Plan Review Details - Permit 08010544
Plan Review Stops For Permit 08010544
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By btrobaug Date 2008-02-28 Time 07:53 Rev Time 0.00
Received By btrobaug Date 2008-02-28 Time 07:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By btrobaug Date 2008-01-29 Time 16:18 Rev Time 0.00
Received By btrobaug Date 2008-01-29 Time 14:21 Sent To I
Notes
2008-01-29 16:18:14 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1, .AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 240.4(C) DEVICES RATED OVER 800 AMPERES: WHERE THE
 OVERCURRENT DEVICE IS RATED OVER 800 AMPERES, THE
 AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE EQUAL
 TO OR GREATER THAN THE RATING OF THE OVERCURRENT DEVICE
 DEFINED IN 240.6. THE FOUR- 250 MCM SHOWN FEEDING THE
 1200 AMP MAIN DO NOT COMPLY WITH THIS ARTICLE. PLEASE
 FIELD VERIFY THE DESCRIBED CONDITIONS ARE CORRECT.
 ALTHOUGH THE SERVICE IS EXISTING THE NON CONFORMITY
 CANNOT BE ALLOWED TO CONTINUE WITH NEW WORK ON THE
 SERVICE BEING PROPOSED.
  
 2} THE "FINAL 1-LINE DIAGRAM" INDICATES DICONNECTING
 THE EXISTING GROUNDING ELECTRODE CONDUCTOR SYSTEM AND
 REPLACING IT WITH A SINGLE GROUND ROD. PROVIDE A
 DIAGRAM OF THE EXISTING GEC SYSTEM, FIELD VERIFY
 CONDITIONS. ALL THE EXISTING ELECTRODES THAT COMPRISE
 THE SYSTEM PER 250.50 MUST BE REUSED, ESPECIALLY
 250.52(A)(3) CONCRETE ENCASED, IF AVAILABLE.
  
 3} IT WOULD APPEAR THAT IN THE EXISTING SERVICE THERE
 ARE 7 MEANS OF DISCONNECT, IN VIOLATION OF ARTICLE
 230.71. PLEASE FIELD VERIFY AND CLARIFY THE PLAN.
  
 SUBMIT WRITTEN RESPONSE TO THE COMMENTS MADE IN THIS
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 15:35 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 15:35 Sent To E
Notes
2008-02-20 15:35:52TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-29 Cont ID  
Sent By btrobaug Date 2008-01-29 Time 16:18 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 10:40 Sent To PC
Notes
2008-01-24 10:42:54TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved