| 2008-01-24 10:35:39 | 2004 FBC W/2007 REVISIONS |
| | INSTALL ROOF NEW CONSTRUCTION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE TAMKO MODIFIED SYSTEM SPECIFIED ON PAGE 6 OF NOA |
| | 07-0111.03 IS FOR INSULATED WOOD DECKS AND IS NOT THE |
| | ONE THAT WAS APPROVED WITH THE MASTER PERMIT. THE ONE |
| | THAT WAS APPROVED IS ON PAGE 17 AND IS FOR |
| | NON-INSULATED WOOD DECKS. THEREFORE, RAS 117 ENHANCED |
| | FASTENING CALCULATIONS FOR THE NEW SYSTEMS ANCHOR SHEET |
| | IS REQUIRED TO BE SUBMITTED. THE APPLICATION SPECIFIES |
| | 1/4" TAPERED INSULATION TO BE INSTALLED AND THE |
| | ASSEMBLY SELECTED ON PAGE 6 OF THE NOA REQUIRES A |
| | MINIMUM 1/2" THICK INSULATION. PLEASE REVISE AND |
| | SPECIFY WHICH ONE OF THE LISTED INSULATIONS WILL BE |
| | USED. |
| | |
| | 2) THE HYDRO-STOP LIQUID APPLIED MEMBRANE ROOFING THAT |
| | WAS SUBMITTED IS NOT THE PRODUCT ( SEALOFLEX NOA NO. |
| | 05-0901.04) THAT WAS APPROVED WITH THE MASTER PERMIT. |
| | THE PRODUCT APPROVAL SUBMITTED FOR THE HYDRO-STOP |
| | REQUIRES INSULATION FOR ALL APLICATIONS. SPECIFY THE |
| | SYSTEM AMD DESIGN PRESSURE FOR THE ASSEMBLY THAT WILL |
| | BE INSTALLED. SUBMIT SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING FROM A FLORIDA |
| | REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT AS REQUIRED BY LIMITATION #7 ON PAGE 8 OF |
| | THE PRODUCT APPROVAL. |
| | |
| | 3) SUBMIT PRODUCT APPROVAL FOR THE POLYGLASS TU PLUS. |
| | |
| | 4) PRODUCT APPROVALS THAT ARE SUBMITTED WHICH ARE |
| | DIFFERENT FROM THE APPROVED ONES WILL BE CHARGED A |
| | REVISION FEE. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |