Plan Review Details - Permit 08010510
Plan Review Stops For Permit 08010510
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 12:28 Rev Time 0.00
Received By mawillia Date 2008-02-13 Time 11:40 Sent To  
Notes
2008-02-13 12:17:50******FIRE STAMPED*****
  
  
 PLAN STAMPED, INITIALED, AND DATED;READY FOR PERMIT
 ISSUANCE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-02-13 Cont ID  
Sent By mcarsill Date 2008-02-13 Time 07:30 Rev Time 0.00
Received By mcarsill Date 2008-02-13 Time 07:20 Sent To  
Notes
2008-02-13 07:28:511. BUILDING ADDRESS SHOULD HAVE BEEN NOTED ON THE
 PLANS.
  
 2. NEW FIRE PUMP INSTALLATION TO COMPLY WITH NFPA 20.
 AFTER INSTALLATION, THE FIRE PUMP AND ALL APPURTENANT
 EQUIPMENT SHALL BE TESTED TO ENSURE PROPER OPERATION.
 WHEN THE PRE-TESTING HAS BEEN COMPLETED, ANOTHER TEST
 IS TO BE PERFORMED WITH THE AUTHORITY HAVING
 JURISDICTION WHICH IS THE BUREAU OF FIRE PREVENTION.
  
 3. ALL NEW 21/2" X 2 1/2" X 4" FIRE DEPARTMENT
 CONNECTIONS LOCATED ON THE SIXTH FLOOR LEVEL ON PAGE
 FP2.60 SHALL BE PROPERLY RESTRAINED TO PREVENT VERTICAL
 OR HORIZONTAL MOVEMENT.
  
 4. ALL NEW STANDPIPE RISERS ILLUSTRATED ON THE DRAWINGS
 SHALL ALSO BE PROPERLY RESTRAINED.
  
 5. THE BUILDING IS TO REMAIN UNDER APPROVED FIRE WATCH
 ACTIVITIES UNTIL SUCH TIME AS THE NEW FIRE PUMP
 INSTALLATION IS INSPECTED, TESTED, AND APPROVED BY THE
 BUREAU OF FIRE PREVENTION.
  
 6. THE STANDPIPE SYSTEM SHALL COMPLY WITH NFPA 14.
  
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 09:31 Rev Time 0.00
Received By mawillia Date 2008-01-23 Time 11:00 Sent To  
Notes
2008-01-23 11:01:06TO "F" BOX