Plan Review Details - Permit 08010526
Plan Review Stops For Permit 08010526
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By lursu Date 2008-03-07 Time 08:50 Rev Time 0.00
Received By lursu Date 2008-03-07 Time 08:50 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-01-30 Cont ID  
Sent By lursu Date 2008-01-30 Time 08:18 Rev Time 0.00
Received By lursu Date 2008-01-30 Time 08:17 Sent To PC
Notes
2008-01-30 08:17:58PLEASE CLARIFY THE LOCATION JOB ,WHICH TOWER EAST OR
 WEST AND THE SUITE NUMBER .
  
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-02 Cont ID  
Sent By mjacobs Date 2008-05-02 Time 16:05 Rev Time 0.00
Received By mjacobs Date 2008-05-02 Time 11:10 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-06 Cont ID  
Sent By mjacobs Date 2008-03-06 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2008-03-06 Time 12:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-30 Cont ID  
Sent By mjacobs Date 2008-01-30 Time 12:53 Rev Time 0.00
Received By mjacobs Date 2008-01-30 Time 10:06 Sent To  
Notes
2008-01-30 14:41:05 
 THE DRAWINGS SEEMS TO BE OK AT THIS TIME OF REVIEW.
 UNTIL A CONTRACTOR IS HIRED AND A VALUE IS INDICATED
 THE PLANS WILL HAVE A 'FAILED' STATUS. THE VALUE OF THE
 PROJECT SHALL ALSO BE INDICATED.
 INDICATE THE SUITE /UNIT NUMBER ON THE APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-29 Cont ID  
Sent By btrobaug Date 2008-04-29 Time 10:14 Rev Time 0.00
Received By btrobaug Date 2008-04-29 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-05 Cont ID  
Sent By btrobaug Date 2008-03-05 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2008-03-05 Time 12:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By dpalmer Date 2008-01-29 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2008-01-29 Time 20:06 Sent To  
Notes
2008-01-29 20:06:53** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW PLANS HAVE ONLY BEEN SUBMITTED FOR
 *PLAN REVIEW * ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
 PLEASE KNOW EVEN ONCE PLANS ARE CODE COMPLIANT MEETING
 COMMENTS FROM REVIEWER(S), PLANS WILL NOT BE STAMPED
 AND REVIEW WILL REMAIN IN A FAILED STATUS UNTIL PERMIT
 APPLICATION HAS BEEN MADE.
  
 2) NOTE: PLEASE KNOW THE ADDRESSING FOR UNIT/SUIT IS
 YET TO BE DETERMINED. PLEASE KNOW AS THIS IS AN
 EXTENSION TO AN EXISTING TENANT PLEASE OBTAIN EXISTING
 SUITE/UNIT NUMBER AND CONFIRM WITH THIS OFFICE AND
 ADDRESSING REVIEWER. PLEASE KNOW THE INFORMATION WAS
 SENT TO THE ADDRESSING REVIEWER AS OF THIS REVIEW.
 PLEASE BE SURE ALL TITLE BLOCKS CONTAIN THE ADJUSTED
 SUITE/UNIT LOCATION ONCE DETERMINED.
 PLEASE SEE LOCATION FOR EAST OR WEST TOWER LOCATION
 ALSO NEEDS TO BEAPPLIED.
 FBC 106.5, 106.1.2 ADMIN SECTION.
 FAC 61G15-23.002, 61G1-16.002
  
 3) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON PLANS
 FOR 277/480V SYSTEMS SHALL BE BROWN, PURPLE, YELLOW.
 THE *ORANGE* COLOR AS SPECIFIED ON THE PLANS IS FOR A
 DELTA HIGH-LEG SYSTEM WHICH THIS IS NOT.
 THIS WAS A LOCAL AMENDMENT FOR THIS AND OTHER LOCAL
 JURISDICTIONS AND WIRING METHOD IN THIS AND OTHER
 EXISTING BUILDING CONTAIN THE COLOR CODING AS MENTIONED
 ABOVE.
 THIS REMAINS A REQUIREMENT PER 90.4 DUE TO EXISTING
 WIRING METHODS FOR SAFETY.
  
 4) NOTE: PLEASE SEE THE METHOD *B* ENERGY CALCULATIONS
 SUBMITTED DO NOT CONTAIN THE INPUT DATA REPORT(S) IN
 ANY OF THE THREE COPIES SUBMITTED.
 PLEASE SEE SHEET #2 OF THE SUMMARY AS THIS SPECIFICALLY
 STATES THE INPUT DATA REPORT MUST ACCOMPANY
 CALCULATIONS.
 PLEASE KNOW AS THERE WERE NOT SUBMITTED NO REVIEW OF
 THE ITEMS ON THE IDR CAN BE DONE AND COORDINATED WITH
 THE SUBMITTED PLANS AND FIXTURE LEGEND.
 PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD. THE SHEET
 WAS SIGNED, AND DATED HOWEVER DID NOT GET SEALED.
 PLEASE ALSO SEE THE OWNER AGENT SIGNATURE IS MISSING ON
 THIS SAME SHEET.
 13-415.1.B, 13-415.2, 13-103.1, 13-103.1.1,
 13-103.1.1.1
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEW TRADES.
  
 5) NOTE: PLEASE STATE MAXIMUM TIMES ON ALL OCCUPANCY
 SENSOR TYPE DEVICES PER 13-415.1.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE NOTE ON E.02 MENTIONS RELOCATION OF
 THE TRANSFORMER. PLEASE SHOW AND INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR WHICH WILL MOST LIKELY BE REQUIRED
 TO BE NEW DUE TO RELOCATION.
 PLEASE SEE 250.66, 250.50, 250.30, 250.50
  
  
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-21 Cont ID  
Sent By mwennerg Date 2008-05-21 Time 15:51 Rev Time 0.00
Received By mwennerg Date 2008-05-21 Time 15:51 Sent To M
Notes
2008-05-21 15:52:57WORK TO COMPLY WITH UL 555 REQUIREMENTS. FIRE DAMPER
 SHALL BE TESTED FOR CLOSURE PRIOR TO FINAL INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-30 Cont ID  
Sent By mwennerg Date 2008-04-30 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2008-04-30 Time 11:11 Sent To  
Notes
2008-04-30 11:11:50REVISION TO FP.01 REMOVED (1) SHEET FOR FILES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-05 Cont ID  
Sent By mawillia Date 2008-03-05 Time 16:27 Rev Time 0.00
Received By mawillia Date 2008-03-05 Time 15:59 Sent To  
Notes
2008-03-05 16:27:52*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS A0.03, A2.09, A4.09, A5.09,
 FP.01, AND E.02 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By mawillia Date 2008-02-06 Time 16:29 Rev Time 0.00
Received By mawillia Date 2008-02-06 Time 15:37 Sent To  
Notes
2008-02-06 16:22:21*****DENIED*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET. ALSO INDICATE EAST OR WEST
 TOWER.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO SHEET AD1.09
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE.
  
 6.INDICATE AS TO WHETHER THERE HAS BEEN ANY
 ALTERATION TO FIRE ALARM DEVICES SHOWN ON SHEET E.02 IN
 THE POWER & MISC. SYSTEMS PLAN.BE ADVISED THAT
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE FIRE
 ALARM REMODEL,
  
 7.NFPA 13, STANDARD FO THE INSTALLATION OF SPRINKLER
 SYSTEMS, 2002 EDITION SHALL BE REFERENCED.AMEND NOTE
 #12 ON SHEET FP.01
  
 8.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED.AMEND NOTE #13 ON SHEET FP.01
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 15:30 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 15:30 Sent To M
Notes
2008-06-09 15:30:26TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 11:26 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 11:26 Sent To FIRE
Notes
2008-05-14 11:27:09TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 14:10 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 14:10 Sent To  
Notes
2008-04-22 14:13:26TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 10:35 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 10:35 Sent To  
Notes
2008-03-04 10:35:38TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-06 Cont ID  
Sent By mawillia Date 2008-02-06 Time 15:37 Rev Time 0.00
Received By mawillia Date 2008-01-24 Time 11:56 Sent To  
Notes
2008-01-24 11:58:54TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-06-10 Cont ID  
Sent By tgordon Date 2008-06-10 Time 11:07 Rev Time 0.30
Received By tgordon Date 2008-06-10 Time 11:07 Sent To  
Notes
2008-06-10 11:08:09RECIVED REVISION SHEET SKM-1 DATED 6-5-08.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-22 Cont ID  
Sent By tgordon Date 2008-05-22 Time 08:45 Rev Time 0.30
Received By tgordon Date 2008-05-22 Time 08:45 Sent To  
Notes
2008-05-22 08:47:12REVISION RECIVED SHEET NO. SKM-1 AND SKM-2. DATED
 5-2-08 (TRANSFRE DUCT WITH FIRE DAMPER).

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-24 Cont ID  
Sent By tgordon Date 2008-04-24 Time 10:36 Rev Time 0.30
Received By tgordon Date 2008-04-24 Time 10:36 Sent To  
Notes
2008-04-24 10:36:47REVISION TO MECH. PLAN M.02.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-05 Cont ID  
Sent By tgordon Date 2008-03-05 Time 11:43 Rev Time 0.25
Received By tgordon Date 2008-03-05 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-25 Cont ID  
Sent By tgordon Date 2008-01-25 Time 09:33 Rev Time 0.30
Received By tgordon Date 2008-01-25 Time 09:33 Sent To  
Notes
2008-01-25 09:37:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 FOR PLAN REVIEW ONLY NOT FOR PERMIT.
  
 1) MECHANICAL PLANS ARE OK AT THIS TIME. WILL NEED TO
 HAVE A LICENSED CONTRACTOR SUBMIT A PERMIT
 APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2008-03-04 Cont ID  
Sent By choops Date 2008-03-04 Time 13:45 Rev Time 0.00
Received By choops Date 2008-03-04 Time 13:45 Sent To  
Notes
2008-03-04 13:45:59*ZONING REVIEW NOT REQUIRED; INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 08:14 Rev Time 0.00
Received By choops Date 2008-01-28 Time 08:14 Sent To  
Notes
***NONE***