Plan Review Details - Permit 08010516
Plan Review Stops For Permit 08010516
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 18:09 Rev Time 0.00
Received By shill Date 2008-04-01 Time 18:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-13 Cont ID  
Sent By shill Date 2008-03-13 Time 09:11 Rev Time 0.00
Received By shill Date 2008-03-13 Time 09:11 Sent To  
Notes
2008-03-13 09:17:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM FIRST LIST:
  
 1.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR SCHEDULE.IN THIS CASE, IT
 IS FOUND ON SHEETS 10-11.IT APPEARS THAT YOU ARE
 USING WALL MOUNT 1.THIS CAN BE DETERMINED BECAUSE YOU
 HIGHLIGHTED IT ON THE PRODUCT APPROVAL.HOWEVER, IF
 YOU ARE GOING TO MARK THE PRODUCT APPROVAL TO SHOW CODE
 COMPLIANCE, PLEASE USE INK RATHER THAN HIGHLIGHTER AS
 HIGHLIGHTER DOES NOT APPEAR WHEN SCANNED.
  
 3.FROM PREVIOUS LIST, FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.WWW.FLORIDABUILDING.ORG.
  
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVAL FROM
 THE WEBSITE.
  
 4.TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED, FBC*106.
  
 ONLY ONE INSTALLATION SCHEDULE WAS PROVIDED.TWO
 COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR PERMIT
 ISSUANCE.DUE TO WORKLOAD, I AM UNABLE TO MAKE COPIES
 FOR CONTRACTORS.PRIOR TO RESUBMITTAL, PLEASE CHECK
 THE PACKAGE TO BE SURE THAT THERE ARE TWO COMPLETE,
 COLLATED SETS OF PERMIT DOCUMENTS FOR PERMIT ISSUANCE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-20 Cont ID  
Sent By shill Date 2008-02-20 Time 15:20 Rev Time 0.00
Received By shill Date 2008-02-20 Time 15:20 Sent To  
Notes
2008-02-20 15:50:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHUTTER CONNECTION MOUNTING TYPE ON THE
 INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE ANCHOR
 CHARTS (AROUND SHEET16; CANNOT READ ON THE PRODUCT
 APPROVALS PROVIDED) .IN THIS CASE, THIS SHOULD BE A
 THROUGH L.
  
 2.IT IS HELPFUL IF PRODUCT APPROVALS ARE COMPLETE.
 THE PRODUCT APPROVALS PROVIDED HAVE THE PAGE NUMBERS
 CUT OFF, SO I CANNOT REFER TO THEM IN MY PLAN REVIEW
 COMMENTS.I WOULD REPRINT IT FROM THE INTERNET, OR USE
 THE INTERNET AS REFERENCE, BUT I DON'T KNOW WHICH
 PRODUCT APPROVALS YOU'VE SUPPLIED AS THEY DO NOT HAVE
 THE FLORIDA NUMBER.SEE OTHER COMMENTS.PLEASE
 PROVIDE PRODUCT APPROVALS WHICH ARE COMPLETELY LEGIBLE,
 INCLUDING PAGE NUMBERS.
  
 3.FROM PREVIOUS LIST, FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.WWW.FLORIDABUILDING.ORG.
  
 4.TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED, FBC*106.
  
 5.A .83 FACTOR IS TO BE APPLIED TO ANCHOR SPACING
 WHEN THE EDGE DISTANCE IS LESS THAN 3 1/2".I'VE
 HIGHLIGHTED THIS NOTE IN THE PRODUCT APPROVAL BUT
 CANNOT DETERMINE WHICH PAGE IT IS LOCATED ON.IT CAN
 BE FOUND ON THE SAME PAGE AS THE ANCHOR CHART WITH FGH.
 I CANNOT DETERMINE WHETHER OR NOT THE ANCHOR SPACING
 SPECIFIED ON THE INSTALLATION SCHEDULE IS CODE
 COMPLIANT DUE TO INSUFFICIENT INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:23 Rev Time 0.00
Received By shill Date 2008-01-25 Time 15:23 Sent To  
Notes
2008-01-25 15:24:52****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 _XX_4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 13:26 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 13:26 Sent To B
Notes
2008-03-11 13:26:53TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:25 Rev Time 0.00
Received By shill Date 2008-01-23 Time 12:22 Sent To  
Notes
2008-01-23 12:22:21TO "MISC" BOX#1