Plan Review Details - Permit 08010591
Plan Review Stops For Permit 08010591
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-22 Cont ID  
Sent By shill Date 2008-02-22 Time 16:49 Rev Time 0.00
Received By shill Date 2008-02-22 Time 16:49 Sent To  
Notes
2008-02-22 16:49:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 2.)AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, SPECIAL
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING AND
 FOR ALL SUBSEQUENT SUBMITTALS.SEE FBC*109.3.6.
  
 3.)THRESHOLD INSPECTION PLAN REQUIRED, FBC*1009.3.6.
  
 4.)SEE FBC*109.3.6.4.4 AND INCLUDE THE STATEMENT
 ATTESTING TO COMPLIANCE.
  
 5.)SEPARATE PERMITS WILL BE REQUIRED FOR THE
 AWNINGS.
  
 6.)CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE
 ARCHITECTURE THROUGH A COMPANY, FS481.219(2).A
 LICENSE NUMBER WAS PRINTED ON THE COVER SHEET BUT I WAS
 UNABLE TO LOCATE THIS NUMBER ON THE WEBSITE
 WWW.MYFLORIDALICENSE.COM (AA-C000288).I?VE PUT IN AN
 INQUIRY TO THE STATE; THIS COMMENT WILL BE REMOVED WHEN
 THE NUMBER IS CONFIRMED.
  
 7.)THE CERTIFICATE OF AUTHORIZATION FOR THE
 ARCHITECTURE FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC61G16-23.002, 003.
  
 8.)CERTIFICATE OF AUTHORIZATION REQUIRED TO PRACTICE
 ENGINEERING THROUGH A COMPANY, FS471.023 (COMMENT
 APPLIES TO TRO JUNG BRANNEN).
  
 9.)THE CERTIFICATE OF AUTHORIZATION FOR THE
 ENGINEERING FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC6G15-23.002.
  
 10.)IN DECLARING GOVERNING CODE, PLEASE REVISE TO
 INCLUDE 2007 REVISIONS WHICH BECAME EFFECTIVE JULY 1,
 2007.
  
 11.)A100, PROVIDE AREA INCREASE CALCULATIONS ON THE
 PLAN.THE PLANS STATE TOTAL SQUARE FOOT AREA, BUT
 COMPLIANCE WITH FBC TABLE 503 IS REQUIRED.STATE TOTAL
 EXISTING SQUARE FOOT AREA FOR EACH FLOOR, TOTAL
 PROPOSED, NEW TOTALS.
  
 12.)I2 HAS BEEN DECLARED AS OCCUPANCY CLASSIFICATION.
 SEE FBC302.1.THIS BUILDING APPEARS TO BE A MIXED
 OCCUPANCY DUE TO THE ASSEMBLY AND BUSINESS AREAS.NOTE
 SEPARATE OCCUPANCIES ON THE PLAN, SQUARE FOOT AREA PER
 FLOOR FOR EACH OCCUPANCY, AND SHOW COMPLIANCE WITH FBC
 TABLE 503.
  
 13.)CLARIFY FIRE RATED WALLS AND OCCUPANCY
 SEPARATIONS.FOR INSTANCE, SEE A201A.A TWO HOUR WALL
 IS SHOWN, BUT THE FOOD STAGING AND DISH WASH AREAS IN
 THE SAME FIRE AREA AS OFFICE AND STAFF LOCKERS.NO
 RATED WALL SHOWN AT THE CORRIDOR OR BETWEEN FOOD
 STAGING, CORRIDOR AND I2 AREAS.OCCUPANCY SEPARATIONS
 SHOULD SEPARATE THE DIFFERENT OCCUPANCIES UNLESS A NON
 SEPARATED USE.PLEASE SEE FBC302 AND CLARIFY
 REQUIREMENTS.THIS IS USUALLY INCLUDED ON A LIFE
 SAFETY PLAN.REQUIRED OCCUPANCY SEPARATIONS ARE NOT
 CLEAR.
  
 14.)PLEASE PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER
 10.
  
 15.)ACCESSIBLE PARKING SPACE, A100, IS TO INCLUDE THE
 FINE, FBC11-4.6.4.
  
 16.)STAFF TOILET ROOM 125, TO BE ACCESSIBLE.SEE
 FBC11-4.1.3(11).
  
 17.)THE ROOM MARKED CUST 133 APPEARS TO BE A WORK
 AREA.WORK AREAS ARE TO BE DESIGNED SO THAT
 INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE AREA, FBC11-4.1.1(3).
  
 18.)SHOW MANEUVERING CLEARANCE, PULL SIDE, FOR THE
 FOLLOWING DOORS:
  
 PASS 121 TO CORRIDOR 120.
 DIRECTORS OFFICE 126
 MULTIPURPOSE ROOM 116
  
 19.)A201R, 1 HOUR FIRE RESISTANCE RATING NOTED FOR
 THE ROOF.ON THE PLAN, SHOW ALL REQUIRED FIRE
 RESISTANCE FBC TABLE 601.
  
 20.)PRODUCT APPROVALS REQUIRED:
  
 MODIFIED ROOF
 DURALOC METAL ROOF
 HARDISOFFIT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 10:29 Sent To  
Notes
2008-02-11 10:29:42** DENIED REVIEW **
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW OR IN DESIGN AS REQUIRED THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE POSSIBLY MADE AT THIS TIME.
  
 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES ARE
 REQUIRED TO BE STATED ON PLANS INCLUSIVE OF ELECTRICAL
 AS WELL AS ARCHITECTURAL SHEETS.
 2004 FBC W/2007 REVISIONS/SUPPLEMENTS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE LICENSE INFORMATION IN TITLE BLOCKS
 FOR ARCHITECTURAL/ENGINEER FIRM TRO/ JUNG/BRANNEN PER
 FLORIDA ADMINISTRATIVE CODES 61G1-16.004 (ARCH) AND
 61G15-23.002 (ENG). PLEASE SEE MISSING LICENSES KNOWN
 AS CERTIFICATE OF AUTHORIZATION NUMBERS AS REQUIRED PER
 FLORIDA STATUTES 481.219 (ARCH) AND 471.023 (ENG).
 PLEASE SEE THIS COMMENT IS NOT FOR FORNEY ENGINEERING
 INC. ALTHOUGH INFORMATION IS STILL REQUIRED ON MEP
 SHEETS AS WELL DUE TO TITLE BLOCKS AS SUBMITTED.
  
 3) NOTE: PLEASE SEE THAT IF BUILDING CONTAINS A FIRE
 ALARM SYSTEM, PLEASE INCLUDE LOCATIONS FOR ALL
 HORN/STROBE DEVICES AS REQUIRED PER FBC 11-4.28.1,.2
 AND .3(4). PLEASE ALSO SEE NFPA-72
 PLEASE INCLUDE NOT ONLY LOCATIONS BUT THE MINIMUM
 LEVELS FOR ADA COMPLIANCE AS GIVEN.
 ** BUILDING DOES APPEAR TO BE A BUILDING WHICH HAS A
 REQUIRED SYSTEM.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS FOR ALL
 NEW LIGHTING CONTROLS BEING INSTALLED PER 13-415.1.ABC
 .1.1, .1.2, .1.3 AND .1.4.
 PLEASE SEE .1.1-.1.3 FOR INTERIOR LIGHTING AND .1.4 FOR
 EXTERIOR. EXTERIOR LIGHTING REQUIRES ONE OF TWO TYPES
 OF CONTROL FOR MINIMUM COMPLIANCE. (MAY BE BOTH) PLEASE
 SEE THAT THE PLANS DO NOT SHOW AN ASTRONOMICAL TIME
 CLOCK WITH THE 10HR BATTERY BACK UP AS NEEDED.
 ** PLEASE BE SURE ALL DEVICES OR SYSTEM DEPENDING ON
 DESIGN CONTAINS ALL MAXIMUM TIMES ON DEVICES, OVER
 RIDES AND ANY TIMED SCHEDULING.
 ** AS NO SYSTEM OR DEVICES ARE SHOWN, NO REVIEW OF
 THESE CAN BE DONE.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS REQUIRED PER 13-415.2. PLEASE BE SURE
 TO SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR EXTERIOR
 LIGHTING.
 PLEASE BE SURE TO COORDINATE ALL LIGHTING ON PLANS WITH
 THAT OF THE FIXTURE LEGEND AND THE CALCULATIONS TO BE
 SUBMITTED.
 PLEASE SEE 13-415.1.B, 13-415.1.C.
  
 6) NOTE: PLEASE SEE KEYED NOTES ON RISER ARE NOT
 COMPLETE FOR NEW FEEDERS ON ALL CONDUITS. THIS CAN NOT
 BE ASSUMED.
 PLEASE COMPLETE.
 240.4, 310.16 ETC
 FBC 106.3.5.1.2
  
 7) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS NOT
 ONLY FOR NEW ADDING TO EXISTING SERVICE AS REQUIRED PER
 220.87 BUT ALSO FOR THE CONTINUOUS LOADS WHICH ARE
 REQUIRED TO BE SHOWN AT 125%. 215.3, 230.42 ETC.
  
 8) NOTE: PLEASE SEE 210.8B2 FOR 15/20AMP 120VOLT
 RECEPTACLES IN KITCHEN AREAS WHETHER OR NOT THEY FEED
 COUNTER SPACE RECEPTACLES OR WHETHER OR NOT THEY ARE
 LOCATED WITHIN 6FT OF ANY SINKS.
  
 9) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINLY.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW IF
 THERE ARE ANY QUESTIONS; PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-17 Cont ID  
Sent By mawillia Date 2008-03-17 Time 13:47 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 16:16 Sent To  
Notes
2008-03-17 13:46:00*****DENIED*****
  
  
 1.THE ADDRESS FOR THE SCOPE OF WORK LOCATION SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.PROVIDE THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR
 THE NEW ONE STORY MULTI-PURPOSE ROOM AND THE NEW ONE
 STORY DINING ROOM.
  
 4.SPECIFY THE INTERIOR WALL AND CEILING FINISH FOR
 THE NEW AND RENOVATED AREAS IN TERMS OF CLASS A, CLASS
 B, OR CLASS C.
  
 5.SPECIFY THE INTERIOR FLOOR FINISH FOR THE NEW AREAS
 IN TERMS OF CLASS I OR CLASS II.
  
 6.PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES
 TO THE EXITS.
  
 7.SHOW THE LOCATIONS OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFIY THE 75' TRAVEL DISTANCE.
  
 8.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM FOR THE
 PROPOSED SCOPE OF WORK.PLEASE BE ADVISED THAT
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE
 ALARM/FIRE SPRINKLER REMODEL OR INSTALLATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET)
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-17 Cont ID  
Sent By mawillia Date 2008-03-17 Time 13:47 Rev Time 0.00
Received By mawillia Date 2008-01-31 Time 14:32 Sent To  
Notes
2008-01-31 14:55:31TO "COMM" BD#1--PLANS ON RACK/3 ROLLS
2008-01-31 14:33:501/31/08--PLANS ROUTED TO INCOMING TODAY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By hmoser Date 2008-03-11 Time 09:10 Rev Time 0.00
Received By hmoser Date 2008-03-11 Time 09:10 Sent To  
Notes
2008-03-11 09:38:35PLAN DENIED
 1)PLEASE PROVIDE DUCT SIZES ON ALL DUCTS AND GRILLS
 ON PLANS .
 2)PLEASE PROVIDE BATH EXHAUST AND TERMINATION OF
 EXHAUEST DUCT ON PLANS .SECTION 402.3.1 2004 FBC (M).
 3)PLEASE SUBMIT A COPY OF MANUFACTURERS INSTALLATION
 INSRUCTIONS ON THE AIR CONDITIONING EQUIPNENT WITH THE
 PLANS .
 4)PLEASE SUBMIT ENERGY CALCULATIONS WITH THE
 PLANS.SECTION 13-400.0.A
 5)PLEASE REFER TO MUNICIPAL CODE ARTICLE 3 SECTION
 90-125 PROHIBITIONS AND LIMITATIONS OF DISCHARGE ( B)
 (5). (CAN NOT TIE A/C CONDENSATE IN A FLOOR DRAIN) 6)
 PLAESE EXPLAIN WHAT DUCT IS 32 X16 AND 18 X16 WITH
 INSULATION IS. PAGE M1 ON MECHANICAL PLANS.
 7) PAGE M4 MECHANICAL SPECIFICATIONS NOTE # 9
 FIBERGLASS DUCT CAN NOT BE PAINTED SECTION 604.3 FBC
 (M) 2004

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By kstevens Date 2008-02-26 Time 18:34 Rev Time 0.00
Received By kstevens Date 2008-02-25 Time 15:57 Sent To  
Notes
2008-02-26 18:57:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECT TRO JUNG BRANNEN TITLE
 BLOCK. THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), AND THE DATE THE PLANS ARE PREPARED ARE
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2)(4) AND FS 481.219, 481.2055.
  
 2. PLANS SHOW DEMOLITION OF EXISTING FLOOR PLANS, (1ST
 & 2ND) AND A NEW PORTE COCHERE. THIS IS NOT INDICATED
 ON THE PERMIT APPLICATION WHICH STATES "DESCRIBE
 PROJECT IN DETAIL". PLEASE INDICATE ALL WORK ON THE
 APPLICATION THAT WILL BE PERMITTED AT THIS TIME. ALSO
 INDICATE THE SQUARE FOOTAGE OF THE ADDITIONS. (SEE
 INFORMATION REQUIRED ON APPLICATION.
  
 3. IN THE INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. ON SHT P2 THERE APPEAR TO BE DEAD ENDS STILL IN
 THE SANITARY SYSTEM.
  
 4. THE STAFF TOILET SHALL BE ACCESSIBLE PER SECTION
 11-4.1.3(11). SUBMIT A DETAIL FOR ALL TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 5. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN.
  
 6. SHT P2 DETAILS P1 & P2 THE GREASE TRAP IS NOT
 APPROVED. PER ARTICLE III SECTION 90-124(7)(B) GREASE
 INTERCEPTORS ARE TO BE INSTALL OUTSIDE WITH THE
 DISHWASHER DISCHARGING VIA A SEPARATE LINE. THE GREASE
 INTERCEPTOR SHALL BE CONSTRUCTED OF STEEL REINFORCED
 CONCRETE PER ARTICLE III SECTION 90-124(7)(F). THE
 GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT RODNEY COMPO (561) 644-1821 OR BY FAX
 (561) 822-2287 OR BY E-MAIL [email protected].
  
 7. SHT P2 INDICATE WHAT WILL BE DRAINING INTO THE FD-B
 IN THE MECHANICAL ROOMS. A TRAP SEAL SHALL BE INSTALLED
 WHERE THE TRAP IS SUBJECT TO EVAPORATION. CONDENSATE
 SHALL NOT DRAIN INTO THE SANITARY SYSTEM. ARTICLE III
 SECTION 90-125(5).
  
 8. SHT P2 A VENT IS REQUIRED FOR THE FD-B IN MECHANICAL
 ROOM 115.
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY HEALTY UNIT
 DIVISION OF ENVIRONMENTAL HEALTH, 901 EVERNIA STREET
 WEST PALM BEACH FOR REVIEW PRIOR TO RESUBMITTING FOR
 REVIEW AT THE CITY WPB.SECTION 102.2.1. PLANS SHALL
 BE STAMPED FOR REVIEW BY THE HEALTH DEPT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By bpowell Date 2008-02-13 Time 08:23 Rev Time 0.00
Received By bpowell Date 2008-02-13 Time 08:23 Sent To  
Notes
2008-02-13 08:26:161. A LANDSCAPE PLAN SHALL BE INCLUDED WITH THE PERMIT
 PACKET AS IT WAS REQUIRED FOR SITE PLAN REVIEW.
  
 2. A TREE ALTERATION PERMIT SHALL BE COMPLETED AND
 APPROVED.
  
 3. THE SITE PLAN HAS AN ERROR IN THE DATA TABLE. THE
 TABLE SHOWS THE PROPOSED NUMBER OF ONE (1) BEDROOM
 UNITS AS 57 AND TWO (2) BEDROOM UNITS AS 12 TOTALING 74
 FOR THE MARLBERRY BUILDING.THE ADDITION IS
 INCORRECT.
  
 4. A CONCRETE PAD IS SHOWN ON THE NORTH SIDE OF THE
 EXPANSION OF THE MARLBERRY BUILDING ON SEVERAL
 DIFFERENT PAGES OF THE PLANS.THIS PAD IS NOT ON THE
 APPROVED PLANS AND IT WILL BE IN DIRECT CONFLICT WITH
 THE LANDSCAPING.
  
 5. THE AIR CONDITIONING UNITS WILL BE IN DIRECT
 CONFLICT WITH THE APPROVED LANDSCAPING.
  
 PLEASE CONTACT BOBBY POWELL JR., WITH ANY QUESTIONS OR
 COMMENTS. (561) 822-1401, [email protected]