PLEASE SEE GENERATOR ROOM WALL DETAIL ON
 EN-6.0 DOES NOT COORDINATE WITH OTHER SHEERS IN PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 15) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE FOR EXAMPLE: EN-2.0 ,
 2.1 ETC WHICH SHOW AREAS/ROOMS HOWEVER DO NOT INDICATE
 ANY DESIGNATIONS.
 THIS IS FOR MANY LOCATIONS ON PLANS HOWEVER NOT ALL ARE
 LISTED.
 PLEASE ALSO BE SURE TO COMPLETE THE SAME FOR UNITS.
 SOME OF THE UNITS IN THE BEGINNING OF UNIT PLANS DO
 INDICATE DESIGNATIONS HOWEVER AS THE UNIT SHEETS GO ON
 THE AREAS AND ROOMS WERE NOT ON SHEETS.
 PLEASE KNOW THAT ARE CODE SECTIONS WHICH APPLY TO UNITS
 WHICH CAN NOT BE CONFIRMED AT THIS TIME SUCH AS
 210.52B1 FOR CIRCUITING OF ITEMS IN DINING AREAS.
 (COMMENTED BELOW).
  
 16) NOTE: PLEASE SEE FAIR HOUSING ACT REGULATIONS 24
 CFR, 100.205 AND FBC CHAPTER 11 FOR REQUIRED HEIGHTS
 AND LOCATIONS FOR DEVICES.
 PLEASE LIST ON PLANS.
  
 17) NOTE: PLEASE BE SURE TO PROVIDE ANY INFORMATION FOR
 ANY ACCESS CONTROL SYSTEMS SUCH AS PARKING GARAGE GATE
 OPERATORS AND BATTERY BACK UP.
 PLEASE ALSO PROVIDE INFORMATION ON ANY ACCESS CONTROLS
 OF INGRESS OR EGRESS DOORS. PLEASE SEE NFPA-101 7.5.1,
 7.5.2, 7.5.4. AT THIS TIME THERE IS NOT ENOUGH
 INFORMATION SHOWN.
 NO DEVICES ARE TO BE INSTALLED WHICH IN THE EVENT OF
 ANY EMERGENCY OR NON EMERGENCY WILL IMPEDE THE EGRESS
 OF OCCUPANTS OR FIRE DEPARTMENT PERSONNEL IN ANY WAY.
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS FROM FIRE
 MARSHAL.
  
 18) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 THIS IS INCLUSIVE OF STAIR WAYS ETC.
 PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES
 A MINIMUM OF 10FT CANDLES UNDER NORMAL AND IS PERMITTED
 DOWN TO 1FT CANDLE UNDER EMERGENCY.
  
 19) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE GENERATOR
 ROOM AS NFPA-110 7.3.3 REQUIRES 30FT CANDLES MINIMUM.
  
 20) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ELEVATOR PITS
 FOR THE MINIMUM OF 5FT CANDLES REQUIRED PER ASME
 A17.1-2004, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
 LEVELS ARE AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO
 BE EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
 21) NOTE: PLEASE KNOW THAT BATTERY BACK UP LIGHTING
 FIXTURES WILL BE REQUIRED FOR ALL EGRESS PATHS
 INCLUDING STAIRS TO PROVIDE THE 1FT CANDLE MINIMUM.
 PLEASE ALSO INCLUDE BATTERY BACK UP FIXTURES IN THE
 FOLLOWING ROOMS.
 FIRE COMMAND ROOM
 MAIN ELECTRICAL ROOM (LOCATION YET TO BE DETERMINED)
 GENERATOR ROOM
 FIRE PUMP ROOM
 ALL ELEVATOR MACHINE ROOMS
 FUTURE RETAIL AREAS
 EPSS ROOM (TO BE SHOWN OR PART OF POSSIBLE DESIGN AS
 NOTED ABOVE).
 ** SOME OF THESE ARE ALREADY SHOWN ON PLANS BUT NOT
 ALL.
 NFPA-700.12F, 700.16, NFPA-7.8 AND 7.9.
  
 22) NOTE: PLEASE LIST ALL ITEMS IN FIRE COMMAND ROOM AS
 REQUIRED PER NFPA-101 11.8.5. PLEASE INDICATE NOTES FOR
 MAPPING OF BUILDINGS ELECTRICAL SYSTEM AND EMERGENCY
 SYSTEMS LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 23) NOTE: PLEASE SEE AREAS SUCH AS FUTURE RETAIL AREAS
 SHALL INCLUDE LIGHTING CONTROLS PER 13-415.1.ABC.1.1,
 .1.2.
  
 24) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AT MANY
 LOCATIONS. PLEASE SEE RETAIL METERS FROM GUTTER FOR
 EXAMPLE WHICH IS AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE INDICATE ON THE RISER FLOATING NEUTRAL KITS
 WHICH WILL BE REQUIRED.
 PLEASE SEE 250.6, 250.24, 250.110, 250.122
  
 25) NOTE: PLEASE SEE ALL OTHER CONDUITS SHALL CONTAIN
 AN EQUIPMENT GROUNDING CONDUCTORS IN CONDUITS AFTER THE
 FIRST MEANS OF DISCONNECT. THE PLANS DO CONTAIN NOTES
 FOR SOME BUT NOT FOR ALL. PLANS ALSO MENTIONS ONLY IF
 PVC.
 PLEASE KNOW ANY METALLIC CONDUIT PATHS SHALL USE
 CONNECTORS WHICH ARE LISTED AS AN APPROVED *EQUIPMENT
 GROUNDING PATH*. THESE CONNECTORS, COUPLINGS ETC SHALL
 CONTAIN A LISTED APPROVED FOR SUCH USE BY A NRTL.
 (NATIONALLY RECOGNIZED TESTING LABORATORY.
 110.3, 250.110, 250.122.
  
 26) NOTE: PLEASE PROVIDE THROUGH FLOOR CURBING DETAILS
 FOR BUS-DUCT PER 368.10 ( C ) ALL.
  
 27). PLEASE PROVIDE WALL AND FLOOR FIRE RATED
 PENETRATION DETAILS ON ELECTRICAL PLANS PER NEC 300.21
 AND NFPA 221, SECTION 4.2, PENETRATION SEALS, STATES
 THE FOLLOWING:
 ALL THROUGH-PENETRATION PROTECTION SYSTEMS SHALL BE
 TESTED AND RATED IN ACCORDANCE WITH ASTM E 814,
 STANDARD TEST METHOD FOR FIRE TESTS OF
 THROUGH-PENETRATION FIRE STOPS, OR ANSI/UL 1479, FIRE
 TEST OF THROUGH-PENETRATION FIRE STOPS. THE POSITIVE
 PRESSURE DIFFERENCE BETWEEN THE EXPOSED AND UNEXPOSED
 SURFACES OF THE TEST ASSEMBLY SHALL NOT BE LESS THAN
 0.01 IN. (2.5 PA) WATER GAUGE. A THROUGH-PENETRATION
 PROTECTION SYSTEM SHALL HAVE AN F RATING NOT LESS THAN
 THE REQUIRED FIRE RESISTANCE RATING OF THE FIRE WALL OR
 FIRE BARRIER WALL. ANSI/UL 1479 /ASTM E 814-02.
  
 28) NOTE: PLEASE SEE PLANS AS SOME SHEETS CONTAINS
 NOTES WHICH ARE TOO SMALL TO READ. PLEASE SEE SHEETS
 EN-2.2 AND 2.3 FOR EXAMPLE. THERE ARE OTHER SHEETS ALSO
 HOWEVER ONLY A COUPLE IS NOTED.
  
 29) NOTE: PLEASE SEE MISSING GROUND LEVEL
 PHOTO-METRICS.
 PLEASE ALSO SUBMIT COMPLETED PHOTO-METRICS FOR POOL
 AREA FOR ANY PROPOSED AFTER DUSK TO DAWN SWIMMING.
 PLEASE KNOW THAT ANY PHOTO-METRICS FOR ANY PROPOSED
 AFTER DUSK AND BEFORE DAWN SWIMMING WILL BE REQUIRED TO
 BE STAMPED BY THE PALM BEACH COUNTY HEALTH DEPARTMENT.
 POOL WILL BE UNDER A SEPARATE PERMIT AND REGULAR PLANS
 FOR ACTUAL POOL WILL ALSO HAVE PLANS STAMPED AT A LATER
 DATE.
 AS LIGHTING FOR POOL AREAS ARE UNDER THIS REVIEW THIS
 WOULD BE NEEDED AT THIS TIME.
  
 30) NOTE: PLEASE PLACE DISTANCES/NOTES ON PLANS FOR
 REQUIRED CLEARANCES OF LIGHT FIXTURES AROUND POOL AREA.
 PLEASE SEE 680.22/23 AND MOST IMPORTANTLY 411.4B WHICH
 REQUIRES 10FT MINIMUM.
  
 31) NOTE: PLEASE PLACE NOTE ON ROOF TOP PLANS. ANY
 PROPOSED LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED
 PER NFPA-780. OR WORDS TO THAT AFFECT.
 PLEASE BE AWARE THAT NON-ACCEPTABLE SYSTEMS SUCH AS
 ESE, CTSARE NOT PERMITTED.
  
 32) NOTE: PLEASE KNOW THE MANUFACTURES SPECS/CUT SHEETS
 FOR THE PROPOSED SAUNA WILL BE NEEDED TO BE SUBMITTED
 FOR REVIEW.
 PLEASE BE AWARE UNIT IS REQUIRED TO BE LISTED BY A
 NRTL.
 110.3
  
 33) NOTE: PLEASE CORRELATE THE ELECTRICAL PLANS WITH
 THE PLUMBING PLANS FOR THE PROPOSED INSTA-HOT WATER
 HEATER UNITS.
 PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION, BRANCH
 CIRCUIT, WIRING ETC SHALL MEET 422.11. IF STORAGE TYPE,
 422.13.
 PLEASE SEE UNIT PANEL SCHEDULES AS THE OVER CURRENT
 PROTECTION AND BRANCH CIRCUITS EXCEED THE RATING OF THE
 BRANCH CIRCUIT PROVIDED.
 PLEASE SE LOAD IS SHOWN AT 8300 VA AND THE CIRCUIT IS
 ONLY 30AMPS WITH #10 AWG.
 PLEASE BE SURE TO SEE THE MINIMUM AND MAXIMUM RATINGS
 PER THE MANUFACTURES RECOMMENDATIONS STATED ON SPECS
 PRINTED ON PLUMBING SHEETS.
 240.4, 310.16, 110.3, 90.7 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 34) NOTE: PLANS SHOWS THE LOCATION OF THIS HEATING UNIT
 FOR HOT WATER BEING LOCATED UNDER THE SINK AND IN CLOSE
 PROXIMITY OF STORAGE OF COMBUSTIBLES WHICH IS NOT
 PERMITTED PER 422.17.
  
 35) NOTE: PLEASE ALSO KNOW THAT ANY PROPOSED DISCONNECT
 WHICH CONTAINS OVER CURRENT PROTECTION SHALL MEET
 110.26 FOR MINIMUM CLEARANCES. (INCLUDING WATER HEATING
 UNIT).
  
 36) NOTE: PLEASE SEE PLANS WHICH SHOWS SMOKE DETECTORS
 INSTEAD OF SMOKE ALARMS. PLEASE SEE NFPA-72 DEFINITIONS
 AS A SMOKE DETECTOR ONLY DETECTS AND DOES NOT SOUND AN
 ALARM WHEREAS A SMOKE ALARM NOT ONLY DETECTS BUT ALSO
 SOUNDS AN ALARM.
 IF THESE ARE INDEED SMOKE DETECTORS PLEASE COMPLETE
 PLANS WITH FIRE ALARM PANEL, SYSTEM AND HORN DEVICES IN
 EACH UNIT. IF THESE ARE SMOKE ALARMS PLEAS ADJUST ALL
 DESIGNATIONS ON PLANS.
  
 37) NOTE: PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3
 WHICH REQUIRES THESE SMOKE DETECTION DEVICES TO BE
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE SEE THE SECTION ABOVE FOR INSTALLATION LOCATIONS
 AS THIS REQUIRES A MINIMUM OF 3FT FROM BATH ROOM DOORS.
 THIS SAME SECTION ALSO REQUIRES 20FT FROM COOKING
 APPLIANCES UNLESS MEETING EXCEPTIONS OF A PARTICULAR
 UNIT.
 PLEASE NOT ONLY ADJUST MANY LOCATIONS ON PLANS, BUT
 ALSO ADD SOME MISSING AND ADJUST SPECIFIED DEVICES FOR
 DEVICES LOCATED WITHIN 20FT.
 PLEASE SEE SOME UNITS NOTED FOR EXAMPLE: UNIT M AND
 OTHERS ALSO.
  
 38) NOTE: PLEASE GO OVER PLANS AND RISER FOR
 COORDINATION OF THE SIZING OF PANELS.
 PLEASE SEE SOME WHICH ARE IN NEED OF ADJUSTING. FOR
 EXAMPLE: RISER SHOWS PANELS *M* AS 125AMP AND PANEL *M*
 IS SHOWN AS 150AMP ON SCHEDULE.
 FBC 106.1.23 FOR COORDINATION.
  
 39) NOTE: PLEASE SEE 210.52C1 FOR KITCHEN COUNTER
 SPACES FOR 12INCHES OR MORE OF COUNTER.
 PLEASE SEE MANY UNITS APPEAR TO SCALE 12INCHES OR MORE
 AND SOME ARE IN QUESTION.
 PLEASE SEE UNITS FOR EXAMPLE: B, C, D, A ETC PLEASE BE
 SURE TO SEE 210.8A6 FOR ANY REQUIRED GFI PROTECTION.
  
 40) NOTE: PLEASE COORDINATE ALL CIRCUITING IN UNITS
 WITH PANEL SCHEDULES. FOR EXAMPLE: PLEASE SEE UNIT *B*
 WHICH SHOWS CIRCUIT #16 TO MASTER BEDROOM HOWEVER
 ACTUALLY SHOWS FEEDING OTHER BEDROOM ON PLANS. PLEASE
 SEE FOR EXAMPLE: COMPLETE CIRCUITING FOR ALL IS
 REQUIRED INCLUDING ITEMS SUCH AS LIGHTING IN BEDROOM IN
 UNIT B WHICH IS MISSING CIRCUIT.
 UNIT K, AND OTHERS.
 FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 41) NOTE: PLEASE SEE THERE ARE SEVERAL LOCATIONS IN
 UNITS WHICH THE DINING, BREAKFAST AREAS AND AREAS OF
 THE LIKE CONTAIN CIRCUITS TO RECEPTACLES WHICH ARE NOT
 APART OF THE ONE OR MORE SMALL APPLIANCE CIRCUITS AS
 REQUIRED PER 210.52B1, 210.11C1, 220.52.
 PLEASE SEE UNIT K, UNIT M FOR A COUPLE OF EXAMPLES;
 THESE ARE NOT ALL.
 ** PLEASE SEE SOME OF THE RECEPTACLES IN THESE AREAS
 ARE BEING SHOWN ON THE GENERAL LIGHTING CIRCUIT
 PROVIDED BY THE MTS PANEL WHICH IS NOT PERMITTED UNLESS
 IT BECOMES ONE OF THE SMALL APPLIANCE CIRCUITS. THIS
 WOULD REQUIRE 1500VA PER CIRCUIT ETC.
  
 42) NOTE: PLEASE SEE DINING AREA WHICH CONTAINS A
 LAUNDRY ROOM RECEPTACLE AND CIRCUIT. PLEASE SEE
 210.11C2 WHICH DOES NOT PERMIT THIS.
 PLEASE SEE UNIT Q FOR ONE EXAMPLE.
  
 43) NOTE: PLEASE SEE 210.52 FOR SOME RECEPTACLES
 MISSING FOR 2FT OF WALL SPACE. MOST RECEPTACLES MEET
 210.52 AND THERE ARE ONLY A FEW MISSING.
 PLEASE SEE UNIT P FOR EXAMPLE AT DOOR. (REDLINED ON
 PLANS).
  
 44) NOTE: PLEASE SEE THE BRANCH CIRCUIT ON MTS PANEL
 WHICH IN SOME UNITS IS SHOWN FEEDING LIGHTING OUTLETS
 OR OTHER DEVICES IN SLEEPING AREAS ARE REQUIRED TO ARC
 FAULT PER 210.12.
 FOR EXAMPLE: UNIT M.
  
 45) NOTE: PLEASE SEE LOAD ON E2 IS MORE THAN THE RATED
 LOAD OF GENERATOR.
 PLEASE SEE SIZING OF EQUIPMENT PER 220.
  
 46) NOTE: PLEASE SEE NOTE ON ELECTRICAL RISER 8TH LEVEL
 WEST RISER WHICH SHOWS 1-125AMP AND 2-150AMP? WHAT ARE
 THESE FOR ?
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 47) NOTE: PLEASE CONFIRM THE NUMBER OF CIRCUITS SHOWN
 ON UNIT PANELS WHICH SHOWS THESE AS 32 CIRCUIT PANELS.
 PLEASE SUBMIT SPEC/CUT SHEET FOR PANELS.
 110.3, 90.7
 FBC 106.1.2
  
 48) NOTE:PLEASE BE SURE TO SPECIFY FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50
  
 49) NOTE: PLEASE SEE PANEL H2 IS NOT ON RISER AT
 MEZZANINE AS LISTED ON PANEL SCHEDULE.
 FBC 106.1.2 FOR COORDINATION.
  
 50) NOTE: PLEASE SEE RISER SHOWS 400AMP OVER CURRENT
 PROTECTION AND RISER UP TO EE AN EW PANELS YET NO
 INFORMATION WAS SHOWN ON HOW THESE WILL BE TAPPED OR
 CONNECTED.
 PLEASE SEE 240.4, 310.16, 240.21 AS THE TAPPED
 CONDUCTORS AS SHOWN ON FEEDER LEGEND AS #3 ARE NOT
 RATED FOR THE 125AMP BREAKER AT TERMINATION.
  
 51) NOTE: PLEASE KNOW IT HAS COME TO OUR ATTENTION THAT
 THE PROPOSED PROJECT IS GOING FOR A LEED
 CERTIFICATION.
 PLEASE BE SURE TO PROVIDE INFORMATION AND ALL NOTES
 ABOVE WITH RESPECT TO FBC AND CHAPTER 13.
  
 52) NOTE: PLEASE KNOW ONE SET OF ELECTRICAL PLANS
 CONTAINS MANY OF THE ABOVE ITEMS REDLINED HOWEVER NOT
 ALL.
 PLEASE ALSO KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW AND DUE TO THE FACT THERE WILL BE
 CHANGES TO PLANS THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 53) NOTE: PLEASE KNOW AS THIS A THRESHOLD PROJECT,
 THREE SETS OF PLANS, AND ALL SUPPORTING DOCUMENTS ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW AND STAMPING.
  
 **
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-13 11:33:17 
  
 ONE ROLL IN ELECTRIC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By rchokshi Date 2008-03-18 Time 10:32 Rev Time 0.00
Received By rchokshi Date 2008-03-18 Time 10:21 Sent To  
Notes
2008-03-18 10:32:02FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE PROVIDE WATER QUALITY CALCULATIONS.PLEASE
 SHOW ON CALCULATION THAT YOU HAVE CONSIDERED FLOOD ZONE
 AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA AND CROWN OF
 THE ROAD WHEN YOU DETERMINE THE FIRST FLOOR ELEVATION.
 FIRST FLOOR ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER
 THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVE.
  
 ABOVE COMMENTS ARE ALMOST SIMILAR WE MADE IN PERMIT #
 07090838.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By mawillia Date 2008-04-16 Time 18:14 Rev Time 0.00
Received By mawillia Date 2008-04-16 Time 17:45 Sent To  
Notes
2008-04-16 18:14:10*****DENIED*****
  
  
 01.THE ADDRESS SHOWN IN THE TITLE BLOCK OF EACH PLAN
 SHEET OF 505 4TH STREET DOES NOT CORRELATE WITH THE
 ADDRESS OF 510 4TH STREET WHICH REGISTERS IN THE
 COMMUNITY PLUS SYSTEM.VERIFY/CONFIRM/AMEND WITH A
 PERMIT SPECIALIST TO MAKE SURE THE CORRECT PROJECT SITE
 ADDRESS IS APPLIED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SURROUNDING PROPERTIES
 OR VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 04.STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 05.ALL CUTTING AND WELDING OPERATIONS SHALL COMPLY
 WITH NFPA 51B.
  
 06. TEMPORARY STANDPIPE SYSTEM REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 07.ON SHEET G-1.3, THEREARE SEVERAL REFERENCES TO
 THE CITY OF MIAMI;PLEASE BE ADVISED THAT THE
 AUTHORITY HAVING JURISDICTION (AHJ) IS THE CITY OF WEST
 PALM BEACH.
  
 08.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 4TH STREET, DISPLAY/SHOW THE ACTUAL NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, NUMBERS
 SHALL BE A MINUMUM OF 6" IN HEIGHT AND A MINUMUM OF 1"
 IN WIDTH.
  
 09.KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX.FOR AN APPLICATION,
 CONTACT WEST PALM BEACH FIRE PREVENTION AT
 561-804-4724.
  
 10.STAIRWELL IDENTIFICATION SIGNS ARE REQUIRED
 IDENTIFYING FLOOR LEVEL, STAIR IDENTITY, AND TERMINUS
 TOP AND BOTTOM.
  
 11.ELEVATOR WARNING SIGNS " IN CASE OF FIRE, DO NOT
 USE THE ELEVATORS "ARE REQUIRED.
  
 12.ALL TRASH CHUTES ARE TO COMPLY WITH NFPA 82.
  
 13.FIRE DOORS AND FIRE WINDOWS ARE TO COMPLY WITH
 NFPA 80.
  
 14.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE
 EXITS, EXIT ACCESS CORRIDORS, AND OTHER AREAS IN TERMS
 OF CLASS A, CLASS B, OR CLASS C.LIKEWISE, SPECIFY THE
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II
 FOR THESE AREAS.
  
 15.ON SHEET LSN-1.1, THE FIRE EXTINGUISHER IN THE
 RESIDENT BICYCLE STORAGE AREA APPEARS TO BE LOCATED IN
 THE BIKE RACKS.(SEE APPROXIMATE AREA C-4)
  
 16.ON SHEET LSN-1.2 AND LSN-1.3, THE PATH OF EGRESS
 (TRAVEL DISTANCE ROUTE) IS SHOWN TO PASS THROUGH A
 VEHICLE PARKING STALL. THE PATH OF TRAVEL SHALL NOT BE
 THROUGH AN OBSTRUCTION OR POSSIBLE OBSTRUCTION.
  
 17.ON PLAN SHEETS EN-2.3 THRU EN-2.7, LIST THE UNIT
 TYPE SO THAT THE PLANS EXAMINER AND/OR FIELD INSPECTOR
 CAN IDENTIFY WHICH LAYOUTIS BEING REFERENCED ON
 EN-3.0 THRU EN-3.6 SHEETS.
  
 18.ON SHEET EN2.7, WORDING IN THE NOTE NOT CLEAR.
 (SEE APPROXIMATE AREA C.5 / 3.5)
  
 19.SMOKE DETECTORS (SD) ARE SHOWN IN THE RESIDENTIAL
 UNITS ON SHEETS EN-3.0 THRU EN-3.6;AMEND THESE DEVICE
 TO SMOKE ALARMS (SA).PLEASE BE ADVISED THAT SD'S ARE
 TIED INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SA'S
 ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY.
  
 20.CORRELATE THE INFORMATION IN THE INDEX OF DRAWING.
 SHEET G1.0 LISTS LSN-1.5 AS LIFE SAFETY PLAN (4TH TO
 6TH LEVEL) ;WHEREAS IT IS TITLED ON SHEET LSN-1.5 AS
 LIFE SAFETY PLAN (3 - 6 LEVEL) .
  
 21.COULD NOT FIND SHEET LSN-1.8 AND LSN-1.9 AS
 INDICATED IN THE INDEX OF DRAWING (SHEET G1.0) .
  
 22.IN THE SEQUENCE OF OPERATIONS FOR THE FIRE ALARM
 SYSTEM (SHEET FAN-1.0) , AMEND TO SHOW AS PER LOCAL
 CODES THAT "DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM" .
  
 23.FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 24.ARE HEAT DETECTORS SLATED FOR THE KITCHEN AREA IN
 THE DWELLING UNITS?
  
 25.SHEET FAN-2.7 IS INCORRECTLY TITLED AS ELECTRICAL
 PLAN (8TH FLOOR);SHOULD BE FIRE ALARM PLAN (8TH
 FLOOR) AS INDICATED IN THE INDEX OF DRAWINGS (SHEET
 G-1.0) .
  
 26.THE INDEX OF DRAWINGS (SHEET G-1.0) LISTS FAN-2.8
 AS FIRE ALARM PLAN (3RD FLOOR) WHEREAS THE SHEET ITSELF
 IS TITLED AS FIRE ALARM PLAN (ROOF LEVEL) .
  
 27.CORRELATE SHEET FAN-2.9 IN THE INDEX OF DRAWING
 WITH THE INFORMATION ON THE ACTUAL SHEET.
  
 28.ELECTRONIC SWITCHES, CHAIN AND LOCK REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 29.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 BOTH THE FIRE ALARM AND THE FIRE SPRINKLER SYSTEMS AND
 ANY ACCESS CONTROL SYSTEMS.
  
 30.NFPA 13 - 2002 EDITION - SHALL BE REFERENCED FOR
 THE INSTALLATION OF THE BUILDING'S FIRE SPRINKLER
 SYSTEM.IT WAS INDICATED IN ONE OF THE PLAN SHEET THAT
 NFPA 13R WOULD BE REFERENCED;PLEASE BE ADVISED THAT
 NFPA 13R IS THE STANDARD FOR THE INSTALLATION OF
 SPRINKLER SYSTEM IN RESIDENTIAL OCCUPANCIES UP TO AND
 INCLUDING 4 STORIES IN HEIGHT.
  
 31.ON SHEET FPN-0.0, AMEND NOTE #14 THAT "WATER FLOW
 DEVICES SHALL INITIATE A GENERAL FIRE ALARM.
  
 32.FIRE SPRINKLER SYSTEM WILL BE MONITORED.
  
 33.EXPLAIN TERMINOLOGY (AND PURPOSE) OF FLOOR CONTROL
 RIG (FCR);FCR IS NOT SHOWN IN THE ABBREVIATIONS SND
 SYMBOLS LEGEND ON THE FPN-0.0 SHEET.
  
 34.KNOX LOCKING CAPS REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTIONS (FDC).CONTACT WEST PALM BEACH FIRE
 PREVENTION AT 561-804-4724 FOR AN APPLICATION.
  
 35.ON PLAN SHEETS FPN-2.3 THRU FPN-2.7, LIST THE UNIT
 TYPE SO THAT THE PLAN REVIEWER AND/OR FIELD INSPECTOR
 CAN IDENTIFY WHICH FIRE SPRINKLER LAYOUT IS BEING
 REFERENCED ON FPN-3.00 THRU FPN-3.02 SHEETS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2008-01-25 Time 09:18 Sent To  
Notes
2008-01-25 09:22:13TO "COMM" BD#20/PLANS ON RACK--2 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-28 Cont ID  
Sent By rregueir Date 2008-04-28 Time 18:13 Rev Time 0.00
Received By rregueir Date 2008-03-29 Time 18:29 Sent To PC
Notes
2008-04-28 18:13:33REVIEW #: 1ST. PLAN CHECK ONLY
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG MN-00: THE MECHANICAL SEQUENCE OF OPERATIONS
 PARTS I, II AND III CONTAIN SEVERAL GRAMMATICAL AND
 PUNCTUATION ERRORS WHICH MAKE THE INTENT AND DESIGN OF
 THE SEQUENCE UNCLEAR. THE SEQUENCE CAN NOT BE REVIEWED
 AT THIS TIME. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE
 SUFFICIENT INFORMATION AND DETAIL TO ADEQUATELY
 DESCRIBE THE ELEMENTS OF THE DESIGN NECESSARY FOR THE
 PROPER IMPLEMENTATION OF THE SMOKE CONTROL SYSTEMS.
 THESE DOCUMENTS SHALL BE ACCOMPANIED BY SUFFICIENT
 INFORMATION AND ANALYSIS TO DEMONSTRATE COMPLIANCE WITH
 THESE PROVISIONS IN ACCORDANCE WITH FBCB 513.2. PLEASE
 CLARIFY THE SEQUENCE IN A MANNER THAT CLEARLY
 DELINEATES THE DESIGN INTENT AND RESUBMIT FOR REVIEW.
 NOTE: INTERIOR EXIT STAIRWAYS ARE PRESSURIZED TO A
 MINIMUM OF 0.15 INCH OF WATER AND A MAXIMUM OF 0.35
 INCH OF WATER IN THE SHAFT RELATIVE TO THE BUILDING
 MEASURED WITH ALL STAIRWAY DOORS CLOSED UNDER MAXIMUM
 ANTICIPATED STACK PRESSURES IN ACCORDANCE WITH FBCB
 909.20.5.
  
 2. PG MN-00: THE TEST CRITERIA FOR SMOKE CONTROL NOTE
 #9, COMMISSIONING OF THE SMOKE CONTROL SYSTEM SHALL BE
 IN ACCORDANCE WITH FBCM 513.3 AND FBCB 909.18.8.
  
 3. PG MN-00: THE RATIONAL ANALYSIS DOES NOT CONTAIN ANY
 ANALYSIS. IT IS A SERIES OF STATEMENTS. A RATIONAL
 ANALYSIS SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS
 TO BE EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS
 SUPPORTING THEM, AND THE METHODS OF CONSTRUCTION TO BE
 UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION
 DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
 ITEMS INDICATED IN SECTIONS 513.4.1 THROUGH 513.4.6 IN
 ACCORDANCE WITH FBCM 513.4. HIS SHOULD BE A SEPARATE
 REPORT SIGNED AND SEALED BY THE DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE SMOKE CONTROL SYSTEM WITH
 SUFFICIENT DETAIL TO DEMONSTRATE COMPLIANCE WITH ALL
 REQUIREMENTS OF THIS SECTION.
  
 4. MN-2.01: GARAGE VENTILATION SYSTEM SEQUENCE OF
 OPERATION, AS PRINTED ON PLAN HAS PORTION WHICH WERE
 CUT OFF AND NOT PRINTED ON PLANS. THIS SECTION CAN NOT
 BE REVIEWED FOR COMPLIANCE WITH FBCM SECTION 404 AT
 THIS TIME.
 NOTE: THERE IS NO INDICATION ON PLANS, IN THE SEQUENCE
 OR IN THE VENTILATION CALCULATIONS FOR HOW CONTINUOUS
 VENTILATION IS TO BE PROVIDED. AUTOMATIC OPERATION OF
 THE SYSTEM SHALL NOT REDUCE THE VENTILATION RATE BELOW
 0.05 CFM PER SQUARE FOOT OF THE FLOOR AREA IN
 ACCORDANCE WITH FBCM 404.2.
  
 5. MN-2.01 THROUGH MN-2.04: VARIOUS EQUIPMENT AND
 APPLIANCES ARE SHOWN BEING INSTALLED IN THE PARKING
 GARAGE WITH A NOTE TO BE INSTALLED AS HIGH AS POSSIBLE.
 APPLIANCES LOCATED IN PUBLIC GARAGES OR OTHER AREAS
 FREQUENTED BY MOTOR VEHICLES, SHALL BE INSTALLED A
 MINIMUM OF 8 FEET ABOVE THE FLOOR UNLESS APPLIANCES ARE
 PROTECTED FROM MOTOR VEHICLE IMPACT AND INSTALLED IN
 ACCORDANCE WITH NFPA 88B PER FBCM 304.5. SOME EXAMPLES
 OF APPLIANCES WHICH MAY BE AFFECTED ARE SF-7 AND CU-1.
  
 6. MN-2.02 AND MN-2.03: SHOW MEANS AND LOCATION OF
 CONDENSATE DISPOSAL FOR AC-1 AND AC-2, DEMONSTRATING
 COMPLIANCE WITH FBCM 307.2.
  
 7. MN-2.03: SEVERAL DUCTS ARE SHOWN PENETRATING 1 AND 2
 HOUR WALL ASSEMBLIES WITHOUT OPENING PROTECTIVES. SHOW
 HOW THESE PENETRATIONS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5 AND 607.1.1.
  
 8. MN-2.03: EF-3 AND EF-4 ARE SHOWN IN AN ENCLOSURE
 WITH LOUVERS WHICH WOULD DISCHARGE EXHAUST AIR FROM THE
 PARKING GARAGE ONTO ONE OR MORE WALKWAYS. EXHAUST AIR
 SHALL NOT BE DIRECTED ONTO WALKWAYS IN ACCORDANCE WITH
 FBCM 401.5.2.
  
 9. MN-2.03: THE LOCATION OF CU-2 SERVING THE TRASH ROOM
 COULD NOT BE LOCATED ON PLANS. PLEASE SHOW LOCATION OF
 CU-2 AND ROUTING OF REFRIGERANT PIPING IN ACCORDANCE
 WITH FBCM 301.1 AND FBCB 106.1.1.
  
 10. MN-2.03 AND M-2.04: GARAGE EXHAUST FAN ENCLOSURES
 FOR EFS 3,4,5 AND 6 ARE SHOWN WITH RUSKIN ELF6375DXD
 LOUVERS (OR EQUIVALENT) IN WALL OPENINGS. IN THE NOA
 FOR THIS LOUVER, THE INSTALLATION INSTRUCTIONS CALL FOR
 THE ROOM BEHIND THE LOUVER TO BE DESIGNED TO DRAIN
 WATER PENETRATING INTO THIS ROOM AND EQUIPMENT SHALL BE
 WATER RESISTANT/WATER PROOF. PLEASE SHOW THESE ROOMS
 AND THE EQUIPMENT INSTALLED IN THEM TO BE IN COMPLIANCE
 WITH THESE REQUIREMENTS PER FBCM 304.1.
  
 11. MN-2.04: IN THE BATHROOM, MEETING ROOM AND
 GENERATOR ROOM AREAS THERE ARE MULTIPLE UNPROTECTED
 DUCT PENETRATIONS AND LOUVER OPENINGS IN FIRE
 RESISTANCE RATED WALL ASSEMBLIES. SHOW HOW THESE
 PENETRATIONS AND OPENINGS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5 AND 607.1.1. COORDINATE WITH
 ARCHITECTURAL AND LIFE SAFETY PLANS.
  
 12. MN-2.04: EXTERIOR LOUVER FOR EF-5 AND EF-6 IS SHOWN
 ON PLANS TO BE AN INTAKE LOUVER WHILE IT APPEARS THAT
 THIS SHOULD BE AN EXHAUST LOUVER. PLEASE CLARIFY PER
 FBCM 501.1 AND FBCB 106.1.1.
  
 13. MN-2.05 THROUGH MN-2.08: PLAN SHOWS RAIN HOODS FOR
 GARAGE EXHAUST AND INTAKE. PROVIDE DETAIL WITH PRODUCT
 APPROVAL FOR RAIN HOODS. OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS IN ACCORDANCE WITH
 FBCM 401.6. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13.
  
 14. MN-2.05: AHU-6 SHOWS AN 18X12 OA DUCT TIED TO THE
 44X12 RETURN. THE DUCT AT THIS AND SEVERAL OTHER
 LOCATIONS THROUGHOUT THESE PLANS HAS A SYMBOL AND AN
 ABBREVIATION ?VD? WHICH COULD NOT BE FOUND IN THE
 LEGEND ON PG M-0.00. A MOTORIZED DAMPER IS REQUIRED AT
 THIS LOCATION IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3
 AND IS CALLED FOR IN THE SMOKE CONTROL SEQUENCE ON PG
 MN-0.00.
  
 15. MN-2.05: AHU-6 ON PLAN IS DRAWING OUTSIDE AIR FROM
 THE SAME PLENUM AREA AS SF1, SF-2, SF-9 AND SF-12. ARE
 THESE FANS EQUIPPED WITH BACKDRAFT DAMPERS TO PREVENT
 COMMUNICATION WITH THE GARAGE AREA WHEN THE SUPPLY FANS
 ARE NOT RUNNING? RECIRCULATION OF AIR FROM THESE AREAS
 IS PROHIBITED IN ACCORDANCE WITH FBCM 403.2.1(1) AND
 AHSRAE 62.1-2004 SECTION 5.16.
  
 16. MN-2.05: O.A. INTAKES FOR FUTURE SPACES ARE SHOWN
 WITH BACKDRAFT DAMPERS AT BRANCHES. THESE LOCATIONS
 REQUIRE MOTORIZED DAMPERS. EACH BRANCH CALLS FOR MORE
 THAN 300 CFM AND THEREFORE DOES NOT QUALIFY FOR
 BACKDRAFT DAMPER EXCEPTION #2 IN ACCORDANCE WITH FBCB
 13-409.1.ABC.3.3.
  
 17. PG MN-2.05: ACCORDING TO LIFE SAFETY PLAN PAGE
 LSN-1.2, SUPPLY FANS 9 AND 12 AS WELL AS AHU-6 HAVE
 DUCTS PENETRATION FIRE RATED ASSEMBLIES IN MULTIPLE
 LOCATIONS. SHOW HOW THESE PENETRATIONS ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.5.
  
 18. PG MN-2.05: SUPPLY FANS 1, 2, 9 AND 12 ARE ALL
 GREATER THAN 2000 CFM. PROVIDE FAN SHUT-DOWN BY SMOKE
 DETECTOR IN ACCORDANCE WITH FBCM 606.2.1 AND 606.4.
  
 19. PG MN-2.05 AND MN-2.06: ACCORDING TO THE SMOKE
 CONTROL SEQUENCE ON PG MN-0.00, WHEN IN SMOKE CONTROL
 MODE THE 44X12 RETURN DUCT FROM AHU-6 WILL BECOME THE
 MAKE-UP AIR FOR SMOKE EXHAUST FAN SEF-1. THE OUTSIDE
 AIR DUCT FOR AHU-6, WHICH WILL BE SERVING AS THE SOURCE
 OF MAKE-UP AIR, IS ONLY 18X12 AND DESIGNED FOR 1320
 CFM. HOW WILL THIS BE ADEQUATE FOR THE 33,750 CFM BEING
 EXHAUSTED FROM THE LOBBY? THIS DESIGN NEEDS TO BE
 JUSTIFIED IN THE RATIONAL ANALYSIS IN ACCORDANCE WITH
 FBCM 513.2 AND 513.4. SEE ALSO COMMENT #14 ABOVE.
  
 20. PG MN-2.06: THE 86X20 EXHAUST DUCT IS PENETRATING
 TWO 2-HOUR RATED WALLS AS SHOWN ON PG LSN-1.2. SHOW HOW
 THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBCM 607.5 AND 607.2.1.
  
 21.PG MN-2.06: THE 28X18 DUCT FOR SF-11 IS
 PENETRATING A 2-HOUR RATED FLOOR ASSEMBLY. SHOW HOW
 THIS PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.6.
  
 22. PG MN-2.06: THE 14X8 OUTSIDE AIR DUCT FOR THE
 FUTURE TENANT SPACES IS PENETRATING A 1-HOUR RATED WALL
 ASSEMBLY AS SHOWN ON PG LSN-1.2. SHOW HOW THIS
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
  
 23. PG MN-2.06: SUPPLY FANS 3, 4, 8 AND 11 ARE ALL
 GREATER THAN 2000 CFM. PROVIDE FAN SHUT-DOWN BY SMOKE
 DETECTOR IN ACCORDANCE WITH FBCM 606.2.1 AND 606.4.
  
 24. PG MN-2.06: SUPPLY DUCT AND LOUVER FOR SF-8 IS
 PENETRATING A 2-HOUR RATED WALL AS SHOWN ON PG LSN-1.2.
 SHOW HOW THIS OPENING/PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.
  
 25. PG MN-2.07: DUCT PENETRATIONS OF 1-HOUR RATED
 CORRIDOR ARE SHOWN AS HAVING FIRE DAMPERS BUT NO SMOKE
 DAMPERS. SHOW THESE PENETRATIONS TO BE PROTECTED WITH
 FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH FBCM 607.5
 AND 607.5.4.
  
 26. PG MN-2.07: CU-7 IS SHOWN IN GARAGE AREA WITH
 REFRIGERANT LINES TERMINATING AT A 4X4 DUCT. AHU-7 IS
 ON THE MEZZANINE LEVEL BELOW AND ON THE OTHER SIDE OF
 THE BUILDING. SHOW THE ROUTING OF REFRIGERANT LINES
 FROM CU TO AHU. FBCM 1101.1, FBCB 106.1.1.
  
 27. PG MN-2.08: SHUTOFF DAMPER CONTROLS ARE REQUIRED
 FOR THE AHU-8 OUTSIDE AIR INTAKE IN ACCORDANCE WITH
 FBCB 13-409.1.ABC.3.3.
  
 28. PG MN-2.08: PROTECTION OF PENETRATION AT FLOOR IS
 REQUIRED FOR SF-11 DUCT IN ACCORDANCE WITH FBCM 607.6.
 SEE COMMENT #21.
  
 29. PG MN-2.17: ROOF PLAN SHOWS SF-12 USED FOR
 PRESSURIZATION OF STAIR. SF-12 IS ALSO SHOWN AS A
 GARAGE VENTILATION FAN ON PG MN-2.05. FAN SCHEDULE ON
 MN-5.01 CALLS FOR SF-12 TO BE ON SECOND LEVEL. PLEASE
 COORDINATE THIS AND ALL FAN DESIGNATIONS ON FLOOR PLANS
 WITH THE INFORMATION ON THE FAN SCHEDULE. VERIFY
 CORRECT LOCATION IDENTIFICATION ON BOTH THE FLOOR PLANS
 AND THE SCHEDULE. FBCM 304.11, FBCB 106.1.1.
  
 30. PG MN-2.17 AND MN-2.18: SERVICE ELEVATOR AND STAIR
 SHAFT VENT OPENINGS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.1.
  
 31. PG MN-2.17 AND MN-2.18: STAIR PRESSURIZATION FAN
 SF-14 AND DUCTWORK SHALL BE LOCATED EXTERIOR TO THE
 BUILDING AND DIRECTLY CONNECTED TO THE SMOKEPROOF
 ENCLOSURE OR CONNECTED TO THE SMOKEPROOF ENCLOSURE BY
 DUCTWORK ENCLOSED BY 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIERS IN ACCORDANCE WITH FBCB 909.20.6.1(1)
  
 32. PG MN-2.17: MAIN ELEVATOR HOISTWAY VENTS SHALL OPEN
 EITHER DIRECTLY TO THE OUTER AIR OR THROUGH
 NONCOMBUSTIBLE DUCTS TO THE OUTER AIR IN ACCORDANCE
 WITH FBCB 3004.2. FLOOR PLAN CURRENTLY SHOWS THEM
 TERMINATING IN THE POOL MECHANICAL ROOM. ALSO, SUPPLY
 FAN DUCTS AND VENTILATION OPENINGS ARE PENETRATING THE
 ELEVATOR SHAFTS WITHIN THE BUILDING. THESE PENETRATIONS
 SHALL BE PROTECTED IN ACCORDANCE WITH FBCM 607.5.5.1.
 COMBINATION FIRE/SMOKE DAMPERS MAY BE USED IF UNDER THE
 CONTROL OF THE SMOKE CONTROL SYSTEM IN ACCORDANCE WITH
 FBCM 513.5.2.
  
 33. PG MN-2.17: NO MEANS OF VENTILATION OR AIR
 CONDITIONING FOR THE ELEVATOR MACHINE ROOMS IS SHOWN ON
 PLANS. ELEVATOR MACHINE ROOMS THAT CONTAIN SOLID-STATE
 EQUIPMENT FOR ELEVATOR OPERATION SHALL BE PROVIDED WITH
 AN INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM
 TO PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL
 EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING
 TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE
 ELEVATOR EQUIPMENT IN ACCORDANCE WITH FBCB 3006.2.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE IN ACCORDANCE
 WITH FBCB 3003.1.4.
  
 34. PG MN-2.17: THE ELEVATOR MACHINE ROOM SERVING A
 PRESSURIZED ELEVATOR HOISTWAY SHALL BE PRESSURIZED UPON
 ACTIVATION OF A HEAT OR SMOKE DETECTOR LOCATED IN THE
 ELEVATOR MACHINE ROOM IN ACCORDANCE WITH FBCB 3006.3.
  
  
 35. PG MN-2.18: RTU-2 DUCT ON ROOF IS SHOWN AS 28X36
 BUT ON RISER DIAGRAM ON PG MN-4.01 THE DUCT IS SHOWN AS
 28X16. COORDINATE PLANS AND DUCT SIZES. FBCM 603.1,
 FBCB 106.1.1.
  
 36. PG MN-3.0 THROUGH MN-3.6: FLOOR PLANS CALL FOR A
 VPAWP1-8 WALL PLENUM WITH A MIAMI-DADE APPROVED LOUVER.
 PROVIDE DETAIL SHOWING HOW AN APPROVED LOUVER IS TO BE
 INSTALLED IN ACCORDANCE WITH ITS APPROVED INSTALLATION
 INSTRUCTIONS WITH A WALL LOUVER ALSO INSTALLED IN THE
 WALL. EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS
 REQUIRED BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND THIS CODE PER FBCM 304.1
 AND THE CONDITIONS OF THE MIAMI-DADE APPROVAL. PROVIDE
 ALL RELATED PRODUCT APPROVALS AND INSTALLATION
 INSTRUCTIONS.
  
 37. PG MN-3.0 THROUGH MN-3.6: EACH UNIT FLOOR PLAN
 SHOWS A WASHER/DRYER, BUT NO PROVISIONS FOR DRYER
 EXHAUST ARE SHOWN ON PLANS. SHOW MEANS AND LOCATION OF
 DRYER EXHAUST WITH DUCT SIZE, TYPE OF MATERIAL AND
 TERMINATION LOCATION, DEMONSTRATING COMPLIANCE WITH
 FBCM 504.1 THROUGH 504.6. ADDITIONAL COMMENTS RELATED
 TO DRYER EXHAUST ARE LIKELY IN SUBSEQUENT REVIEW AS NO
 INFORMATION IS CURRENTLY PROVIDED.
  
 38. PG MN-3.0: IN UNIT C, THE 6X4 SUPPLY DIFFUSER IN
 THE FOYER IS NOT BEING FED BY ANY DUCT. SHOW HOW THIS
 AIR IS TO BE SUPPLIED IN ACCORDANCE WITH FBCM 603.1.
  
 39. PG MN-3.0: IN UNIT B, SUPPLY DIFFUSER IN LIVING
 ROOM IS MISSING SIZE AND CFM DESIGNATION. PROVIDE
 MISSING INFORMATION. FBCM 603.1.
  
 40. PG MN-3.0 THROUGH MN-3.6: FLOOR PLAN CALLS FOR
 RETURN AIR GRILL WITH ACCESS PANEL AT ALL A/C UNITS.
 PROVIDE DETAIL ON PLANS AND MANUFACTURER?S INSTALLATION
 INSTRUCTIONS SHOWING THE AIR CONDITIONING APPLIANCES
 ARE ACCESSIBLE FOR SERVICE AND REPLACEMENT WITHOUT
 REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1.
  
 41. PG MN-3.0: IN UNIT D, SUPPLY DIFFUSER IN POWDER
 ROOM IS MISSING SIZE AND CFM DESIGNATION. PROVIDE
 MISSING INFORMATION. FBCM 603.1.
  
 42. PG MN-3.0: IN UNIT C, THE 10X4 TRANSFER GRILL IN
 MASTER SITTING ROOM IS TOO SMALL TO MEET THE BALANCED
 RETURN EXCEPTION UNDER FBCM 601.4(2). SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED IN THIS AREA IN ACCORDANCE
 WITH THIS SECTION.
  
 43. PG MN-3.1: IN UNIT F, AHU-2 CALLS FOR A TOTAL OF
 500 CFM BUT FLOOR PLAN CALLS FOR 550 CFM. PLEASE
 COORDINATE FLOOR PLANS AND EQUIPMENT SCHEDULES. FBCM
 603.1.
  
 44. PG MN-3.1: IN UNIT F, THE 20X6 TRANSFER GRILL
 BETWEEN BEDROOM AND DINING ROOM IS TOO SMALL TO MEET
 THE BALANCED RETURN EXCEPTION UNDER FBCM 601.4(2). SHOW
 HOW BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA IN
 ACCORDANCE WITH THIS SECTION.
  
 45. PG MN-3.2: IN UNIT H, NO PROVISIONS FOR BALANCED
 RETURN ARE SHOWN ON PLANS FOR AHU-2. SHOW HOW BALANCED
 RETURN IS TO BE ACHIEVED IN THIS AREA IN ACCORDANCE
 WITH FBCM 601.4.
  
 46. PG MN-3.2: IN UNIT J, AHU-3 CALLS FOR 780 CFM WHILE
 FLOOR PLAN CALLS FOR 890 CFM. IT APPEARS THAT THE 4
 INCH DROP IN THE BATHROOM IS MISLABELED AT 150 CFM
 RATHER THAN THE USUAL 40 CFM. PLEASE VERIFY DESIRED
 AIRFLOWS AND COORDINATE FLOOR PLAN WITH EQUIPMENT
 SCHEDULE. FBCM 603.3.
  
 47. PG MN-3.3: IN UNIT M, AHU-2 CALLS FOR A TOTAL OF
 500 CFM BUT FLOOR PLAN CALLS FOR 550 CFM. PLEASE
 COORDINATE FLOOR PLANS AND EQUIPMENT SCHEDULES. FBCM
 603.1.
  
 48. PG MN-3.4: IN UNIT Q, AHU-6 IS SHOWN BUT AHU-6 ON
 SCHEDULE (MN-5.01) IS SHOWN AS SERVING THE LOBBY WITH
 6000 CFM. PLEASE COORDINATE FLOOR PLANS WITH A/C
 SCHEDULE. FBCM 603.1, FBCB 106.1.1.
  
 49. PG MN-3.4 AND MN-3.5: AHU-5 IS SHOWN AS A
 HORIZONTAL UNIT ABOVE THE CEILING. SHOW HOW THE AIR
 HANDLERS WILL BE ACCESSIBLE FOR SERVICE AND REPLACEMENT
 WITHOUT REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1.
  
 50. PG MN-3.4 AND MN-3.5 AND COMMON AREAS: LOCATION OF
 REMOTE CONDENSING UNITS FOR SPLIT SYSTEMS AND ROUTING
 OF REFRIGERANT LINES IN MOST CASES COULD NOT BE FOUND
 ON PLANS. SHOW LOCATION OF ALL APPLIANCES AND PIPING.
 FBCM 303.1, FBCB 106.1.1.
  
 51. PG MN-3.4: IN UNIT P, AHU-4 IS A VERTICAL UNIT IN A
 PLENUM CLOSET. ARCHITECTURAL FLOOR PLAN CALLS FOR DOOR
 TYPE 19 AT THIS LOCATION. DOOR SCHEDULE ON AN-8.0 SHOWS
 THIS TO BE A WOOD DOOR. PLENUM ENCLOSURES SHALL BE
 CONSTRUCTED OF MATERIALS PERMITTED FOR THE TYPE OF
 CONSTRUCTION CLASSIFICATION OF THE BUILDING IN
 ACCORDANCE WITH FBCM 602.2. AS THIS BUILDING IS OF TYPE
 IA CONSTRUCTION, NO PORTION OF THE PLENUM MAY BE
 CONSTRUCTED OF WOOD. ALSO, MATERIALS EXPOSED WITHIN
 PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED
 INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 PER FBCM 606.2.2.1. SHOW A CLOSET DOOR
 ON ARCHITECTURAL PLANS WHICH IS IN COMPLIANCE WITH
 THESE SECTIONS.
  
 52. PG MN-3.2 UNIT H AND ALL SIMILARLY CONFIGURED
 APARTMENTS: IS EF-1 EXHAUST DUCT PASSING THROUGH A
 RETURN PLENUM? EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR PLENUMS
 IN ACCORDANCE WITH FBCM 601.3.
  
 53. PG MN-3.5: IN UNIT T, PROVIDE BALANCED RETURN FROM
 LIVING AREA TO AHU-2 IN ACCORDANCE WITH FBCM 601.4.
  
 54. PG MN-3.5: IN UNIT V, FLOOR PLAN IS MISSING AHU
 DESIGNATIONS. PROVIDE MISSING INFORMATION. FBCM 603.1,
 FBCB 106.1.1.
  
 55. PG MN-3.6: IN UNIT Z, DROP IN THE CLOSET IS MISSING
 GRILL SIZE AND CFM DESIGNATIONS. PROVIDE MISSING
 INFORMATION. FBCM 603.1.
  
 56. PG MN-4.02 AND MN-4.03: SEE COMMENTS 29 THROUGH 34
 REGARDING STAIR AND ELEVATOR SHAFT VENTILATION.
  
 57. PG MN-5.01: REVIEW OF ENERGY CALCULATIONS AND
 COOLING LOAD CALCULATIONS HAVE BEEN MOVED TO THE END OF
 THE REVIEW COMMENTS. PLEASE SEE COMMENTS STARTING AT
 #71:
  
 58. PG MN-5.01: FAN SCHEDULE, SF-1 IS SHOWN ON SCHEDULE
 AS PART OF THE SMOKE EVACUATION SYSTEM FOR THE LOBBY.
 THIS FAN IS NOT SHOWN AS PART OF THE SMOKE EVACUATION
 SYSTEM ON FLOOR PLANS. PLEASE COORDINATE FLOOR PLANS
 AND EQUIPMENT SCHEDULES. FBCM 301.1, FBCB 106.1.1.
  
 59. PG MN-5.01: PACKAGED DUCTLESS SCHEDULE, BOTH CU-1
 AND CU-2 ARE SHOWN TO HAVE A UNIT DESIGNATION OF CU-1.
 APPLIANCES SERVING DIFFERENT AREAS OF A BUILDING OTHER
 THAN WHERE THEY ARE INSTALLED SHALL BE PERMANENTLY
 MARKED IN AN APPROVED MANNER THAT UNIQUELY IDENTIFIES
 THE APPLIANCE AND THE AREA IT SERVES IN ACCORDANCE WITH
 FBCM 304.11. PLEASE CORRECT UNIT DESIGNATIONS.
  
 60. PG MN-5.02: AHU DETAIL, NOTE 1 CALLS FOR CPVC PIPE
 IN PLENUM CLOSET.
 A) WHAT SIZE PIPE IS TO BE USED? CONDENSATE WASTE AND
 DRAIN LINE SIZE SHALL BE NOT LESS THAN ? INCH INTERNAL
 DIAMETER IN ACCORDANCE WITH FBCM 307.2.2.
 B) CPVC MAY OR MAY NOT MEET THE FLAME SPREAD ? SMOKE
 DEVELOPMENT RATING OF 25/50 AS REQUIRED BY FBCM
 606.2.2.1 DEPENDING ON SIZE OF PIPE AND WHETHER OR NOT
 IT IS CHARGED WITH WATER (UNDER PRESSURE). EXCEPTION
 NUMBER 5 OF THIS SECTION REQUIRES COMBUSTIBLE MATERIALS
 TO BE ENCLOSED IN APPROVED GYPSUM BOARD ASSEMBLIES OR
 ENCLOSED IN MATERIALS LISTED AND LABELED FOR SUCH
 APPLICATION. ARMAFLEX IS NOT LISTED AND LABELED FOR
 ENCLOSING COMBUSTIBLE MATERIALS IN PLENUMS. SHOW HOW
 THE REQUIREMENTS OF THIS SECTION ARE TO BE MET.
  
 61. PG MN-5.02: DUCT CONNECTION AND HANGER DETAILS, THE
 SUPPORT SPACING TABLE APPEARS TO APPLY TO SHEET METAL
 DUCTS, BUT THAT IS NOT INDICATED ON PLANS. THE SPACING
 SHOWN ON THE TABLE IS NOT ADEQUATE FOR THE SPACING
 REQUIREMENTS OF FLEX DUCTS. SHOW SUPPORT SPACING FOR
 FLEXIBLE DUCTS WHICH ARE IN COMPLIANCE WITH FBCM
 603.5.6.6.
  
 62. PG MN-5.02: CONDENSATE DRAIN TRAP DETAIL CALLS FOR
 REPLACEMENT OF EXISTING CONDENSATE TRAPS. THERE SHOULD
 BE NO EXISTING TRAPS AS THIS IS NEW CONSTRUCTION. WILL
 USED MATERIALS BE INSTALLED? SEE FBCB 301.4.4.
  
 63. PG MN-5.02 AND MN-5.04: FIRE DAMPER DETAIL AND
 FIRE/SMOKE DAMPER DETAIL, THE DETAILS SHOWN ON PLANS
 LIKELY DO NOT CORRELATE WITH FIRE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL
 SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBCM 607.2. COORDINATE
 DETAILS ON PLANS WITH MANUFACTURER?S INSTRUCTIONS.
  
 64. PG MN-5.02: CONDENSING UNIT ROOF DETAIL, NO
 INFORMATION OR DETAIL COULD BE FOUND IN STRUCTURAL
 PLANS FOR CONSTRUCTION AND FASTENING OF RACK. PROVIDE
 WIND LOAD CALCULATIONS AND STRUCTURAL DETAIL FOR
 CONSTRUCTION OF ROOF RACK FOR CONDENSING UNIT FOR
 BUILDING PLAN REVIEW IN ACCORDANCE WITH FBCM 301.13 AND
 FBCB 1609.1.
  
 65. PG MN-5.02: CONDENSING UNIT ROOF DETAIL SHOWS
 CONDENSING UNITS SECURED TO RACK WITH CABLES. SHOW HOW
 THESE CABLES ARE TO BE USED TO SECURE CONDENSERS
 WITHOUT INTERFERING WITH THE SERVICE ACCESSIBILITY OF
 THE UNITS. CLEARANCES AROUND APPLIANCES TO ELEMENTS OF
 PERMANENT CONSTRUCTION, INCLUDING OTHER INSTALLED
 EQUIPMENT AND APPLIANCES, SHALL BE SUFFICIENT TO ALLOW
 INSPECTIONS, SERVICE, REPAIR OR REPLACEMENT WITHOUT
 REMOVING SUCH ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1.
  
 66. PG MN-5.03: HORIZONTAL AHU DETAIL, PROVIDE
 SECONDARY OR AUXILIARY DRAIN PROTECTION IN ACCORDANCE
 WITH FBCM 307.2.3.
  
 67. PG MN-5.03: ROOFTOP PACKAGE UNITS, PROVIDE
 MANUFACTURER?S TEST DATA SHOWING THESE UNITS ARE
 DESIGNED TO WITHSTAND ANTICIPATED WIND PRESSURES. NOT
 JUST THE ATTACHMENTS, BUT THE UNITS THEMSELVES SHALL BE
 DESIGNED TO WITHSTAND WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13 AND FBCB 1609.1.
  
 67. PG MN-5.03: ROOFTOP PACKAGE UNITS, THE ATTACHMENT
 DETAIL IS NOT LEGIBLE AS IT APPEARS THAT CERTAIN LAYERS
 DO NOT LINE UP IN THE DRAWING. PLEASE CORRECT. ALSO,
 PLEASE SEE COMMENT # 65 REGARDING SUPPLEMENTAL
 RESTRAINTS AND SERVICE ACCESS FOR THE UNITS.
  
 68. PG MN-5.05: OUTSIDE AIR CALCULATIONS, PLEASE
 REFERENCE ASHRAE 62.1-2004. ADDENDUM N AS SHOWN ON
 PLANS IS NOT THE CURRENT ADOPTED STANDARD ACCORDING TO
 FBCM CHAPTER 15.
  
 69. PG MN-5.05: OUTSIDE AIR CALCULATIONS, PLEASE
 PROVIDE CALCULATIONS SHOWING APARTMENT UNITS HAVING
 ADEQUATE NATURAL VENTILATION IN ACCORDANCE WITH FBCM
 SECTION 402 SINCE MECHANICAL VENTILATION FOR THE
 APARTMENTS IS NOT PROVIDED.
  
 70. NO INFORMATION COULD BE FOUND ON PLANS REGARDING
 THE EMERGENCY GENERATOR. SHOW MEANS AND LOCATION OF
 FUEL STORAGE TO BE IN COMPLIANCE WITH FBCM 915.1, 915.2
 AND NFPA 37-02. SHOW MEANS OF VENTILATION AND EXHAUST
 TO BE IN COMPLIANCE WITH FBCM 401.5, 401.6 AND NFPA
 110-02 SECTIONS 7.7.1 THROUGH 7.7.8.
  
 71. ENERGY CALCULATIONS: THE VERSION OF ENERGY
 CALCULATIONS WHICH WERE SUBMITTED IS NOT THE VERSION
 ADOPTED UNDER THE CURRENT EDITION OF THE FLORIDA
 BUILDING CODE. AN ACCURATELY COMPLETED FORM 400A-04R
 (GENERATED BY THE FLA/COM-2004 COMPUTER PROGRAM,
 VERSION 2.5) DEMONSTRATING THAT CODE COMPLIANCE HAS
 BEEN ACHIEVED SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL FOR METHOD A COMPLIANCE IN ACCORDANCE WITH
 FBCB 13-400.3.A. ALSO, THE FRONT PAGE INDICATES THIS IS
 A TWO STORY BUILDING WITH A MAX TONNAGE OF 3. PLEASE
 CORRECT AS THESE ARE NOT ACCURATE REPRESENTATIONS.
  
 72. ENERGY CALCULATIONS: THERE ARE MANY DISCREPENCISE
 BETWEEN THE INFORMATION SHOWN IN THE INPUT DATA REPORT
 (IDR) AND THE CONDITIONS SHOWN ON THE PLANS.
 EXAMPLE: EVERY ZONE IS SHOWN IN THE IDR AS HAVING A
 DEPTH OF 100 FEET. THIS IS CLEARLY NOT THE CASE ON THE
 PLANS. ALSO, THE LOBBY IS SHOWN AS HAVING A HEIGHT OF 8
 FEET. THIS IS ALSO NOT CORRECT AS THE LOBBY HEIGHT GOES
 FROM THE GROUND FLOOR THROUGH THE MEZZANINE.
 EXAMPLE: THE IDR SHOWS THE AC IN THE LOBBY-MEZZANINE TO
 BE <65,000 BTU/H OR 18,000 BTU/H BUT AHU-6 ON PLAN IS
 SHOWN AS 180,000 BTU/H OR 15 TONS. AN EFFICIENCY RATING
 OF 13 SEER WOULD BE INAPPROPRIATE FOR A UNIT OF THAT
 SIZE.
 EXAMPLE: THE ZONES AS DESCRIBED IN THE IDR ARE NOT
 CORRECTLY SEPARATED BASED ON THE WAY ZONES ARE REQUIRED
 TO BE SEPARATED IN ACCORDANCE WITH FBCB
 13-407.1.ABC.2.4.3. THERE ARE ZONES WHICH COVER MORE
 THAN ONE FLOOR AND ZONES WHICH COVER MORE THAN 25,000
 SQUARE FEET. BOTH OF THESE CONDITIONS ARE PROHIBITED
 UNDER THIS SECTION.
  
 73. THESE ARE EXAMPLES OF DISCREPANCIES WHICH HAVE BEEN
 IDENTIFIED IN THE ENERGY CALCULATIONS. THEY ARE NOT
 INTENDED TO BE AN EXHAUSTIVE LIST OF ALL PROBLEMS OR
 INACCURACIES CONTAINED WITHIN. IT IS THE RESPONSIBILITY
 OF THE DESIGN PROFESSIONAL TO PREPARE AND SUBMIT AN
 ACCURATELY COMPLETED ENERGY CODE COMPLIANCE FORM.
 PLEASE TAKE THE TIME TO VERIFY ALL DATA INCLUDED IN THE
 IDR AS IT WILL BE REVIEWED AND COMPARED TO THE
 SUBMITTED PLANS.
  
 74. DUE TO THE INACCURATE NATURE OF THE ENERGY CODE
 COMPLIANCE FORM, THE COOLING LOAD CALCULATIONS CAN NOT
 BE REVIEWED AT THIS TIME. PLEASE VERIFY ANY CHANGES
 MADE TO THE ENERGY CODE CALCULATIONS AND THE PLANS ARE
 INCORPORATED INTO THE COOLING LOAD CALCULATIONS AND
 RESUBMIT IN ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 NOTE: DUE TO THE AREAS OF INFORMATION WHICH IS LACKING
 ON THE PLANS, A THOROUGH REVIEW CANNOT BE COMPLETED AT
 THIS TIME. IT IS LIKELY THAT ADDITIONAL NEW COMMENTS
 WILL BE GENERATED DURING SUBSEQUENT REVIEWS ONCE
 MISSING INFORMATION IS PROVIDED.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING WITH
 INDICATION AS TO HOW THE COMMENT WAS ADDRESSED AND
 WHERE THE RELEVANT INFORMATION CAN BE LOCATED. ALSO,
 PLEASE RETURN ONE SET OF OLD/VOIDED PLANS TO ASSIST IN
 SUBSEQUENT REVIEWS.
  
 NOTE: ALL PERMITS WHICH ARE ISSUED AFTER JULY 1, 2008
 ARE SUBJECT TO NEW STATE REQUIREMENTS FOR CARBON
 MONOXIDE SENSORS IN EVERY SLEEPING ROOM WHEN FUEL FIRED
 APPLIANCES OR AN ATTACHED GARAGE IS PRESENT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By kstevens Date 2008-03-24 Time 14:50 Rev Time 0.00
Received By kstevens Date 2008-03-20 Time 15:55 Sent To  
Notes
2008-03-24 15:56:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. PLANS ARE INCOMPLETE AT THIS TIME AND MORE COMMENTS
 MAY BE FORTHCOMING WHEN ALL REQUIRED PLANS ARE
 SUBMITTED. SECTION 106.1.2.
  
 2. SHT G-1.0 THE INDEX OF DRAWING DOES NOT REFLECT THE
 SHEETS SUBMITTED. MANY SHEETS SHOWN ON THE INDEX WERE
 NOT SUBMITTED AND MANY SHEETS SUBMITTED WERE NOT
 INDICATED ON THE INDEX OF DRAWINGS. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 3. ALL ARCHITECTURAL SHEETS. THE SIGNATURE OF THE
 ARCHITECT IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED TO SIGN THE PLANS. IF INDEED
 THIS IS THE ARCHITECTS LEGAL SIGNATURE, THEN A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT. FAC 61G1-16.003, 61G1-16.004(5) & FS
 481.2055.
  
 4. SHT AN-2.1 MEN'S & WOMEN'S BATHROOM & CHANGING ROOM
 SHALL BE ACCESSIBLE. PLEASE SUBMIT DETAILS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 5. SHT AN-2.1 THE GREASE INTERCEPTORS SHALL BE SIZED BY
 THE UTILITY DEPT. PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE AT (561) 644-1821, BY FAX
 (561) 822-2287, OR BY E-MAIL [email protected]. A WRITTEN
 DETERMINATION SHALL BE SUBMITTING INDICATING THE
 REQUIRED GREASE INTERCEPTOR SIZE. ARTICLE III SECTION
 90-124(7)(A THRU G).
  
 6. SHT AN-2.1 THE MINIMUM FACILITIES CALCULATIONS ARE
 UNCLEAR. THE FIXTURES FOR THE ASSEMBLY ARE INDICATED ON
 THE FLOOR PLAN. ALSO THE TOILET FACILITIES FOR THE
 MEETING ROOM ARE SHOWN ALL EXCEPT THE DRINKING
 FOUNTAINS, (ONLY 1 SERVICE SINK REQUIRED FOR THE
 BUILDING IF ACCESSIBLE TO ALL RETAIL SPACES). BUT NO
 FIXTURES ARE SHOWN FOR THE TETAIL SPACES. WILL THESE BE
 INDICATED AT THE BUILD-OUT OF THE RETAIL SPACES? ALSO 3
 DRINKING FOUNTAINS ARE REQUIRED BUT ONLY 2 DRINKING
 FOUNTAINS ARE SHOWN. TABLE 403.1.
  
 7. SHT AN-2.1 SHOWS FLAT FLOOR DRAINS AT THE PLAZA ON
 THE WEST SIDE OF THE MAIN LOBBY/DROP OFF AREA BUT NOT
 ON THE LEFT SIDE. PLEASE CLARIFY. ALSO THERE ARE 10
 OTHER FLAT FLOOR DRAINS SHOWN AT THE DRIVE THRU/DROP
 OFF AREA. IF THESE ARE FOR STORM DRAINAGE THEN THE
 CORRECT RECEPTICLE FOR DRAINING THE STORM WATER IS AREA
 DRAINS. SECTION 202.
  
 8. SHT AN-2.3 MANY UNIT TYPES ARE NOT LEGIBLE. THERE IS
 OTHER INFORMATION PRINTED OVER THE TOP OF THE UNIT
 TYPE. SECTION 106.1.1.
  
 9. SHT AN-2.4 MORE INFORMATION IS REQUIRED. WILL THE
 PRIVATE TERRACES FOR UNITS "D" & "F" HAVE STORM
 DRAINAGE? PLEASE CLARIFY. SECTIONS 106.1.2, 1106 &
 1107.
  
 10. SUBMIT CALCULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS AT EACH DECK, TERRACES, PRIVATE TERRACES, POOL
 DECK AND ROOF ELEVATIONS PER SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS AND TABLES. WHERE REQUIRED SHOW ALL
 SECONDARY DRAINS/SCUPPERS. SHOW THE AREA PLUS 1/2 THE
 VERTICAL WALL CONTRIBUTION INCLUDING PARAPETS AS WELL
 AS ALL ROOF AREAS THAT DRAIN ON TO THE AREA FROM ABOVE
 FOR EACH DRAIN IN THE CALCULATIONS SUBMITTED.
  
 11. SHT AN-8.1 SHOW COMPLIANCE WITH SECTION 1210.2 FOR
 COMMON AREA TOILET ROOMS AND BATHROOMS.
  
 12. SUBMIT RISER DESIGNATION NUMBERS FOR EACH RISER SO
 THEY CAN BE TRACKED THRU THE BUILDING FROM THE
 UNDERGROUND THRU THE VENT THRU ROOF. (EXAMPLES SAN-1,
 SAN-2, SAN-3, RWL-1, RWL-2, RWL-3 ETC.) (SEE CONDENSATE
 RISER DESIGNATION NUMBERS).--RISER #1 AS SHOWN DOES
 NOT RELFECT ALL RISERS DESIGNATED AS RISER #1. RISER #1
 SHOWS KITCHEN SINKS ON THE 2ND THRU 8TH FLOORS (14
 DFU), BUT SOME RISER #1 DO NOT HAVE A KITCHEN SINK ON
 THE 2ND FLOOR AS SHOWN ON THE FLOOR PLAN. THOSE RISER
 #1 CAN BE TYPICAL OF MANY RISERS AND CAN BE INDICATED
 AS RISER #1 TYPICAL OF SAN-1, SAN-5, SAN-7 ETC FOR
 EXAMPLE AS RISERS THAT ARE THE SAME AS RISER #1. FOR
 RISERS THAT ARE DIFFERENT BUT IN THE SAME CATAGORY
 THOSE RISERS CAN BE TYPICAL OF ANOTHER RISER NUMBER.
 EACH TYPICAL RISER SHALL INDICATE THE OFFSETS SHOWN ON
 THE FLOOR PLAN.THIS IS REQUIRED FOR EACH RWL OR STORM
 RISER ALSO.
  
 13. SUBMIT A COMPLETE STORM RISER ISOMETRIC RISER
 DIAGRAM FOR THE BUILDING STORM HORIZONTAL DRAINAGE
 SYSTEM. SHOW ALL PIPE SIZES, RISERS FROM THE BUILDING
 STORM DRAIN THRU TO THE DECK DRAINS, TERRACE DRAINS,
 ROOF DRAINS ETC, CLEANOUTS, OFFSETS & INDICATE SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. INDICATE THE
 RISERS DESIGNATION NUMBERS FOR EACH RISER TO TRACK
 PIPING THRU THE BUILDING. SECTIONS 106.3.5.1.3, 1101.1,
 1101.8, 1106 & 1107 WITH ALL SUBSECTIOS & TABLES.
  
 14. SUBMIT STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES,
 OFFSETS ETC. AND INDICATE THE RISER DESIGNATION NUMBER
 FOR EACH RISER SO IT CAN BE TRACKED FROM THE STORM
 BUILDING HORIZONTAL DRAIN THRU THE DECK DRAINS,
 TERRACES, ROOF DRAINS ETC. SECTIONS 106.3.5.1.3, 1106,
 & 1107 WITH ALL SUBSECTIONS & TABLES.
  
 15. SUBMIT A COMPLETS SANITARY ISOMETRIC HORIZONTAL
 RISER DIAGRAM FOR THE BUILDING SANITARY DRAIN INCLUDING
 ALL PIPING NOT SHOWN ON VERTICAL RISER DIAGRAMS. SHOW
 ALL PIPE SIZES, CLEANOUTS, TRAPS, VENTS ETC. SECTIONS
 106.3.5.1.3, 701.1, 704, 708, 901 & 1001.1.
  
 16. SUBMIT A COMPLETE CONDENSATE HORIZONTAL ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS IN ISOMETRIC
 FORM. SHOW ALL PIPE SIZES, OFFSETS ETC. SECTION
 106.3.5.1.3.
  
 17. SUBMIT A COMPLETE POTABLE HORIZONTAL WATER
 ISOMETRIC RISER DIAGRAM AND VERTICAL RISER DIAGRAMS
 SHOWING ALL PIPE SIZES, VALVES & WATER HAMMER
 ARRESTORS. SECTIONS 106.3.5.1.3, 601.1, 603, 604, 606,
 607, & 608 WITH ALL SUBSECTIONS AND TABLES.
  
 18. SHT PN-201 AREA DRAIN NEAR COL. LINE 8 BETWEEN
 COLS. N & O SHOWS 4" AD BUT ALSO SHOWS 6" AD(3907SF)
 WITH 4" DOWNSTREAM. PLEASE CLARIFY. TABLE 1106.3. (6"
 PIPE REQD FOR 3907SF @ 1/8"/FT.
  
 19. SHT PN-2.01 CD/18 - CD/19 - CD/20 - CD/21 SHOWS
 1-2/2" CD DRAIN. PLEASE CLARIFY. SECTION 106.1.1.
  
 20. SHT PN-2.01 INFORMATION NEAR COL. LINE 8/I IS NOT
 LEGIBLE. PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 21. SHT PN-2.01 ALL CONDENSATE LINES, RWL LINES & STORM
 LINES ARE SHOWN WITHOUT PIPING. PLEASE INDICATE WHERE
 THESE LINES CONNECT TO THE HORIZONTAL CONDENSATE AND
 STORM DRAINS. SECTIONS 106.1.1, 106.1.2, 1101.1, TABLES
 1106.2, 1106.3.
  
 22. SHT PN-2.01 SHOW THE REQUIRED CLEANOUTS FOR ALL
 SYSTEMS PER SECTIONS 708, & 1101.8.
  
 23. SHT PN-2.02ALL CONDENSATE LINES, RWL LINES &
 STORM LINES ARE SHOWN WITHOUT PIPING. PLEASE INDICATE
 WHERE THESE LINES CONNECT TO THE HORIZONTAL CONDENSATE
 AND STORM DRAINS. SECTIONS 106.1.1, 106.1.2, 1101.1,
 TABLES 1106.2, 1106.3.
  
 24. SHT PN-2.02 INFORMATION BY CONDENSATE RISERS 30,31
 & 33 THRU 35 IS NOT LEGIBLE. SECTION 106.1.1. PLEASE
 CLARIFY.
  
 25. SHT PN-2.02 SHOWS 4" AD BUT ALSO SHOWS 6" AD
 (3707SF) WITH 4" DOWNSTREAM. PLEASE CLARIFY. TABLE
 1106.3. (6" PIPE REQD FOR 3707SF @ 1/8"/FT.
  
 26. SHT PN-2.02 SHOWS 4" FD (955 SF) AT COL. LINE
 14/F.2. IF THIS IS STORM, THE RECEPTICAL SHALL BE
 DESIGNATED AS AN AREA DRAIN OR ROOF DRAIN. SECTION
 202.1.
  
 27. SHT PN-2.02 SHOWS TWO 12" STORM SEWER PIPES AT THE
 CEILING BUT DOES NOT INDICATE THE PIPES CONNECTING TO
 ANY BUILDING STORM DRAIN OR STORM RISERS. PLEASE
 CLARIFY. SECTIONS 106.1.1, 106.1.2 & 1106.
  
 28. SHT PN-2.02 NOTES AT EAST SIDE OF BLDG ARE
 INCOMPLETE. SECTIONS 106.1.1 & 106.1.2. PLEASE SUBMIT
 COMPLETE INFORMATION.
  
 29. SHT PN-2.02 SHOW REQUIRED CLEANOUTS REQUIRED FOR
 THE SANITARY AND STORM SYSTEMS PER SECTIONS 708 &
 1101.8.
  
 30. SHT PN-2.02 SHOWS24" ROUND BY 24" DEEP SUMP PIT
 AND AN 18"X18"X18" SUMP PIT BUT THERE IS NO PIPING
 EXITING THE PITS. PLEASE SHOW THE SUMP DISCHARGE PIPING
 ON THE FLOOR PLAN AND SUBMIT A RISER DIAGRAM FOR THE
 PIPING SHOWING ALL PIPE SIZES, CLEANOUTS. VALVES &
 CHECK VALVES AS WELL AS THE TERMINATION POINT FOR THE
 DISCHARGE LINES. SECTIONS 106.1.2 & 712.
  
 31. SHT PN-2.03 DETAIL #3 PLAN VIEW SHOWS A 6" SAN
 STACK BUT THE RISER DIAGRAM AND THE FLOOR PLAN SHOW A
 4" SAN STACK. PLEASE CORRELATE. SECTION 106.1.1 &
 TABLES 710.1(1) & 710.1(2).
  
 32. SHT PN-2.03 DETAIL #3 RISER ISOMETRIC RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN AT THE DRINKING
 FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1.
  
 33. SHT PN-2.03 6" RWL OFFSET AT COL. LINE 8/M-N
 INDICATED DOWN AT BOTH ENDS OF THE OFFSET. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 34. SHT PN-2.03 VENT SHOWN IN THE FLOOR BY THE TURNING
 AREA. PLEASE CLARIFY. SECTION 106.1.1.
  
 35. SHT PN-2.04 THE 6" RWL OFFSET AT COL. LINE 11 SHOWS
 DOWN AT BOTH ENDS OF THE OFFSET. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 36. SHT PN-2.04 A RELIEF VENT IS REQUIRED FOR THE 2"
 AAV. SECTION 917.3.2.
  
 37. SHT PN-2.04 COL. LINE 14 INDICATES A 4" FD (955
 SF). IF THE SYSTEM IS FOR STORM WATER, THE RECEPTICAL
 SHALL BE DESIGNATED AS A ROOF DRAIN OR AREA DRAIN.
 SECTION 202.
  
 38. SHT PN-2.05A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 39. SHT PN-2.05 SHOWS 4" SAN. DOWN FOR RISER 168FU & 6"
 DOWN 424FU ON THE SAME BRANCH/DRAIN LINE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 40. SHT PN-2.05 SHOWS A TWO INCH VENT AT THE CEILING
 SPACE, BUT DOES NOT WHOW WHERE THE VENT IS LOCATED.
 PLEASE CLARIFY. SECTION 106.1.2.
  
 41. SHT PN-2.05 INDICATES A 4" SAN DOWN FOR RISERS 1 &
 2 AT THE UPPER END OF THE DRAIN LINE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 42. SHT PN-2.05 INDICATES A 4" SAN DOWN FOR RISERS 2 &
 3 AT THE UPPER END OF THE DRAIN LINE. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 43. SHT PN-2.05 INDICATES A 3" VENT DOWN BY COL. LINE
 4/J-K. VENT TO TERMINATE OUTSIDE OF BUILDING. PLEASE
 CLARIFY. SECTION 903.3.
  
 44. SHT PN-2.06 SHOWS 4" FLOOR DRAIN (955 SF) & 4"
 FLOOR DRAIN (303 SF). IF THE SYSTEM IS FOR STORM WATER,
 THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF DRAIN OR
 AREA DRAIN. SECTION 202.
  
 45. SHT PN-2.06 A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 46. SHT PN2.06 SHOWS A 3" SD FROM BELOW (294 SF), BUT
 THE RISER SEEMS TO BE AT THE HIGH END OF THE DRAIN
 LINE. PLEASE CLARIFY. SECTION 106.1.1.
  
 47. SHT PN-2.07 INFORMATION SOUTH OF CD RISERS 60 & 61
 NOT LEGIBLE. INDICATE THE LOCATION OF THE STORM DRAINS.
 SECTIONS 106.1.1 & 106.1.2.
  
 48. SHT PN-2.07 A RELIEF VENT IS REQUIRED FOR THE 3"
 AAV. SECTION 917.3.2.
  
 49. SHT PN-2.07 SHOWS A 4" FLOOR DRAIN (900 SF).IF
 THE SYSTEM IS FOR STORM WATER, THE RECEPTICAL SHALL BE
 DESIGNATED AS A ROOF DRAIN OR AREA DRAIN. SECTION 202.
  
 50. SHT PN-2.08 INFORMATION BY CD/48 NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 51. SHT PN-2.08 SHOWS 4" FLOOR DRAIN (955 SF) & 4"
 FLOOR DRAIN (303 SF). IF THE SYSTEM IS FOR STORM WATER,
 THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF DRAIN OR
 AREA DRAIN. SECTION 202.
  
 52. SHT PN-2.09 INDICATES CD/17A RISER THAT IS NOT
 SHOWN ON THE PREVIOUS LEVELS/ PLEASE CLARIFY. SECTIONS
 106.1.1 & 106.1.2.
  
 53. SHT PN-2.09 NOTE BY COL. LINE 9/P NOT LEGIBLE.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 54. SHT PN-2.10 SHOWS FOUR 4" FLOOR DRAINS, (303 SF)
 (955 SF) (993 SF) (404 SF). IF THE SYSTEM IS FOR STORM
 WATER, THE RECEPTICAL SHALL BE DESIGNATED AS A ROOF
 DRAIN OR AREA DRAIN. SECTION 202.
  
 55. SHT PN-2.10 SANITARY RISER #1 NEAR N.1/K.1 - 15/16
 COL LINE IS INDICATED AS RISER 1B ON THE 2ND FLOOR.
 PLEASE CORRELATE. SECTION 106.1.1 & TABLE 710.1(2).
  
 56. PLUMBING FLOOR PLANS FOR THE 4TH THRU 8 TH FLOORS,
 ROOF PLANS & POOL DECK HAVE NOT BEEN SUBMITTED. PLEASE
 SUBMIT ALL FLOOR PLANS. SECTION 106.1.2.
  
 57. SHT PN-3.0 DETAIL #3 SANITARY RISER #1 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 58. SHT PN-3.2 RISER I2 DOES NOT REFLECT THE FLOOR PLAN
 AT THE LAV. PLEASE CORRELATE. SECTION 106.1.1.
  
 59. SHT PN-3.2 RISER G1 VENT REQUIRED FOR BOTH LAVS.
 SECTION 901.2.1.
  
 60. SHT PN-3.3 DETAIL #3 UNIT M SHOW PIPING TO W/C 2ND
 BATH. SECTION 106.1.2.
  
 61. SHT PN-3.3 RISER K1 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 62. SHT PN-3.4 RISER P6 VENT FOR LAV DOES NOT RELFECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 63. SHT PN-4.0 RISER FOR UNIT C DETAIL #3 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 64. SHT PN-4.1 RISER FOR UNIT K1 DETAIL 1 DOES NOT
 REFLECT THE FLOOR PLAN AT THE WATER HEATER BETWEEN REF
 & KITCHEN SINK & 3/4" TO W/M ON FLOOR PLAN, 1/2" ON
 RISER. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 65. SHT PN-4.1 RISER FOR UNIT E DETAIL 2 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1. (SHOWS 1" PAST LAV IN 2ND BATH).
  
 66. SHT PN-4.2 RISER FOR UNIT I DETAIL 3 DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTIONS
 106.1.1 & 601.1. (WATER SUPPLY LINE TO W/H AND OUT OF
 THE W/H).
  
 67. SHT PN-4.4 UNIT P RISER AND FLOOR PLAN. SHOW THE
 PIPE SIZE FOR THE COLD WATER FROM THE UNIT SHUT OFF
 VALVE TO PAST 1ST LAV. (1/2" INDICATED). SECTIONS
 106.1.2 & 601.1.
  
 68. SHT PN-4.4 UNIT O SHOWS 3/4" COLD WATER TO BATHROOM
 ON FLOOR PLAN, BUT INDICATES BOTH 3/4" AND 1/2" COLD
 WATER PAST KITCHEN SINK ON RISER DIAGRAM. PLEASE
 CLARIFY AND CORRELATE. SECTIONS 106.1.1, 106.1.2, 601.1
 & 604.
  
 69. SHT PN-4.5 INDICATES 1/2" HOT WATER TO REF IN UNIT
 T RISER. COLD WATER SUPPLY REQUIRED. SECTIONS 106.1.1 &
 601.1.
  
 70. SHT PN-5.0 UNABLE TO VERIFY SANITARY RISER TO SEE
 IF THEY REFLECT THE FLOOR PLANS AS THE 4TH THRU 8TH
 FLOORS & POOL DECK HAVE NOT BEEN SUBMITTED.SOME
 RISERS ARE NOT TYPICAL. SOME FLOOR PLANS SHOW OFFSETS
 NOT TYPICAL OF OTHER RISERS WITH THE SAME NUMBER. EACH
 RISER SHALL BE INDIVIDUALLY NUMBERED SO THEY CAN BE
 TRACKED THRU THE BUILDING.
  
 71. SHT PN-5.1 RISER DIAGRAM SUBMITTED IS NOT COMPLETE.
 SUBMIT AN ISOMETRIC RISER DIAGRAM THAT REFLECT THE
 COMPLETE SANITARY BUILDING HORIZONTAL DRAIN WITH RISER
 CONNECTIONS THAT REFLECTS THE FLOOR PLAN. SHOW ALL PIPE
 SIZES, TRAPS, VENTS, AND DFU'S AS THEY ACCUMULATE TIN
 THE SYSTEM. SECTIONS 106.3.5.1.2, 701.1 704, 706, 708,
 709, 710 & 711.
  
 72. SHT PN-6.01 NON-POTABLE WATER TREATMENT ISOMETRIC
 RISER DIAGRAM. PLEASE SHOW ALL PIPE SIZES. SUBMIT A
 WATER RISER DIAGRAM FOR THE COMPLETE SYSTEM FROM THE
 PUMP, CHLORINATOR & FILTER AREA TO THE PUBLIC TOILETS,
 AND TO THE POINT OF IRRIGATION CONNECTION. SHOW THE
 LOCATION OF THE PUMP, CHLORINATOR & FILTER AREA ON THE
 FLOOR PLAN AS WELL AS THE PIPING TO THE TOILET ROOMS
 AND FIXTURES AND THE POINT OF CONNECTION FOR THE
 IRRIGATION. SECTIONS 106.1.2 & 601.1.
  
 ***FHA/ACCESSIBILITY NOTES***
  
 73. SHTS AN-2.4, AN-2.3, AN-2.6 & AN-2.7 UNIT TYPE "E"
 SHOW THE W/C ADJACENT TO THE WALL IN ONE BATHROOM. NO
 BACKING DETAIL HAS BEEN SUBMITTED FOR THE W/C NEXT TO A
 WALL ON SHT AN-7.2. PLEASE SUBMIT BACKING DETAIL AS
 INDICATED ON PAGES 6.4 & 6.5.
  
 74. SHT AN-7.2 DETAIL 5 THE OPENING FOR THE WATER
 CLOSET BETWEEN THE LAV AND TUB SHALL SHOW A MINIMUM
 33". (18" - 15"). SEE PAGES 7.43 THRU 7.45.
  
 75. SHT AN-7.2 DETAIL 6 ELEVATION. SHOW THE BOTTOM OF
 THE BACKING FOR THE TUB TO BE 6" MAX OFF THE TUB PER
 PAGE 6.9.
  
 76. SPECIFICATION "A" OR "B" SHALL BE INDICATED FOR
 EACH UNIT AS REQUIRED ON PAGES 7.34 & 7.35. PLEASE
 INDICATE ON PLANS.
  
 77. SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLANS FOR
 THE WATER CLOSETS IN ALL ACCESSIBLE BATHROOMS. PAGE
 7.43.
  
 78. SHT AN-7.5 DETAILS 2 AND 6 SHOWER CONTROLS LOCATION
 AND HEIGHT NOT INDICATED PER SECTIONS 11-4.21.3 &
 11-4.21.5.--NOTE AT EACH DETAIL STATES, "FOR NUM.
 DIMENSIONS & SPECS. (ADA) SEE SHEET A-7.?. PLEASE
 CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 79. SHT AN-7.6 DETAIL #1 WATER CLOSET STALLS SHALL
 COMPLY WITH SECTION 11-4.17.3 & FIG. 11-30E. A LAV IS
 REQUIRED IN THE ACCESSIBLE STALL.--SHOWERS SHALL
 COMPLY WITH SECTION 11-4.21.2 FOR SIZE. PLEASE SHOW
 COMPLIANCE.
  
 80. SHT AN-7.6 PLEASE SHOW COMPLIANCE WITH SECTIONS
 11-5.16, 11-4.19, 11-4.21 & 11-4.22 WITH ALL
 SUBSECTIONS. FOR BATHROOMS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-08 Cont ID  
Sent By aaponte Date 2008-02-08 Time 08:08 Rev Time 0.00
Received By aaponte Date 2008-02-08 Time 08:08 Sent To  
Notes
2008-02-08 09:00:311. PLEASE MARK THE EXACT AREA COUNTED AS REQUIRED OPEN
 OPACE (SITE PLAN)
 2.THE BASEMENT SOURHT EXIT FROM ELEVATOR LOBBY DOES NOT
 PROVIDE SPACE FOR PEDESTRIANS.
 3. PLEASE INDICATE TRAVEL LANES BETWEEN AXES K.1 TO
 I.1. CIRCULATION PATTERN MAY BE TIGHT. PLEASE INDICATE
 TURNING RADIUS TO ENSURE SPACE IS SUFFICIENT.
 4. RETAIL DOORD UNDER ARCADE ALONG 4TH STREET SHALL BE
 SETBACK. ARCADE SHALL BE 10' CLEAR BETWEEN COLUMN AND
 WALL WITHOUT ANY DOOR INTRUSION.
 5. COLUMNS AT BUILDING ENTRANCE ARE NOR ALLOWED TO LAND
 ON THE ROW (SIDEWALK OR ROAD) ACCORDING WITH SITE PLAN
 APPROVAL, 4TH STREET SHALL BE TREATED AS A PUBLIC ROW.
 6. SECOND FLOOR MEETING ROOM AND BUSINESS CENTER SHALL
 BE REMOVED. ONLY RESIDENTIAL USES ARE ALLOWED ABOVE THE
 1ST STORY.
 7. PLEASE PROVIDE EAST ELEVATION.
 8. DUE TO CONDITIONS IMPOSED BY THE DAC PARKING
 VARIANCE APPROVAL, AND THE FACT THAT THE SUBJECT PERMIT
 IS ONLY FOR ONE PORTION OF THE PROJECT, ADDITIONAL
 CONDITIONS WILL BE IMPOSED TO ENSURE THE COMPLIANCE
 WITH THE PARKING REQUIREMENTS. PLEASE CONTACT ANA MARIA
 APONTE, CITY URBAN DESIGNER AT 561-8221439 FOR FURTHER
 DISCUSSION.
 9. ARCHITECTURAL DRAWING 2.14 IS MISSING.
 10. PLEASE PROVIDE DETAIL DRAWINGS FOR THE OPEN SPACE
 INCLUDING FLOOR MATERIALS, LOCATION OF DRINKING
 FOUNTAIN, SEATING AREAS, LIGHTING AND LANDSCAPE. 11. IN
 REPLACEMENT OF STREET TREES ALONG 4TH STREET, PLEASE
 PROVIDE LANDSCAPE IN MOVABLE POTS.
 12. PLEASE PROVIDE LANDSCAPE DRAWINGS. THEY WE NOT
 INCLUDED IN THE SET SUBMITTED.
 13. ACCORDING WITH THE ROSEMARY ELEVATION, THE
 DECORATIVE OR WATER ELEMENT ON THE BACK OF THE STAIRS
 HAS A PORTION INTRUDING INTO THE SIDEWALK. SIDEWALK
 SHALL BE 10' CLEAR. PLEASE CLARIFY.
 14. AC LOUVERS SHALL BE PAINTED THE SAME COLOR OF THE
 FACADE TO MINIMIZE IMPACT.